background image

GENERAL

Pressure variations are sensed by a bellows, diaphragm or piston sensor
which either actuates or de-actuates one, two or three snap-acting switches
at a pre-determined set point(s).  Set point(s) is adjusted by turning an
internal knob and pointer (H types) or internal screw (J types).

Tools Needed

Screwdriver

Hammer

Adjustable wrench

MOUNTING

I

NSTALL UNIT WHERE SHOCK, VIBRATION AND TEMPERA-

TURE FLUCTUATIONS ARE MINIMAL. ORIENT UNIT SO THAT
MOISTURE IS PREVENTED FROM ENTERING THE ENCLO-

SURE.  IF UNIT IS BEING INSTALLED WHERE HEAVY CONDENSATION
IS EXPECTED, VERTICAL MOUNTING (PRESSURE CONNECTION
DOWN) IS REQUIRED.  DO NOT MOUNT UNIT IN AMBIENT TEMPERA-
TURES EXCEEDING PUBLISHED LIMITS.

400 Series pressure controls can be mounted in any position, provided the
electrical conduit is not facing up.  The preferred mounting position is ver-
tical (pressure connection down).

The cast-in knockouts for 3/4” electrical conduit are located on the side
and rear of the enclosure.  These can easily be knocked out by placing the
blade of a screwdriver in the groove and rapping sharply with a hammer.

Mount the unit via the (2) 1/4” screw clearance holes on the enclosure.
See Dimensions. Units may also be mounted via the NPT pressure con-
nection. 

ALWAYS HOLD A WRENCH ON THE PRESSURE HOUSING HEX
WHEN MOUNTING UNIT.  DO NOT TIGHTEN BY TURNING
ENCLOSURE.  THIS WILL DAMAGE SENSOR AND WEAKEN 

SOLDER OR WELDED JOINTS.

U N I T E D   E L E C T R I C  

C O N T R O L S

Installation and Maintenance
Instructions

IMP400-07

Please read all instructional literature carefully and thoroughly before starting.  Refer to the final page for the listing of Recommended Practices,
Liabilities and Warrantees.

400 Series
Pressure Controls

Types: H400, H402, H403, 
H400K, H402K, J400, J402, 
J403, J400K, J402K

Part I - Installation

WIRING

DISCONNECT ALL SUPPLY CIRCUITS BEFORE WIRING.

ELECTRICAL RATINGS STATED IN LITERATURE AND ON NAME-
PLATE SHOULD NEVER BE EXCEEDED.  OVER-LOAD ON A

SWITCH CAN CAUSE FAILURE ON THE FIRST CYCLE. 

WIRE UNITS ACCORDING TO LOCAL AND NATIONAL ELECTRI-
CAL CODES.  MAXIMUM RECOMMENDED WIRE SIZE IS 14 AWG.

Connect conduit to the case and wire directly to the switch terminals accord-
ing to local and national electrical codes.  Bring the wires up to terminals
from the rear of the case. (See fig. 1.) If manual reset switch or DPDT options
are used, lead wires are supplied, color coded as follows:

ALLOW ENOUGH SLACK SO AS NOT TO AFFECT SWITCH MOVE-
MENT WHEN MAKING SETTING ADJUSTMENTS AND ENSURE
THAT THE WIRES ARE NOT TOUCHING THE COVER WHEN
INSTALLED.

NOTE: For larger wire gauges, a one time shift may be experienced or
expected due to space limitations within the enclosure. Verify setpoint after
installation. 

NOTE: The middle switch assembly is omitted for dual switch controllers.
The outer switch assemblies are omitted for single switch controllers. Type
“J” controls have internal screw adjustments and type “H” have cam assem-
blies for internal calibrated adjustments. 

Switch 1

Switch 2

Common

Violet

Yellow

Normally Open

Blue

Orange

Normally Closed 

Black

Red

Figure 1

Summary of Contents for H400

Page 1: ...R I C C O N T R O L S Installation and Maintenance Instructions IMP400 07 Please read all instructional literature carefully and thoroughly before starting Refer to the final page for the listing of Recommended Practices Liabilities and Warrantees 400 Series Pressure Controls Types H400 H402 H403 H400K H402K J400 J402 J403 J400K J402K Part I Installation WIRING DISCONNECT ALL SUPPLY CIRCUITS BEFOR...

Page 2: ...acy at the dial midpoint Switches may be set together or apart up to 100 of the range scale On dual switch models either switch may be set high On triple switch models the third middle switch has no over travel mechanism and must always be set to the highest pressure when the switches are set apart Altering the setting of one switch will usually have little effect on the other s however re calibra...

Page 3: ...163 58 1 4 451 453 454 4 28 108 74 1 4 Differential Pressure 448 450 452 5 03 127 79 1 4 147 157 6 13 155 57 1 4 520 525 8 62 218 90 1 2 S147B S157B 6 13 155 57 1 2 530 535 8 12 206 20 1 2 455 559 7 00 178 05 1 4 540 543 7 90 200 7 1 8 544 547 8 06 204 7 1 8 Option M210 Differential Pressure Indication Surface Mounting Hardware Part Number 6361 704º Dimensions Figure 3 Span Adjust Screw Figure 2 Z...

Page 4: ...ed is upon delivery free from defects in material and workmanship and that any such product which is found to be defec tive in such workmanship or material will be repaired or replaced by UE F O B UE provided however that this warranty applies only to equipment found to be so defective within a period of 12 months after installation by buyer but not to exceed 18 months after delivery by the seller...

Reviews: