UE 2W2D Installation And Maintenance Instructions Manual Download Page 6

6

 

IM_ONE-01

 

www.ueonline.com

I Am Working (IAW®) 

The One Series also contains UE’s patented IAW

®

 diagnostic software.  On a continuous basis, the One Series is checking itself for proper operation, and letting 

you know locally that things are OK using animated arrows on the display.  For remote assurance, the output can be set up for 3-state operation, allowing the 
host device to detect normal, tripped, and fault conditions (see Key Programming Features, page 7 for a full description of the 3-state operation).  IAW

®

 watches 

over many possible problems, both within itself and in the overall system (a list of the various parameters is outlined in the chart under Fault Codes, page 10).  
In the event of a fault condition, the One Series will attempt to display the problem and provide remote electrical indication. In the case of certain micro-controller 
faults, the revolving arrow may freeze or go out, indicating that a failure exists.

OTHER FEATURES

The One Series has other advanced features:  
•  When the Plugged Port feature is enabled, the One Series will watch for process conditions which could be evidence of a plugged sensing port or  
  an accidentally-closed instrument valve, and alert the user to potential problems.
•  The switch output can be configured for either automatic reset or latching, requiring the user to manually acknowledge the alarm. 
•  User selectable switch response time (delay) filter allows for dampening the One Series response to process upsets or spikes, eliminating nuisance trips.   
  (See Key Programming Features, page 7 for a complete description of these features). 

DISPLAY FEATURES AND DIAGNOSTICS

The One Series features a large, easy to read LCD display.  It is used for three main purposes:  process indication, programming of key 
features and switch status/troubleshooting.

In the Process Display mode, the display may be indicating the following:
•  Current process value and units of measure:  A value will be displayed as long as the reading is within 110% of the full scale range noted on the nameplate.    
  The units of measure are factory-set.
•  I Am Working (IAW

®

) status:  When the unit and process are working properly a circular 4-segment arrow will be revolving around the letters “IAW” in the  

  top center of the display.  (For a full description of IAW

®

, see above).

• Offset/Span Adjustment:  The word “offset” will appear above the process value, indicating that the offset and/or span calibration has been modified by the  
  user (see Key Programming Features, for a description of Offset and Span).  In addition, the user can easily access information such as the set point, dead 
  band and minimum/maximum process readings. 

•  By pushing the right        button once, the display will scroll as follows:
   

 

 

SP1   XX.XX    DB1   XX.XX 

 

SP2   XX.XX    DB2   X.XX (8W2D model only)

•  By pushing the left        button once, the display will scroll the min/max process values seen:
   

 

 

MAX   XX.XX    MIN   XX.XX

  The display will revert back to the Process Display mode after scrolling.

ALARM CONDITION

When the process goes beyond the set point, the display will begin to flash, alternating between the process value and “SW1”.  The display will continue to flash 
until the process has returned to a value beyond the deadband, at which point the display will revert to normal operation and process value display.  If the unit 
was programmed to have a latching output, a small “Latch” icon will light in the display when the set point is reached, indicating that the output is latched and 
needs to be manually reset.  (See Key Programming Features, for a complete description).

FAULT CONDITIONS

In the case of a fault condition, the display may indicate the following:
If the IAW

®

 software detects a fault outside of the micro-controller, and can still operate, it will display an error message.

If the fault is one which affects the micro-controller or the display, the revolving arrow around “IAW” will either freeze or go out.
If it is a failure of the power supply or the wiring, the display will go blank.
(See Fault Codes, page 10 for a complete description of fault diagnostics.)

PROGRAMMING

Tools Required

Software Flowchart, page 13 

Step 1:  Prior to Programming

 

Programming of the One Series is done using the two buttons on the faceplate (labeled        and        ).  By stepping down through the main menu using the 
left         button, you can access the various features of the One Series.  The right          button is then used to move into the feature’s submenu for setting up or 
modifying the parameters. 

NOTE: 

 See the flowchart on page 13 showing the entire program menu structure.

Important Note: 

 The One Series programming menu is a single direction loop, with submenus embedded in it.  Because the main menu is single direction, there 

is no way to reverse direction and back up in the program.  If you need to make a correction to a prior Main Menu step, you will need to continue forward and exit, 
then re-enter the program and step through to the appropriate feature.  If you are in a Submenu, you will need to circle back to the beginning of the Submenu 
and re-enter the Submenu. 

The One Series has a number of advanced features you will need to understand before you can effectively use them.  These features are discussed on next page.  

Summary of Contents for 2W2D

Page 1: ...NS ONLY THIS EQUIPMENT IS ATEX CERTIFIED SUITABLE FOR APPROPRIATE USE IN GAS ZONE 2 DUST ZONE 22 APPLICATIONS OR GAS ZONE 0 DUST ZONE 20 APPLICATIONS WHEN INSTALLED PER DRAWING A 62174 20 EUROPE 0539 DEMKO 03 ATEX 0322281X 0539 DEMKO 03 ATEX 0322281X II 1 G EEx ia IIC T5 II 3 G EEx nL IIC T5 II 1 D T 90ºC II 3 D T 90ºC 40ºC TAMB 85ºC IP66 40ºC TAMB 85ºC IP66 2W3A MODELS THIS EQUIPMENT IS SUITABLE ...

