When installing the line set:
• Make sure the lines are suitable for use with R410a.
• Do not crush the lines and always allow a minimum bend radius of 2 inches.
• Keep the ends of the lines covered to prevent dirt and debris from entering the lines during installation.
• Secure the line set to the building with isolating hardware to prevent vibration transmission to the building.
• Seal and isolate the opening(s) where the line set is routed into the building.
• Insulate the gas (suction) line to prevent water condensation on the gas line.
• Flush the lines with an inert gas before and/or during brazing to prevent oxidation inside the lines.
• Release the inert gas holding charge and remove the plugs in the dehumidifier lines before brazing.
• Do not overheat the lines connected to the dehumidifier or the condensing unit when brazing.
• Be aware of the relative location of the dehumidifier (Indoor unit) and condensing unit (Outdoor Unit) when
installing the line set.
LINE SET INSTALLATION
30 FT
MAX
CONDENSING
UNIT
DEHUMIDIFIER
30 FT
MAX
CONDENSING
UNIT
OIL TRAP
DEHUMIDIFIER
The maximum allowable elevation
difference between the dehumidifier
and condensing unit is 30 feet.
If the elevation difference
between the dehumidifier and
condensing unit is greater than
16 feet, an oil trap should be
created in the line set.