UE 12 Series Installation And Maintenance Instructions Download Page 2

IMP12-14

www.ueonline.com

2

for dIfferentIal Pressure Models, Mount agaInst a rIgId suPPort usIng 

the MountIng bracket attached to the sensor asseMbly.  then 
connect the hIgh and low Pressure connectIons  (hIgh Pressure 
Port Is on the left, when facIng the unIt).

for asseMblIes wIth junctIon boxes, It Is recoMMended that the 
Product be Mounted vertIcally wIth the Pressure connectIon 
down.

the Product May be Mounted In any PosItIon. however, If InstallatIon 
locatIon results In frequent exPosure to  lIquId It Is recoMMended 
that the Product be Mounted vertIcally wIth the Pressure 
connectIon down. If  Product Is to be set after MountIng, verIfy that 
adjustMent oPenIng Is accessIble, “front” MarkIng on naMePlate Must 

face the oPerator.

note: due to product sensitivity on sensor type w, it is recommended that these models 
be mounted vertically with pressure connection facing down.  other types of mounting may 
cause slight set-point shifts, which may require readjustment.

Panel Mounting via 1/2” NPTM or M20 Electrical Connection

when panel mounting, mount through 7/8” clearance hole in panel.  use 1/2” or M20 

conduit nut to secure in place.  always support the product by holding a wrench on the hex. 

to attach conduIt connectIon, hold electrIcal connectIon steady wIth 

wrench on hex, then thread on conduIt.

Surface Mounting Bracket Kit (P/N 62169-13)

 

(see Fig. 6)

open the adjustment cover and orient the unit so that adjustment opening will be accessible 

when the switch is mounted.  close the adjustment cover ensuring that the bracket does 

not interfere with the cover as this serves as the dual seal device method of primary seal 

failure annunciation and venting.  failure to install the unit correctly with the mounting 

bracket may result in improper venting of the adjustment cover.

WIRINg

dIsconnect all suPPly cIrcuIts before wIrIng Product. wIre In accordance 

wIth local and natIonal electrIcal codes. the wIres should be 

Protected agaInst MechanIcal daMage by use of a conduIt or 

other suItable Means.

electrIcal ratIngs stated In the lIterature and PrInted onto the 

Product housIng Must not be exceeded. overload on a swItch can 
cause faIlure on the fIrst cycle.

dIn connector (oPtIon M515, fIgure 4) Is not aPProved for class I, 

dIv. 1 hazardous locatIons/flaMeProof atMosPheres.

for atex InstallatIon, an external groundIng screw (oPtIon M460) 

Is requIred for non-MetallIc conduIt systeMs. (see fIgure 2)

for atex InstallatIon In hazardous locatIons, the wIrIng to the 

Pressure swItch Must only be connected In the safe area or by an 

aPProved terMInal box certIfIed to en standards 60079-0:2012, 

60079-1:2007, 60079-31:2009, 60079-7:2007, Iec 60079-0:ed.6, Iec 

60079-1:ed.6, Iec 60079-31:ed.1, Iec 60079-7:ed.4 

1/2" nPt (male) or M20 (male) conduit connection is provided on top of the prod-

uct with 72” long, 18 awg leadwires. the product is available with sPdt or dPdt 

operation. external grounding screw and clamp is provided with option M460 for atex 

installation with non-metallic conduit systems (see figure 2).
factory sealed leadwires are color coded:

TERMINALS 

SPDT 

DPDT

 

Circuit 1  Circuit 2

common 

brown  brown   yellow

normally closed 

red 

red 

  black

normally open 

blue 

blue 

  violet 

ground 

green green

DIN Connector with 4 Male Terminals (see Figure 4)

connector conforms to dIn 43650. use a female mating dIn connector (not ue sup-

plied).

Coding: TERMINALS

terminal #1

common

terminal #2

normally closed

terminal #3

normally open

ground

Part II - Adjustments

Tools Needed

flathead screwdriver with 3/16” or 1/4” wide blade

1.  connect control to pressure source.
2.  with power disconnected, slide cover toward electrical terminations while twisting  
 

it to overcome friction.

3.  connect power to terminals or leads.
4.  Insert screwdriver into adjustment slot and turn clockwise to 

increase

 

 

setting or counter clockwise to 

decrease

 setting.  (see figure 3)

for setting on rIse, apply desired pressure and turn adjustment clockwise until switch 
actuates (circuit across n.o. and coM terminals closes).
for setting on fall, apply pressure equal to normal system operating pressure. 
reduce source pressure to setpoint value. turn adjustment counter clockwise until 
switch actuates (circuit across n.c. and coM terminals closes).

Zone Hazardous Locations Flameproof 

gap and Joint Details

electrical conduit fitting threaded connection: M20 x 1.5, 7 threads minimum engage-
ment

Figure 2

option M460 External 

grounding Screw

Summary of Contents for 12 Series

Page 1: ...t is installed This product is suitable for use in Class I Divisions 1 2 Groups a B C and D Class II Divisions 1 2 Groups E f and G class III or non hazardous locations only 50 C 58 F Tamb 80 C 176 F Enclosure Type 4X This product is ATEX and iecex certified for equipment category 2 Suitable for appropriate use in gas zone 1 and dust zone 21 applications EN 60079 0 2012 EN 60079 1 2007 EN 60079 31...

Page 2: ...ot be exceeded overload on a switch can cause failure on the first cycle DIN connector option M515 figure 4 is not approved for Class I Div 1 Hazardous Locations Flameproof atmospheres for atex installation an External grounding screw option M460 is required for non metallic conduit systems SEE figure 2 for atex installation in hazardous locations tHE WIRING TO THE PRESSUrE SWITCH MUST ONLY BE CON...

Page 3: ... 1 16 27 0 M526 HM4 autoclave 1 4 male 1 3 32 8 1 1 16 27 0 M527 HF6 Autoclave 3 8 female 1 4 36 1 1 1 16 27 0 M528 HM6 Autoclave 3 8 male 1 5 37 6 1 1 16 27 0 XP112 1 2 NPT female 0 6 15 2 1 1 16 27 0 XP113 1 2 NPT female 0 6 15 2 1 1 16 27 0 XP114 1 4 NPT female 0 6 15 2 1 1 16 27 0 XP115 1 4 NPT female 0 6 15 2 1 1 16 27 0 Type 2 3 5 Type 4 6 8 P0 P9 Type 7 9 Type K4 K6 Type K1 K3 Types K1 K3 a...

Page 4: ...allation sheet Do not mount unit in ambient temp exceeding published limits LIMITED WARRANTY Seller warrants that the product hereby purchased is upon delivery free from defects in material and workmanship and that any such product which is found to be defective in such workmanship or material will be repaired or replaced by Seller Ex works Factory Watertown Massachusetts INCOTERMS provided howeve...

Reviews: