S9600-30DX Hardware Installation Guide | 3
Installation Environment Requirements
•
Power Reserve: The S9600-30DX power supply is available with:
1.
DC Version:
1+1 Redundant and hot swappable -48 voltage DC power supply field
replaceable unit or;
2.
AC Version:
1+1 Redundant and hot swappable 100-240V AC power supply field replaceable
unit.
To ensure the redundant feed power design functions properly, a field with dual power
circuit is recommend with a reserve of at least 1600 watts on each power circuit.
•
Space Clearance: The S9600-30DX width is 17.16 inches (43.6cm) and shipped with a rack
mount brackets suitable for 19 inch (48.3cm) wide racks. The depth of the S9600-30DX
chassis is 30 inches (76.2cm) without the field replaceable units (FRUs) and comes with
adjustable check mounting rails suitable for rack depths of 22 inches (55.9cm) to 33 inches
(83.8cm). The handle for the fan units will extend outwards by 1.15 inch (2.9cm) and the
handle for the power supplies will extend outwards by 1.19 inches (3cm). Therefore, to
accommodate the fan and power supply handles, a minimum space clearance of 6 inches
(15.2cm) is needed at the back of the S9600-30DX. A total minimum reserve depth of 36
inches (91.4cm) is required.
Figure 1.
•
Cooling: The S9600-30DX airflow direction is front-to-back. Make sure the equipment on
the same rack have the same airflow direction.