S9300-32D Hardware Installation Guide | 4
•
Cooling: The S9300-32D has two options for airflow direction. There is a back-to-front
option (Figure 3. Left) and a front-to-back option (Figure 3. Right). Make sure the
equipment on the same rack have the same airflow direction.
(Back-to-Front Airflow)
(Front-to-Back Airflow)
Figure 3.
Figure 4.
Preparation Check List
Task
Check
Date
Power voltage and electric current requirement
DC version
: -40 to -75V DC, 40Ax2 ampere maximum or;
AC version:
200
–
240V, 7.5x2 ampere maximum
Installation spacing and weight load requirement:
S9300-32D
is 1RU (1.75”/4.5cm) in height, 19” (48.3cm) in
width,
and 31.4 inches (79.7cm) in depth without considering cable routing
Thermal requirement
S9300-32D working temperature is 0 to 40°C (32°F to 104°F),
airflow direction is front-to-back or back-to-front
Installation tools required
#2 Phillips Screwdriver, 6-AWG wire stripper, and crimping tool
Accessories required
PC with terminal emulation software