IMTX200-03

www.ueonline.com

GENERAL

bEFORE  INSTALLING,  CHECK  THE  SENSOR  MODEL  SELECTED  FOR 

COMPATIbILITY  TO  THE  PROCESS  MEDIA  IN  CONTACT  WITH  THE 

SENSOR AND WETTED PARTS.

MISuSE OF THIS PRODuCT MAY CAuSE EXPLOSION AND PERSONAL 

INjuRY.    THESE  INSTRuCTIONS  MuST  bE  THOROuGHLY  READ  AND 

uNDERSTOOD bEFORE uNIT IS INSTALLED.

 

THIS EquIPMENT IS SuITAbLE FOR uSE IN CLASS I, DIvISION 

1, GROuPS A, b, C AND D; CLASS II, DIvISION 1, GROuPS E, F AND G; 

CLASS III; OR NON-HAzARDOuS LOCATIONS ONLY. -

40°C (-40°F) ≤ 

Tamb. ≤ 85°C (185°F), 

ENCLOSuRE TYPE 4X.

THIS EquIPMENT IS ATEX CERTIFIED FOR EquIPMENT CATEGORY 2. 

SuITAbLE FOR APPROPRIATE uSE IN GAS zONE 1 AND DuST zONE 

21 APPLICATIONS. 

 

0539 DEMKO 08 ATEX 0810742X

 

 

II 2 G Ex d IIC T5

 

 II 2 D Ex tD A21 IP66 T+90°C

 

-40°C ≤ Tamb. ≤+80ºC

The  TX200™  pressure  transmitter  is  available  as  either  a  field  adjustable 

(TX200A) or fixed range (TX200B) model.  The TX200A is capable of a 5:1 

turndown (see Part II – Adjustments).  both models utilize a piezo-resistive 

or bonded foil sensor technology to continuously monitor pressure in a sys-

tem.  Changes in system pressure change the resistance in the sensor trans-

lating to either a 4-20 mA or voltage (vDC) output to a digital meter, gage, 

PLC (programmable logic controller) or other device.

Please refer to product bulletin for product specifications.  Product bulletin 

may be found at www.ueonline.com

PROOF PRESSuRE* LIMITS STATED IN THE LITERATuRE AND ON TRANSMITTER 

HOuSING MuST NEvER bE EXCEEDED, EvEN bY SuRGES IN THE SYS-

TEM.  OCCASIONAL OPERATION OF uNIT uP TO MAXIMuM PRESSuRE IS 

ACCEPTAbLE (E.G., START-uP, TESTING). CONTINuOuS OPERATION SHOuLD NOT 

EXCEED THE DESIGNATED OvER RANGE PRESSuRE.

*Proof Pressure
The  maximum  pressure  to  which  a  pressure  sensor  may  be  occasionally 

subjected, which causes no permanent damage (e.g., start-up, testing).  The 

units may require re-adjustment.

THESE  PRODuCTS  DO  NOT  HAvE  ANY  FIELD  REPLACEAbLE  PARTS. 

ANY SubSTITuTION  OF COMPONENTS MAY  IMPAIR  SuITAbILITY FOR 

CLASS I, DIvISION 1.

TX200™ 

Pressure Transmitter

THE EPOXY RESIN SHALL NOT bE SubjECTED TO A TEMPERATuRE 

GrEATEr ThAn 125°C.

Part I - Installation

 

Tools Needed

Adjustable Wrench

MouNTING 

ALWAYS  LOCATE  uNITS  WHERE  SHOCK,  vIbRATION  AND  AMbIENT 

TEMPERATuRE  FLuCTuATIONS  ARE  MINIMAL.  DO  NOT  MOuNT  IN 

AMBIEnT  TEMPErATurE  ArEAs  EXCEEDInG  185°F  (IF  uL/

cuL 

APPrOvAL Is APPLICABLE) Or 80 °C (IF ATEX APPrOvAL Is APPLICABLE). 

IF  SEvERE  PRESSuRE  SuRGES  ARE  EXPECTED,  CONSIDER  THE  uSE  OF  A 

PRESSuRE SNubbER.

uNIT MAY bE MOuNTED IN ANY POSITION. ALWAYS HOLD A WRENCH 

ON THE SENSOR FLATS (PRESSuRE PORT) WHEN MOuNTING uNIT.

Panel Mounting via 1/2” NPTM or M20 Electrical Connection

When  panel  mounting,  mount  through  7/8”  clearance  hole  in  panel.   hold 

in 

place with serrated 1/2” or M20 conduit nut.  Always support the unit by 

holding a wrench on the hex.

WIRING

DISCONNECT  ALL  SuPPLY  CIRCuITS  bEFORE  WIRING  uNIT. 

ELECTRICAL  RATINGS  STATED  IN  LITERATuRE  AND  ON  THE 

TRANSMITTER MuST NOT bE EXCEEDED.  FOR AMbIENT TEMPERA-

TuRES bELOW -10

°C 

AND AbOvE +60

°

C, uSE FIELD WIRING SuITAbLE FOR 

bOTH MINIMuM AND MAXIMuM AMbIENT TEMPERATuRE.

EXTERNAL GROuNDING SCREW (OPTION M460) IS REquIRED FOR 

NON-METALLIC CONDuIT SYSTEMS. (ATEX REquIREMENT ONLY– SEE 

FIGuRE 2).

IN ORDER TO MEET EuROPEAN EMC REquIREMENTS, THE TX200™ 

WIRING MuST bE INSTALLED IN A GROuNDED METAL CONDuIT OR 

WITH OTHER SuITAbLE SHIELDING.

THE  TX200™  TRANSMITTER  ACCEPTS  10-36  vDC  FOR  4-20  MA 

OuTPuT uNITS AND 10-30 vDC FOR vOLTAGE (vDC) OuTPuT uNITS. 

THE  SuPPLY  vOLTAGE  SHALL  NOT  EXCEED  36  vDC  FOR  4-20  MA 

OuTPuT  uNITS  AND  30  vDC  FOR  vOLTAGE  (vDC)  OuTPuT  uNITS.  THE 

suPPLY MusT BE IsOLATED FrOM MAIns vOLTAGE BY DOuBLE/rEInFOrCED 

INSuLATION.

U N I T E D   E L E C T R I C 

C O N T R O L S

Installation and Maintenance 

Instructions

Please read all instructional literature carefully and thoroughly before starting.  Refer to the final page for the listing of Recommended 
Practices, Liabilities and Warranties.

IMTX200-03

Summary of Contents for TX200

Page 1: ...ducts do not have any field replaceable parts Any substitution of components may impair suitability for Class I Division 1 TX200 Pressure Transmitter The epoxy resin shall not be subjected to a temperature greater than 125 C Part I Installation Tools Needed Adjustable Wrench Mounting Always locate units where shock vibration and ambient temperature fluctuations are minimal Do not mount in ambient ...

Page 2: ...l scale pressure range Pcal Cal is the amount of pressure simulated by turning the shunt cal on The Cal is engraved on the TX200A housing and written on the Certificate of Calibration Pcal is the full scale pressure range the user is adjusting to Vzero is the output of the voltage VDC out model with no pressure applied VFSO is the full scale output in volts of a voltage VDC out model Example For a...

Page 3: ...16 0 54 13 7 B G 1 2 female 1 3 8 1 01 25 7 C 7 16 20 SAE male 15 16 0 77 19 6 D HM4 Autoclave male 15 16 1 10 27 9 E HM6 Autoclave male 15 16 1 29 32 8 F LM4 Autoclave male 15 16 1 18 30 0 G LM6 Autoclave male 15 16 1 32 33 5 H G 1 4 male 15 16 1 03 26 2 J G 1 2 male 1 3 8 1 78 45 2 Wire Color Coding Red VDC Black VDC Green Earth Ground Blue Voltage VDC Output OR M20 METRIC 03 0 to 15 psis 04 0 t...

Page 4: ...Preventative maintenance and periodic testing is necessary for critical appli cations where damage could endanger property or personnel Electrical ratings stated in literature and on nameplate must not be exceed ed Overload on a switch can cause damage even on the first cycle Wire unit according to local and national electrical codes using wire size recom mended in installation sheet Do not mount ...

Reviews: