Ultra-Aire MD33 Installation Instructions

The Ultra-Aire MD33 has an illuminated display, user selectable setpoint, and a power ON / OFF button located 

behind the diffuser. The diffuser is fastened with tamper resistant screws to limit access to the control. The diffuser 

can also be fastened with the included phillips screws if limiting access to the control is not needed. 
When turning power on for the first time, the set point will be at the factory setting of 55% RH. In the event of  

a power outage, the dehumidifier restarts at the previous set point when power is restored.
Pressing the middle button (the power button), the control will toggle the Ultra-Aire MD33 to turn ON or OFF.  
If the unit is on and power button is pressed, control will turn compressor and fan off. As a result, both DISPLAY  

and LED will go off.  
If the unit is off and power button is pressed, control will turn fan on. As a result, both DISPLAY and LED will  

go on. 
If there is an error, the unit will shut down and indicator LED will turn to red and display will show an error code 

(see page 14 for error codes).  

Sequence of Operation

1.  Press the ON 

/

 OFF button to turn the dehumidifier control on. The display will show “00” for a couple of  

seconds and then it will display the RH level of the room and the dehumidifier blower will turn on to start  

sampling the air for one minute.
Indicator LED, located above display, will be green, showing the unit is operating normally.

2.  Pressing either of the arrow keys will cause the DISPLAY to flash and indicate the current set point. The RH set 

point can be adjusted from a minimum of 35% to a maximum of 99% in 1% increments. Adjust the humidity set 

point as desired. The recommended initial setting is 55%.
Pressing the DOWN arrow key below the 35% set point on the control will cause the display to read “00” and 

the Ultra-Aire MD33 will run continuously. After 10 seconds, it will go back to display room RH level.
Ten seconds after making an adjustment, from either UP or DOWN arrow keys, the display will go back to show 

the room RH level.

3.  If the sensor detects a reading above the set point, it will run the fan to sample the return air for a period of one 

minute. The sampled humidity of the return air will be compared to the RH setting. If the humidity is above the 

setting, the dehumidifier compressor turns on. The compressor remains on until the measured humidity falls 3% 

below the RH setting. If the sampled humidity is below the setting, the compressor and blower turn off and the 

display returns to showing the RH setting. The dehumidifier will sample again every 15 minutes.

CONTROLS

Summary of Contents for MD33

Page 1: ...l framing The Ultra Aire MD33 provides the ultimate in comfort health and property protection TS 927 6 18 Rev E P N 4035900 Serial No Install Date Sold by HVAC Installer Please Leave Manual for Homeow...

Page 2: ...rements 7 Dehumidifier Installation 8 Maintenance 12 Air Flow 12 Controls 13 Service 15 Warranty 17 TABLE OF CONTENTS Therma Stor is committed to manufacturing quality products To maintain our standar...

Page 3: ...TRICAL AND PLUMBING CODES MUST BE ADHERED TO FOR PROPER UNIT OPERATION AND WARRANTY COMPLIANCE IMPROPER INSTALLATION MAY CAUSE PROPERTY DAMAGE OR INJURY INSTALLATION SERVICE AND MAINTENANCE MUST BE PE...

Page 4: ...DOIVENT TRE RESPECT S POUR UNE UTILISATION AD QUATE DE CETTE UNIT ET UNE VALIDIT DE LA GARANTIE UNE INSTALLATION NON CONFORME PEUT CAUSER DES DOMMAGES MAT RIELS OU DES BLESSURES TOUTE INSTALLATION TO...

Page 5: ...ted behind tamper proof cover Air Filter 1 2 Washable mounted behind diffuser Dehumidistat Digital tamper proof float switch input Cabinet Galvanized Steel Decibels 46 dBA Drain Connection 3 4 O D Dra...

Page 6: ...ing members or unwanted noise may result Unit is designed to be suspended by side mounting flanges only Drain hose must be routed with downward slope from unit drain connection to appropriate location...

Page 7: ...z AC only 15 amp fused and grounded electrical supply A visible circuit breaker or disconnect switch near the unit is required for maintenance and service A dedicated circuit is recommended Use of a U...

Page 8: ...ER POWER BEFORE BEGINNING INSTALLATION 1 2 Electrical Box Shipping Bracket AVERTISSEMENT FERMEZ LE DISJONCTEUR ALIMENTATION AVANT DE COMMENCER L INSTALLATION Items Included in Box Ultra Aire MD33 Dehu...

Page 9: ...p 3 There are three electrical knock outs one on the back and two on the bottom of the unit Remove appropriate knock out and install non metallic cable clamp with clamp screws inside of unit oriented...

Page 10: ...ng on both sides Additional insulation or sound dampening material not provided may be required if the dehumidifier cabinet contacts the studs especially in applications involving metal studs Fasten t...

Page 11: ...e of the electrical wires are pinched Step 15 Turn breaker power back on Step 16 Set the digital controller to desired RH See Controls Section on page 13 Step 17 Install diffuser cover by aligning the...

Page 12: ...ORD IS DAMAGED IT MUST BE REPLACED BY THE MANUFACTURER ITS SERVICE AGENT OR SIMILARLY QUALIFIED PERSONS IN ORDER TO AVOID A HAZARD AVERTISSEMENT ASSUREZ VOUS QUE L UNIT EST FERM E OU D BRANCH E OU QUE...

Page 13: ...will show 00 for a couple of seconds and then it will display the RH level of the room and the dehumidifier blower will turn on to start sampling the air for one minute Indicator LED located above di...

Page 14: ...after an hour Evaporator Temperature Mode To enter evaporator temperature mode press and hold both arrow buttons for 5 seconds and the LED will change to Blue The display will flash at twice the rate...

Page 15: ...TO PERFORM SOME TESTS THESE TESTS SHOULD BE PERFORMED BY A QUALIFIED SERVICE PERSON MISE EN GARDE LES TRAVAUX DE D PANNAGE NE DEVRAIENT TRE EFFECTU S QUE PAR UN TECHNICIEN CVCA QUALIFI AVERTISSEMENT...

Page 16: ...ning 1 Wiring or connectors loose 2 Blower relay failure 3 Blower capacitor failure 4 Blower failure Check wiring and connectors for damage or loose connections Check power to blower circuit replace p...

Page 17: ...y costs related to changes to a Product or Component that may be required by any codes laws or regulations that may become effective after initial purchase of the Product by Customer Customer Responsi...

Page 18: ...18 Ultra Aire MD33 Installation Instructions www InWallDehumidifier com 800 533 7533...

Page 19: ...19 www InWallDehumidifier com 800 533 7533 Ultra Aire MD33 Installation Instructions...

Page 20: ......

Reviews: