S9180-32X Hardware Installation Guide | 4
•
Cooling: The S9180-32X has two options for airflow direction. There is a back-to-front
option (Figure 3. Left) and a front-to-back option (Figure 3. Right). Make sure the
equipment on the same rack have the same airflow direction.
Back-to-Front Airflow
Front-to-Back Airflow
Figure 3.
Figure 4.
Preparation Check List
Task
Check
Date
Power voltage and electric current requirement
DC version
: -40 to -72V DC, 16A maximum x2 or;
AC version:
100 to 240V, 7A maximum x2
Installation spacing requirement
:
S9180-32X spacing requires a height of 1RU (1.72
”/4.5cm),
a width
of 19
” (48cm)
and a depth of 16.9 inches (42.8cm)
Thermal requirement
S9180-32X
’s
working temperature is 0°C to 45°C (32°F to 113°F)
Installation tools required
#2 Phillips Screwdriver
Accessories required
PC with terminal emulation software, 18-AWG(minimum) wire with
ring terminal for grounding
Rear wall clearance = 6”