UE 2W2D Installation And Maintenance Instructions Manual Download Page 9

 

IM_ONE-01 

9

 

www.ueonline.com

LATCH MODE:  

(N/A on Model 8W2D)

The switch output can be configured to latch when the set point is reached.  
•  Latching Mode: In the Programming Mode, set “LCH1” to “ON”.  The output changes to the switched state when the set-point is crossed, and will remain in  
  the switched state until it is manually reset by the user.

•  To clear a Latched Output: Display will be reading "MAN RSET".  To clear and exit, press both buttons              .  
•  To return to the Process Display, without clearing, press the right button       .  
•  To continue programming without clearing, press the left button       .    

 

   .

PLUGGED PORT:

The One Series has the ability to detect process conditions which may indicate that the process port has become blocked, plugged or put into a “bypass” condition.  
It does this by dynamically monitoring pressure changes over time.  If the process does not change by a certain amount during the time period selected (both set 
by the user), the display will indicate “PLUG” and the output will go to the “open” state.  

There are four possible settings for the detection time:  
•  OFF     •  1 Min.     •  1 Hr.     •  24 Hrs.

Setting the detection time to “OFF” disables the plugged port function.  This should be done where danger of plugging is not a concern, or where the system 
pressures may not change over time (e.g., a storage tank).  If the feature is enabled the user must then enter the plugged port range.  This number represents 
the expected variation in the process variable. The number is limited to +/- 10% of the full scale range of the sensor.  The diagram below illustrates the feature’s 
operation.

T

0

 Process variable ramp up

T

1

 Process variable stabilizes, new thresholds calculated

T

2

 Threshold exceeded, new thresholds calculated, timer reset

T

3

 Low threshold exceeded, new thresholds calculated, timer reset

T

4

 Plugged Port timer expires, Plugged port condition reported

T

5

 Plugged Port condition cleared, new thresholds calculated, timer reset

T

6

 Low threshold exceeded, new thresholds calculated, timer reset

 

T

0

 

T

1

 

T

2

 

T

3

 

T

4

 

T

5

 

T

6

DELAY:

In some applications, it is desirable to “dampen” the switch response and prevent intermittent false trips due to pressure spikes or other transient/isolated events. 
The Delay feature provides a software digital filter with a programmable time constant for suppressing certain transient short-duration events.  The filter settings 
are: 

•  OFF     •  ¼ second     •  ½ second     •  1 second     •  2 seconds 

NOTE: 

The One Series typically responds to a process change in under 50 mSec.  Using the Delay feature can lengthen the overall response time of the switch for 

certain types of pressure changes.

•  A shorter delay setting provides a faster response but is less stable.  
•  A longer delay setting provides a slower response and is more stable.

During a plugged port fault (the interval from T

4

 to T

5

)

 

the 

display will read “PLUG” and the switch will be set in the 
“OPEN” state.  The fault will be cleared if the pressure 
varies outside of the detection range or if the feature is 
disabled by the user.

Summary of Contents for 2W2D

Page 1: ...NS ONLY THIS EQUIPMENT IS ATEX CERTIFIED SUITABLE FOR APPROPRIATE USE IN GAS ZONE 2 DUST ZONE 22 APPLICATIONS OR GAS ZONE 0 DUST ZONE 20 APPLICATIONS WHEN INSTALLED PER DRAWING A 62174 20 EUROPE 0539 DEMKO 03 ATEX 0322281X 0539 DEMKO 03 ATEX 0322281X II 1 G EEx ia IIC T5 II 3 G EEx nL IIC T5 II 1 D T 90ºC II 3 D T 90ºC 40ºC TAMB 85ºC IP66 40ºC TAMB 85ºC IP66 2W3A MODELS THIS EQUIPMENT IS SUITABLE ...

Page 2: ...lean and free of debris Use a wrench on the hex pressure connection to tighten Test for leaks On Differential Pressure models the Low L side pressure must NOT exceed the high H side pressure WARNING NEVER INSERT ANY OBJECT INTO THE PRESSURE SENSOR OPENING DAMAGE TO THE SENSOR WILL RESULT AFFECTING ACCURACY Local and Remote Temperature Models For Remote Sensing models C H R Route the extension wire...

Page 3: ... PAGE 12 FOR ADDITIONAL INFORMATION ON SELECTING AN INTRINSIC SAFETY BARRIER SUBSTITUTION OF COMPONENTS MAY IMPAIR INTRINSIC SAFETY WARNING MODEL 4W3A ACCEPTS 90 130 VAC VDC AS ITS POWER SOURCE THE SWITCHED OUTPUT MAXIMUM LOAD RATING IS 10 A 24 280 VAC AT T amb 38 C 100 F DERATE 1 8 A 10 C 18 F OVERLOADING THE SWITCH MAY CAUSE FAILURE WARNING THE ONE SERIES 8W2D MODEL ACCEPTS 12 30 VDC AS ITS POWE...

Page 4: ...L1 and L2 terminals Connect the potential free solid state relay at TB1 to an appropriate load Refer to the Switch Ratings Table for the switch ratings The 4W3A has one terminal block labeled TB1 TB1 has four positions marked with L1 L2 and a switch symbol covering the remaining two positions TB1 terminal block accepts 14 22 AWG wiring and the recommended torque is 3 5 in lbs The 8W2D has three te...

Page 5: ...switch is fully programmable over the entire range of the sensor Reaction time for the One Series to a process change is typically 50 mS or less 2 WIRE SIMPLICITY 2W Models only The One Series 2 Wire electronic pressure switch patented is designed to operate on discrete input leakage current models 2W2D and 2W3A or analog input 4 20 mA loop power models 2WLP41 and 2WLP43 The microprocessor based O...

Page 6: ...ription of Offset and Span In addition the user can easily access information such as the set point dead band and minimum maximum process readings By pushing the right button once the display will scroll as follows SP1 XX XX DB1 XX XX SP2 XX XX DB2 X XX 8W2D model only By pushing the left button once the display will scroll the min max process values seen MAX XX XX MIN XX XX The display will rever...

Page 7: ... confirm save the changes and return to the Process Display mode to Discard changes press the right button NO will be displayed Press both buttons to confirm discard the changes and return to the Process Display mode KEY PROGRAMMING FEATURES SWITCH MODE The One Series allows the switch output to be set up for either 3 state I Am Working or 2 state operation For an overview of the I Am Working IAW ...

Page 8: ...usly captures the readings from the sensor and stores the minimum and maximum values since the last time they were reset These can be viewed at any time by pushing the left button The display will scroll the information and then return to the Process Display mode To reset these values enter the Programming Mode see page 6 use the left button to get to the CLR MAX MIN command and press the right bu...

Page 9: ...resents the expected variation in the process variable The number is limited to 10 of the full scale range of the sensor The diagram below illustrates the feature s operation T0 Process variable ramp up T1 Process variable stabilizes new thresholds calculated T2 Threshold exceeded new thresholds calculated timer reset T3 Low threshold exceeded new thresholds calculated timer reset T4 Plugged Port ...

Page 10: ... diagnostics are capable of detecting many possible fault conditions Some fault conditions will clear automatically when the parameter returns to normal others require the unit to be powered down and restarted and some are catastrophic and require repair or replacement A list of fault conditions is shown below DISPLAY WILL SCROLL FAULT RESULT SWITCH OUTPUT 4 20 mA OUTPUT PLUG Plugged Port Detected...

Page 11: ...an help Please have the manufacturer s model number ready when you call us In rare cases when the series resistor value is too large and falls out of the Acceptable Range placing another resistor across the input will allow it to work Please call 617 926 1000 Technical Sales for assistance Please note that a maximum of 30 VDC supply voltage and a load of 40 mA must not be exceeded or permanent dam...

Page 12: ...ty barriers must be installed with a suitable 1Ω earth ground Isolated barriers offer simplified installation since there is no requirement for the ground but are generally more expensive than the diode safety barriers Shunt Diode Safety Barriers The entity parameters of diode safety barriers suitable for use with the 2W2D models are V max 28 Volts I max 93 mA Because the 2W2D model derives its op...

Page 13: ...IM_ONE 01 13 www ueonline com PROCESS DISPLAY ...

Page 14: ...14 IM_ONE 01 www ueonline com Models 8W2D and 2WLP Dual Conduit shown with Temperature Sensor Models 4W3A 2W2D and 2W3A Single Conduit shown with Gauge Pressure Sensor DIMENSIONAL DRAWINGS ...

Page 15: ...IM_ONE 01 15 www ueonline com Temperature Model L Temperature Model R SENSOR OPTIONS Gauge Pressure 1 2 NPT female Temperature Models H C Differential Pressure ...

Page 16: ...ca tions where damage could endanger property or personnel Electrical ratings stated in literature and on nameplate must not be exceeded Overload on a switch can cause damage even on the first cycle Wire unit according to local and national electrical codes using wire size recommended in installation sheet Do not mount unit in ambient temp exceeding published limits LIMITED WARRANTY Seller warrant...

Reviews: