IMP120-14

www.ueonline.com

Part II - Adjustments

Tools Needed

Screwdriver

5/8” open end Wrench

5/64” Allen Wrench

AfTer CoMPleTIng ADJuSTMenTS on TYPe H121 AnD H122 

ConTrolS,  be Sure To re-InSTAll ADJuSTMenT Cover. 

Do noT over TIgHTen Cover SCreWS. 

for set point adjustment and gapping, connect control to a calibrated 

pressure source.

Types J120 (All) and J120K Models 455-559 (See Figure 4a)

remove cover.  loosen phillips screw adjustment lock. Adjust set point 

by turning 5/8” hex adjustment screw clockwise (In) to raise set point, 

or counterclockwise (ouT) to lower set point.  Secure adjustment 

screw by tightening adjustment lock.

Type J120K Models 36-39,147-S157B, & 367 (See Figure 4b)

r e m o v e   f r o n t   c o v e r   a n d   g a s k e t   f r o m   s e n s o r  

assembly  located  below  enclosure  by  unscrewing  4  phillips  screws.  

loosen phillips screw adjustment lock.  Adjust set point by turning 5/8” 

hex screw clockwise (In) to increase setting or counterclockwise (ouT) 

to decrease setting.  Adjusting screw should be locked by tightening 

adjustment lock.

Types H121, H121K

Adjust  set  point  by  turning  external  knob  and  pointer  to  desired 

setting on scale.

Types H122, H122K

Individual  microswitches  may  be  set  together  or  separately  by  up 

to  100%  of  range.    The  front  (low)  microswitch  should  never  be 

set  higher  than  the  rear  (High)  microswitch.    Turning  external 

knobs  will  increase  or  decrease  each  switch  setting  independently.

Types H122P

Individual switches may be set together or separately by up to 60% 

of  range.    The  front  switch  is  set  by  turning  the  internal  calibrating 

screw to the right for lower set point and turning to the left for higher 

set point.  When not set together, the front switch should never be set 

higher than the rear switch.  Turning the external knob will increase or 

decrease both switch settings simultaneously without disturbing their 

relationship.  

Controls with Options

Option 1519 and other models with an Adjustable Deadband 

Switch

This  microswitch  has  an  integral  adjustment  wheel.    Turning  this 

wheel raises and lowers the pressure rise set point. The fall set point 

remains constant. Consult factory for additional information.

Type J120, Option 1530, Manual Reset 

This microswitch, when actuated, remains actuated until the pressure 

drops sufficiently to allow the reset knob (located on the left side of 

the control) to be manually turned to reset the microswitch.

Option M210 Indicator for 

Differential Pressure Controls, Span Adjustment

(See figure 5). To adjust indication for maximum accuracy at any 

desired set point, follow steps 1 thru 3 listed  below:

 1)  remove front window and gasket (four screws) to gain access    

to span adjustment.

 2)  Connect control to calibrated gauges and set required differential 

 

pressure. 

 3)  using a screwdriver, slowly turn the span adjustment to obtain

 

required indication.  remount the front gasket and window. 

NOTE:

 Spanning adjustment will not affect the mid-range indication. 

The adjustment is factory calibrated and sealed to indicate tampering.  

Do noT forCe SPAn ADJuSTMenT, SInCe PerMAnenT 

DeforMATIon of THe lInkAge MeCHAnISM MAY reSulT.

Figure 5

Option M210

J120K: Opposed Sensor,  

Models 36-39, 147-157, S147B, 

S157B, 367

Figure 4b

Figure 4a 

DO NOT TURN

Summary of Contents for 120 Series

Page 1: ... or both can be used during installation A 3 4 explosion proof plug is provided for properly sealing the unused conduit opening thE explosion proof plug must be properly sealed during product installation GENERAL Misuse of this product may cause explosion and personal injury These instructions must be thoroughly read and understood before unit is installed This equipment is suitable for use in Cla...

Page 2: ... engage cover O ring Types J120 J120K H121 H121K H122 H122K H122P Mount controls vertically pressure connection facing down see Figure 1a or horizontally see Figure 1b Control may be surface mounted via the four 1 4 screw holes on the enclosure or mounting bracket It can also be mounted directly to a rigid pipe using the pressure connection Controls with Breather Drain Option M450 Type J120 J120K ...

Page 3: ...ront switch is set by turning the internal calibrating screw to the right for lower set point and turning to the left for higher set point When not set together the front switch should never be set higher than the rear switch Turning the external knob will increase or decrease both switch settings simultaneously without disturbing their relationship Controls with Options Option 1519 and other mode...

Page 4: ...71 174 521 525 531 535 and 540 548 Turn hex IN an additional 1 1 2 flats from this point This will provide a 5 9 mil gap Models 680 701 705 356 376 612 616 270 274 Turn hex IN 3 flats from this point approximately 1 2 turn This will provide a 14 16 mil gap Models 183 189 190 194 483 489 490 494 565 567 Turn hex IN 1 flat from this point This will provide a 4 7 mil gap CONTACT FACTORY FOR ASSISTANC...

Page 5: ...35 0 1 2 530 535 8 84 224 5 1 2 550 552 8 81 223 8 1 4 551 553 555 8 34 211 8 1 4 560 564 7 53 191 3 2 Sanitary 565 567 7 53 191 3 1 1 2 Sanitary 612 616 7 88 200 2 1 4 680 8 13 206 5 1 4 701 705 15622 15834 15839 7 44 189 0 1 4 Differential Pressure 36 39 147 157 367 7 59 192 8 1 4 S147B S157B 7 59 192 8 1 2 455 457 559 8 44 214 4 1 4 540 543 9 34 237 2 1 8 544 548 9 41 239 0 1 8 Types H121 H122 ...

Page 6: ...sonnel For all applications a factory set unit should be tested before use Electrical ratings stated in literature and on nameplate must not be exceeded Overload on a switch can cause damage even on the first cycle Wire unit according to local and national electrical codes using wire size recommended in installation sheet Do not mount unit in ambient temp exceeding published limits LIMITED WARRANT...

Reviews: