INSTALLATION REGULATIONS

Ubiflux Vigor W225

English

Summary of Contents for 0882250

Page 1: ...INSTALLATION REGULATIONS Ubiflux Vigor W225 English ...

Page 2: ...have received clear instructions on the safe use of the appliance and understand the possible dangers on the condition that the appliance has been placed and installed in the normal position for use Children between the ages of 3 and 8 may not insert the plug into the socket nor clean or make changes to the settings of the appliance nor carry out any maintenance on the appliance that would normall...

Page 3: ... Maintenance siphon 31 9 3 Maintenance installer 32 10 Electrical diagram 35 11 Electrical connections accessories 37 11 1 Connecting position switch 37 11 1 1 Connecting position switch with filter indication 38 11 1 2 Connecting wireless remote control without filter indication 39 11 1 3 Connecting extra multiple switch with filter indication 40 11 1 4 Connecting extra multiple switch with filte...

Page 4: ...imensions It is possible however to later equip the appliance with a Plus pcb The appliance comes ready to plug in with a 230 V mains plug 3 Version 3 1 Technical information Ubiflux Vigor W225 Plus Supply voltage V Hz 230V 50Hz Dimensions w x h x d mm 600 x 650 x 455 Duct diameter mm ø125 Ext diameter condensate discharge mm ø32 Weight kg 29 Filter class ISO Coarse 60 ISO ePM1 0 50 for the air su...

Page 5: ... a right hand version the warm connections 1 3 are on the right hand side of the appliance Left hand version Right hand version All dimensions in millimeters Diameter of all collars is 125 mm All dimensions in millimeters Diameter of all collars is 125 mm 1 To dwelling 2 To outside 3 From dwelling 4 From outside 5 Electrical connections 6 Siphon connection 7 Exhaust air filter 8 Supply air filter ...

Page 6: ...or example be chosen but control is also possible with the Air Control Connecting Air Control page 42 CO2 sensor s Connecting CO sensor s page 43 a humidity sensor Connecting humidity sensor page 45 or the App 4 2 Bypass The 100 bypass makes it possible to supply outside air which is not heated up by the heat exchanger Particularly during summer nights it is desirable to supply cooler outside air ...

Page 7: ...tions regarding the ventilation of homes and residential Safety provisions for low voltage installations The regulations for connecting indoor plumbing in homes and residential buildings Any additional regulations of the local power companies The installation regulations of the Ubiflux Vigor W225 appliance In addition to the above design and installation requirements and recommendations the nation...

Page 8: ...32 not supplied with the appliance so that the siphon can be cleaned easily in the future The condensate discharge can be connected for example with a straight or angled connection with gasket Slide the condensate discharge connection with gasket with sufficient length across the connection of the siphon Important Never switch the two condensate discharge connections below the appliance Important ...

Page 9: ... of 5 m s in the main ducts and 3 5 m s in the branches The location of the discharge of the mechanical ventilation air and the sewer stack vent must be chosen to prevent noise nuisance The location of the input valves must be chosen in such a way to prevent fouling and drafts We recom mend using input valves When using flexible mufflers account must be taken during the installation that these may n...

Page 10: ...a building management system Using the red 3 pole connector X15 or with the Plus version the red connector X06 on the UWA2 E pcb a connection can be made between the appliance and the ModBus system Electrical diagram page 35 for the right connection For the correct setting of the jumpers X12 X121 X122 see the explanation given with electrical diagram Electrical diagram page 35 for more information...

Page 11: ...used to operate the appliance and to provide the user with information about the status of the appliance When the mains power is switched on the software version is first shown the main screen is then displayed Main screen 6 2 Display layout The screen is divided up into 6 zones where various symbols displays can be shown per zone Layout of main screen Filter message and fault message are located ...

Page 12: ...demand driven ventilation Break contact active or make contact active This appliance is set as Master appliance if a number of appliances are connected cascade Appliance is set as Slave appliance maximum of 9 appliances can be connected to a Master Control via eBus for example Air Control Control via ModBus or externalBus Bypass boost is active Zone no Symbol on display Description 4 Internet conn...

Page 13: ...ve to reset the correct language time and date in setting menu 4 The appliance will then operate immediately after this according to the mode of the multiple switch If no multiple switch is connected then the appliance operates always in mode 1 Switching off Switching off mains power 1 Pull the 230 V power plug from the electric system the appliance is now free of voltage 2 Nothing is now shown on...

Page 14: ...ay Codes Non locking fault When the appliance detects a non locking fault it will keep running limitedly The permanently lighted display shows the fault symbol Press the fault symbol for an explanation solution to the fault The screen can be left by pressing the Home button If a fault cannot be solved please contact the installer Locking fault When the appliance detects a locking fault it will no ...

Page 15: ...t available Take voltage from appliance Replace UWA2 B pcb Fault is automatically reset when voltage is again put back on appliance E1155 E2000 Touchscreen fault general fault message Fault codes only visible when using service tool Check wiring to touchscreen replace wiring if damaged replace touchscreen if fault still occurs replace UWA2 B Fault is automatically reset when voltage is again put b...

Page 16: ... Home button and the display then returns to the main screen the filter message is reset and the filter message now disappears Comment If the filter wizard is opened in order to replace the filter whilst there is no filter message on the display screen go in the settings menu to step number 4 2 to open the filter wizard Now follow the instructions on the display and once finished the timer of the ...

Page 17: ...r supply by pulling out the plug Open the filter door 2 Remove the two filters 3 Remove the front cover 4 Remove the heat exchanger Be careful not to damage the foam parts in the appliance 5 Wash the heat exchanger with hot water max 45 C and a regular detergent Then rinse the exchanger with hot water 6 Fold down the fan lock to create space underneath the fan 32 Art nr 616711 A Ubiflux Vigor W225...

Page 18: ...ly back into the appliance when doing so take care that the EPS parts and rails in the appliance are not damaged which could otherwise leads to internal leaks in the appliance Take care when returning the heat exchanger that the text on the type plate is not upside down Place the heat exchanger back such that this type plate is visible 13 Put the front cover back on and screw it secure 14 Install ...

Page 19: ...service activities then a wizard starts up automatically follow the instructions on the display for the correct connection of the fan cables Basic print X15 externalBus ModBus X16 24V X17 eBus X18 24V max 5VA X19 Signal Output Plus print X03 24V X04 externalBus X06 ModBus X08 Contact input 1 X09 Contact input 2 X10 Relais output 1 X11 Relais output 2 X12 Analog input 0 tot 10 V X13 Analog input 0 ...

Page 20: ...for wireless remote control C Transmitter with 4 settings for example kitchen D Transmitter with 2 settings for example bathroom E Any additional 2 or 4 settings transmitters maximum of 6 transmitters can be signed on to 1 receiver F Modular cable Note For the modular cable that is used the tab of both modular connectors must be mounted facing the mark on the modular cable Wire colors C1 C6 may va...

Page 21: ...t on the type of modular cable used 11 1 4 Connecting extra multiple switch with filter indication A Ubiflux Vigor appliance For example a Ubiflux Vigor appliance type 4 0 B1 Multiple switch with filter indication B2 Extra multi switch with filter indication C Splitter D Modular cable Note For the modular cable that is used the tab of both modular connectors must be mounted facing the mark on the ...

Page 22: ...nector E Position green eBus connector to rear of control 1 Ubiflux Vigor appliance 2 Basis pcb 3 Cover 4 The cable that comes with RH cable 5 RH humidity sensor 6 Duct from dwelling A Ubiflux Vigor appliance To switch on and set the sensitivity of the humidity sensor go to step number 7 1 and 7 2 in the settings menu 42 Art nr 616711 A Ubiflux Vigor W225 43 ...

Page 23: ...air quality Matching the ventilation need with demand driven ventilation can be done in two different ways namely based on CO2 measurements or based on a time program Two different sets are available for this Manual operation with the aid of an extra connected multiple switch of course remains a possibility as well For further information regarding setting operating and connecting demand driven ve...

Page 24: ...appliance 4 Temperature sensor 5 PCB type UVP1 6 Airflow direction 7 Dipswitch setting postheater 1 Heating coil 2 Maximum safety with manual reset 3 2 pole eBus connection X17 on appliance 4 Temperature sensor 4 PCB type UVP1 5 Airflow direction 6 Dipswitch setting preheater C1 brown C2 blue C3 green yellow C4 black C5 white C1 brown C2 blue C3 green yellow C4 black C5 white ...

Page 25: ...ng on and off Off On off 11 2 Switch temperature 1 5 C 0 0 C 10 0 C 11 3 Switch temperature 2 25 C 15 0 C 40 0 C 11 4 Mode valve 10 volt control Closed Open Closed 11 5 Valve control Relay output 1 Relay output 1 Relay output 2 Analogue output 1 Analogue output 2 When using a geo heat exchanger parameter 11 1 must be changed from OFF to ON 12 Service 12 1 Exploded view When ordering parts in addit...

Page 26: ...s pcb UWA2 E 0883246 9 Mains plug and cable 230 V 0883261 10 Internal preheater incl maximum security 11 Temperature sensor NTC 10K 0704637 12 Condensation discharge 0883264 13 Cable set 0883265 14 Cable set 15 Side panel 1 item universal left right The power cable is fitted with a circuit board connector When replacing it always order a replacement mains cable from Ubbink NV To prevent dangerous ...

Page 27: ...ypass temperature from outside 10 C 7 C 15 C 2 4 Bypass hysteresis 2 C 0 C 5 C 2 5 Mode Bypass boost Uit Aan Uit 2 6 Fan setting selection Bypass boost 3 0 1 2 of 3 3 Frost protection 3 1 Frost temperature 0 C 1 5 C 1 5 C 3 2 Minimum intake temperature 10 C 7 C 22 C Step no Description Factory settings Setting range Comment 4 Filter message 4 1 Number of days until filter message 90 1 365 days 4 2...

Page 28: ...liance with Plus pcb Step no Description Factory settings Setting range Comment 9 Switch contacts 9 1 Make or break contact 1 Make Make Break 9 2 Switch contact control 1 Off Off On Meets Bypass conditions Open bypass valve Open external valve 9 3 Contact 1 Supply fan action Fan off Fan off Fan runs at absolute minimum Fan at setting 1 Fan at setting 2 Fan at setting 3 Fan at step 0 Fan according ...

Page 29: ...de valve 24 volt control Closed Open Dicht 11 5 Valve control Relay output 1 Relay output 1 Relay output 2 Analogue output 1 Analogue output 2 14 Conformity declaration Conformity declaration Manufacturer Ubbink NV Address Jan Samijnstraat 9 BE 9050 Gentbrugge Belgium Product Heat recovery appliance type Ubiflux Vigor W225 Ubiflux Vigor W225 Plus The product described above complies with the follo...

Page 30: ... heat exchanger Recuperative plastic cross counterflow heat exchanger Thermal efficiency 92 Maximum flow rate 225 m h Maximum rated power 165 W Sound power level Lwa 39 dB A Reference flow rate 158 m h Reference pressure 50 Pa Specific Power Input SEL 0 17 Wh m Control factor 1 0 in combination with multiple switch 0 95 in combination with clock control 0 85 in combination with 1 sensor 0 65 in co...

Page 31: ...ing Sustainable materials are used in the manufacture of this appliance The packaging should be disposed of in a responsible manner and in accordance with governmental regulations 60 Art nr 616711 A Ubiflux Vigor W225 61 ...

Page 32: ... Jan Samijnstraat 9 B 9050 Gentbrugge Tel 32 0 9 237 11 00 www ubbink be info ubbink be Ubbink UK Ltd Unit 2 Redbourne Park Liliput Road Brackmills Ind Est Northampton NN4 7DT T 44 0 1604 433000 F 44 0 1604 433001 ...