Page 2: ...lean and free of debris Use a wrench on the hex pressure connection to tighten Test for leaks On Differential Pressure models the Low L side pressure must NOT exceed the high H side pressure WARNING NEVER INSERT ANY OBJECT INTO THE PRESSURE SENSOR OPENING DAMAGE TO THE SENSOR WILL RESULT AFFECTING ACCURACY Local and Remote Temperature Models For Remote Sensing models C H R Route the extension wire...

Page 3: ... PAGE 12 FOR ADDITIONAL INFORMATION ON SELECTING AN INTRINSIC SAFETY BARRIER SUBSTITUTION OF COMPONENTS MAY IMPAIR INTRINSIC SAFETY WARNING MODEL 4W3A ACCEPTS 90 130 VAC VDC AS ITS POWER SOURCE THE SWITCHED OUTPUT MAXIMUM LOAD RATING IS 10 A 24 280 VAC AT T amb 38 C 100 F DERATE 1 8 A 10 C 18 F OVERLOADING THE SWITCH MAY CAUSE FAILURE WARNING THE ONE SERIES 8W2D MODEL ACCEPTS 12 30 VDC AS ITS POWE...

Page 4: ...L1 and L2 terminals Connect the potential free solid state relay at TB1 to an appropriate load Refer to the Switch Ratings Table for the switch ratings The 4W3A has one terminal block labeled TB1 TB1 has four positions marked with L1 L2 and a switch symbol covering the remaining two positions TB1 terminal block accepts 14 22 AWG wiring and the recommended torque is 3 5 in lbs The 8W2D has three te...

Page 5: ...switch is fully programmable over the entire range of the sensor Reaction time for the One Series to a process change is typically 50 mS or less 2 WIRE SIMPLICITY 2W Models only The One Series 2 Wire electronic pressure switch patented is designed to operate on discrete input leakage current models 2W2D and 2W3A or analog input 4 20 mA loop power models 2WLP41 and 2WLP43 The microprocessor based O...

Page 6: ...ription of Offset and Span In addition the user can easily access information such as the set point dead band and minimum maximum process readings By pushing the right button once the display will scroll as follows SP1 XX XX DB1 XX XX SP2 XX XX DB2 X XX 8W2D model only By pushing the left button once the display will scroll the min max process values seen MAX XX XX MIN XX XX The display will rever...

Page 7: ... confirm save the changes and return to the Process Display mode to Discard changes press the right button NO will be displayed Press both buttons to confirm discard the changes and return to the Process Display mode KEY PROGRAMMING FEATURES SWITCH MODE The One Series allows the switch output to be set up for either 3 state I Am Working or 2 state operation For an overview of the I Am Working IAW ...

Page 8: ...usly captures the readings from the sensor and stores the minimum and maximum values since the last time they were reset These can be viewed at any time by pushing the left button The display will scroll the information and then return to the Process Display mode To reset these values enter the Programming Mode see page 6 use the left button to get to the CLR MAX MIN command and press the right bu...

Page 9: ...resents the expected variation in the process variable The number is limited to 10 of the full scale range of the sensor The diagram below illustrates the feature s operation T0 Process variable ramp up T1 Process variable stabilizes new thresholds calculated T2 Threshold exceeded new thresholds calculated timer reset T3 Low threshold exceeded new thresholds calculated timer reset T4 Plugged Port ...

Page 10: ... diagnostics are capable of detecting many possible fault conditions Some fault conditions will clear automatically when the parameter returns to normal others require the unit to be powered down and restarted and some are catastrophic and require repair or replacement A list of fault conditions is shown below DISPLAY WILL SCROLL FAULT RESULT SWITCH OUTPUT 4 20 mA OUTPUT PLUG Plugged Port Detected...

Page 11: ...an help Please have the manufacturer s model number ready when you call us In rare cases when the series resistor value is too large and falls out of the Acceptable Range placing another resistor across the input will allow it to work Please call 617 926 1000 Technical Sales for assistance Please note that a maximum of 30 VDC supply voltage and a load of 40 mA must not be exceeded or permanent dam...

Page 12: ...ty barriers must be installed with a suitable 1Ω earth ground Isolated barriers offer simplified installation since there is no requirement for the ground but are generally more expensive than the diode safety barriers Shunt Diode Safety Barriers The entity parameters of diode safety barriers suitable for use with the 2W2D models are V max 28 Volts I max 93 mA Because the 2W2D model derives its op...

Page 13: ...IM_ONE 01 13 www ueonline com PROCESS DISPLAY ...

Page 14: ...14 IM_ONE 01 www ueonline com Models 8W2D and 2WLP Dual Conduit shown with Temperature Sensor Models 4W3A 2W2D and 2W3A Single Conduit shown with Gauge Pressure Sensor DIMENSIONAL DRAWINGS ...

Page 15: ...IM_ONE 01 15 www ueonline com Temperature Model L Temperature Model R SENSOR OPTIONS Gauge Pressure 1 2 NPT female Temperature Models H C Differential Pressure ...

Page 16: ...ca tions where damage could endanger property or personnel Electrical ratings stated in literature and on nameplate must not be exceeded Overload on a switch can cause damage even on the first cycle Wire unit according to local and national electrical codes using wire size recommended in installation sheet Do not mount unit in ambient temp exceeding published limits LIMITED WARRANTY Seller warrant...

Reviews: