LISA-U2 series - System integration manual
UBX-13001118 - R27
System description
Page 39 of 183
C1-Public
1.6.1.3
Rising edge on RESET_N
When the module is in power-off mode (i.e. switched off with
VCC
maintained), the module can be
switched on by means of the
RESET_N
input pin alternatively to the
PWR_ON
input pin: the
RESET_N
signal must be forced low for at least 50 ms and then released to generate a rising edge that starts
the module power-on sequence.
RESET_N
input pin can also be used to perform
an “external” or “hardware” reset of
the module, as
described in section
Electrical characteristics of the LISA-U2 series
RESET_N
input are slightly different from the other
digital I/O interfaces: the pin provides different input voltage thresholds. Detailed electrical
characteristics are described in the LISA-U2 series data sheet
RESET_N
is pulled high to
V_BCKP
by an integrated pull-up resistor also when the module is in power-
off mode. Therefore an external pull-up is not required on the application board.
The simplest way to switch on the module by means of the
RESET_N
input pin is to use a push button
that shorts the
RESET_N
pin to ground: the module will be switched on at the release of the push
button, since the
RESET_N
will be forced to the high level by the integrated pull-up resistor,
generating a rising edge.
If
RESET_N
is connected to an external device (e.g. an application processor on an application board)
an open drain output can be directly connected without any external pull-up. A push-pull output can
be used too: in this case, make sure that the high level voltage of the push-pull circuit is below the
maximum voltage operating range of the
RESET_N
pin (specified in the
RESET_N
pin characteristics
table in the LISA-U2 series data sheet
). To avoid an unwanted power-on or reset of the module,
make sure to fix the proper level at the
RESET_N
input pin in all possible scenarios.
Some typical examples of application circuits using the
RESET_N
input pin are described in section
1.6.1.4
Real Time Clock (RTC) alarm
When the module is in power-off mode (i.e. switched off with
VCC
maintained), it can be switched on
by means of a previously programmed RTC alarm (see the u-blox AT commands manual
, AT+CALA
command) alternatively to the
PWR_ON
and
RESET_N
pins: the RTC system will initiate the power-
on sequence.
1.6.1.5
Additional considerations
The module is switched on when the
VCC
voltage rises up to the normal operating range (i.e. applying
supply properly, as described in section
): the module is commonly switched on in this way for
the first time. Then, the module must be properly switched off as described in section
, e.g. by
the AT+CPWROFF command.
When the module is in power-off mode, i.e. it has been properly switched off as described in the section
(e.g. by the AT+CPWROFF command) and a voltage within the operating range is maintained at
the
VCC
pins, the module can be switched on by a proper start-up event (i.e. by
PWR_ON
as described
in
, or by
RESET_N
, or by RTC alarm as
described in section