Contact Resistance Tester MRL-11
11.O CONNECTIONS
Connect ‘Rx’ with test leads per CORRECT CONNECTION diagram shown below:
Rx
C+
C-
P+
P-
T
h
ic
k
l
e
a
d
T
h
in
l
e
a
d
T
h
in
l
e
a
d
T
h
ic
k
l
e
a
d
CORRECT CONNECTION
Rx
C+
C-
P+
P-
WRONG CONNECTION
12.0 OPERATING INSTRUCTIONS:
Ensure that connections to ‘Rx’ are proper and tight.
Connect mains power supply and switch rocker switch ON.
LCD displays as figure 1 below:
Fast measure
Measure
Data
Time PC
Figure ‘1’
MEASURE IN ‘FAST MEASURE’ mode:
‘Fast measure’ is automatically selected, to start test press ‘ENTER’ and automatically
after approximately 3 seconds ‘Rx’ and test current are displayed as per figure 2 below:
100A
1000.0 uOhm
Print Save
Figure ‘2’
By default cursor is at ‘Print’ and to print results, press ‘ENTER’. To save results, move
cursor with key to ‘Save’ and press ‘ENTER’.
Attention!