background image

IMTX200-03

www.ueonline.com

EARTH GROuND MuST ALWAYS bE CONNECTED TO THE GREEN WIRE 

TO PROvIDE SHIELDING AND ELECTRICAL SAFETY.

WIRE  IN  ACCORDANCE  WITH  LOCAL  AND  NATIONAL  ELECTRICAL 

CODES.    bY  THE  INSTALLATION,  THE  WIRES  SHALL  bE  PROTECTED 

AGAINST MECHANICAL DAMAGE. E.G. bY uSE OF A CONDuIT.

THE  WIRING  TO  THE  PRESSuRE  TRANSMITTER  MuST  ONLY  bE 

CONNECTED  IN  THE  SAFE  AREA  OR  bY  AN  APPROvED  TERMINAL 

BOX  CErTIFIED  TO  En  60079-1  Or  En  60079-7  FOr  hAZArDOus 

LOCATIOns/FLAMEPrOOF ATMOsPhErEs. (ATEX rEQuIrEMEnTs OnLY)

A  1/2”  nPT  (male)  or  M20  conduit  connection  is  provided  on  top  of  the 

transmitter with 18 AWG, 72” leadwires. External grounding screw and clamp 

is provided with option M460.  The leadwires are color coded as follows:

 

4-20 mA output

 

Voltage (VDC) output

 

red: 

+ signal 

red:  + vDC signal

 

Black:   – signal 

Black:  – vDC signal

 

Green:   Earth Ground 

Green:  Earth Ground

 

 

 

Blue:  1-5 v Output

The transmitter may be wired in either a sourcing (see figure 1A) or sinking 

(see figure 1b) circuit. 

Part II - Adjustments

SPANNING THE TX200A™ TRANSMITTER  uSING THE  

SHuNT CAL. FEATuRE 

The  range  of  the  TX200A  can  be  adjusted  by  a  ratio  of  5:1  using  the  shunt 

calibration feature (see figure 3).  No pressure source is required for this process.  

Example:  

A 1,000 psi range TX200A can be adjusted for any range between 0 to 200 psi 

and 0 to 1,000 psi.

use the formula below to calculate l

cal

 or v

cal

.  This number represents the output 

current or voltage that the user will set with the shunt cal. on in order to achieve 
the desired range.

4-20 mA models formula: 

I

cal

 = (Cal# x 16mA/P

cal

) + 4mA

Voltage out (VDC) models formula: 

V

cal

 = (Cal# x V

FSO

/P

cal

) + V

zero

• 

I

cal

 is the output current that the user will set, with the shunt cal on to achieve 

the desired full scale pressure range (P

cal

)

• 

v

cal

 is the output voltage that the user will set, with the shunt cal on to achieve 

the desired full scale pressure range (P

cal

)

• 

Cal# is the amount of pressure simulated by turning the shunt cal on.  The 
Cal# is engraved on the TX200A housing and written on the Certificate of 
Calibration.

• 

P

cal

 is the full scale pressure range the user is adjusting to.

• 

v

zero

 is the output of the voltage (vDC) out model with no pressure applied.

• 

v

FSO

 is the full scale output, in volts, of a voltage (vDC) out model.

Example: For a TX200A with a 1-5 Volt output: Vzero = 1 volt and VFSO = 4 volts

Procedure:

1.  Determine the desired pressure range
2.  Calculate Ical for 4-20mA models or vcal for voltage (vDC) models using 

the formulae above.

3.  Power the TX200 with a suitable power supply.
 

a.  

4-20mA

 models can be powered with a 24vDC power supply   

 

and 100Ω resistor in series.  The voltage across the resistor    

 

represents the current in the loop.  100mv = 1mA.

 

b.  

Voltage (VDC)

 out models can be connected directly to a 24v  

 

power supply.  The output voltage is measured between the blue  

 

(+) and black (–) wires.

Please refer to figure 3 for steps 4-7.

4.     Adjust the zero as necessary.

5.     Turn the Cal switch clockwise to the on position.

6.     Adjust the Span and Fine Span controls until the output reaches the I

cal 

         

    or v

cal

 number calculated in step 2.

7.     Turn the Cal switch counter-clockwise to the off position.
8.     The transmitter should now be adjusted to the desired pressure range.

Example:

 End-user has a uE transmitter P/n TX200A10s1(0 to 2500 psig /0 to 172,4 bar range).  

For a particular application, a 0-1500 psig (0 to 103,4 bar) range is desired using this transmitter 

- this is the 

P

cal

.  

The 

Cal#

 engraved on the transmitter housing is 424 psi (29,2 bar).  using the 

formula above, 

I

cal

 = (424 x 16/1500) +4, the 

I

cal

 calculated is 8.52.  When all steps above are 

completed, the transmitter in this example would be spanned so that the 4 mA output signal = 0 

psig and the 20 mA output signal = 1500 psig (103,4 bar).

Figure 1C

Figure 3

Figure 1A

Figure 1B

4-20 mA output

Voltage output

Figure 2

4-20mA output:

• 

1300 ohms max at 36 vDC

•  700 ohms max at 24vDC

voltage (vDC) output:

• 

2000 ohms min

LoAD IMPEDANCE 

Summary of Contents for TX200

Page 1: ...ducts do not have any field replaceable parts Any substitution of components may impair suitability for Class I Division 1 TX200 Pressure Transmitter The epoxy resin shall not be subjected to a temperature greater than 125 C Part I Installation Tools Needed Adjustable Wrench Mounting Always locate units where shock vibration and ambient temperature fluctuations are minimal Do not mount in ambient ...

Page 2: ...l scale pressure range Pcal Cal is the amount of pressure simulated by turning the shunt cal on The Cal is engraved on the TX200A housing and written on the Certificate of Calibration Pcal is the full scale pressure range the user is adjusting to Vzero is the output of the voltage VDC out model with no pressure applied VFSO is the full scale output in volts of a voltage VDC out model Example For a...

Page 3: ...16 0 54 13 7 B G 1 2 female 1 3 8 1 01 25 7 C 7 16 20 SAE male 15 16 0 77 19 6 D HM4 Autoclave male 15 16 1 10 27 9 E HM6 Autoclave male 15 16 1 29 32 8 F LM4 Autoclave male 15 16 1 18 30 0 G LM6 Autoclave male 15 16 1 32 33 5 H G 1 4 male 15 16 1 03 26 2 J G 1 2 male 1 3 8 1 78 45 2 Wire Color Coding Red VDC Black VDC Green Earth Ground Blue Voltage VDC Output OR M20 METRIC 03 0 to 15 psis 04 0 t...

Page 4: ...Preventative maintenance and periodic testing is necessary for critical appli cations where damage could endanger property or personnel Electrical ratings stated in literature and on nameplate must not be exceed ed Overload on a switch can cause damage even on the first cycle Wire unit according to local and national electrical codes using wire size recom mended in installation sheet Do not mount ...

Reviews: