SMoG-HoG

®

SHn Series Models 

2

SMOG-HOG NOMENCLATURE

Smog-Hog electronic air cleaners are available in a 

variety of configurations and sizes. codes shown below 

identify characteristics which might be built into a given 

unit. the model number completely identifies the design 

and can be found on the unit nameplate. For example, 

a model designated SHn-10-H could be defined 

according to descriptions listed below (see bold):

 SHN

  - SMoG-HoG n-Series 

  10

  - airflow in 100s of cfM (i.e., 10 @ 1,000 cfM, etc.) 

  H

  - High static pressure blower* 

  HH

  - Higher static pressure 

  XB

  - Without blower* 

  T

  - tee-shaped unit (SHn-50 only) 

  M

  - Double pass models* 

 

    *not available on SHn-50 models

Models SHN-10, SHN-20, SHN-40 & SHN-50

this type of Smog-Hog is a self-contained, two-stage, 

Penney-type, electrostatic precipitator complete with 

fully-interlocked, energy-limiting, high voltage power 

supply, mechanical prefilter, ionizer, collection cell, 

afterfilter, blower assembly, indicator light, interlock 

switch and push-to-test buttons. Models available 

include:

 

SHn-10 SHn-40

 

SHn-20 SHn-50-t

Models SHN-10-XB, SHN-20-XB, SHN-40-XB

this type of Smog-Hog is a self-contained, two-stage, 

Penney-type, electrostatic precipitator complete with 

fully-interlocked, energy-limiting, high voltage power 

supply, mechanical prefilter, ionizer, collection cell, 

afterfilter, indicator light, interlock switch and push-to-

test buttons. XB units are designed for use in a ducted 

application where a blower is included in the existing 

ventilation system. Models available include:

 

SHn-10-XB

 

SHn-20-XB

 

SHn-40-XB

SHN Series Voltages Available

  Voltage  Phase  HZ  Voltage  Phase  HZ

 

115 

60 

230 

60

 

115 

50 

400 

50

 

208 

60 

460 

60

 

220 

50 

575 

60

1. INSPECTION NOTE

upon receipt of your unit, check for any shipping 

damage. a damaged carton indicates that the 

equipment may have received rough handling during 

shipping that may have caused internal damage. notify 

your delivery carrier and enter a claim if any damage is 

found.

2. INSTALLATION PLANNING

A.  Unducted or Area Capture. 

consideration should 

be given to the placement of the precipitator to 

maximize its effectiveness. The number of units 

required to clean the air will depend on the layout of 

the room and the concentration of pollutants.

Because it is necessary to develop proper airflow 

patterns, the placement and number of precipitators 

should be as suggested by uaS or your local 

representative.

B.  Ducted or Source Capture. 

When your Smog-Hog 

is used as a ducted source collector, the enclosure 

or pick-up hood design is important for adequate 

capture of contaminants. Drive pulleys and belts 

have been selected to provide proper airflow at the 

design static pressure specified. Pulleys and belts 

should not be replaced without first contacting uaS 

customer Service at 1-800-252-4647.

Do not operate this equipment in the presence of

 

combustible vapors or gases.

C.  Access Clearance. 

allow at least 36” (914mm) door 

swing and access clearance on the door side of the 

unit. All models require 18” (457mm) clearance from 

the electrical junction box on top of the unit to any 

overhead obstruction to allow adequate access.

3. INSTALLATION

carefully remove the unit from the shipping container, 

inspecting for shipping damage. for ease of installation, 

open access door and remove the cell, ionizer and 

filters from the cabinet.
ceiling mounted units are suspended by means of 

1⁄2” threaded rods run through weld nuts in the top 

corners of the units. (refer to page 3 and 4 for weld 

nut locations on all but XB models.) additional support 

should be used for auxiliary equipment or ducting.

reinstall the components removed earlier to facilitate 

the mounting of the unit.

A.  Unit Mounting. 

Models SHn-10 and SHn-20 are 

designed for suspended mounting. units can be 

provided with eyebolts for chain hanging, but the 

length of chain should be kept level. the preferred 

method of hanging is by threaded rods through 

the top of the cabinet. if chain is used, it should 

be of the welded link type, with a 2,000 lb. (8900 

n.) test strength or better. “S” hooks used for 

connections should be closed. the chain should 

be hung vertically. if any angle is introduced, the 

chain and fasteners should be sized to handle the 

added tension. Models SHn-40 and SHn-50 may be 

suspended by rods but are not approved for chain 

hanging.

!

  CAUTION

Summary of Contents for CLARCOR Smog-Hog SHN-10

Page 1: ...Model SHN 20 Shown Smog Hog Electrostatic Precipitator l models SHN 10 SHN 20 SHN 40 AND SHN 50 OWNER S MANUAL ...

Page 2: ... following information available when contacting UAS UAS ORDER _________________________________________________________________ UNIT MODEL ________________________________________________________________ UNIT SERIAL _________________________________________________________________ SYSTEM ACCESSORIES ______________________________________________________________________________ ___________________...

Page 3: ...efilters 7 B Mist Stop Filter 7 C Ionizing Sections 7 D Collection Cells 7 E Afterfilters 7 F Power Packs 7 G Push to Test Buttons 7 H Blower 7 I Drive 7 J Discharge Grill 7 K Cabinet 7 L Component Access Door Electrostatics 7 M Access Door Drive Set 7 9 MAINTENANCE 8 A Cleaning Instructions 8 B Component Cleaning Methods 9 C Other Cleaning Considerations 9 D When are Components Clean 9 10 PERIODI...

Page 4: ...explosive Use non flammable cleaners Keep flammable materials and vapors such as gasoline away from unit The unit should be inspected frequently and contaminants removed to prevent excessive accumulation which may result in flash over or fire damage Operate only in a safe and serviceable condition Operating temperature to the air stream should not exceed 120 F 49 C DANGER WARNING WARNING CAUTION C...

Page 5: ... 4 2 4 2 02 4 2 PTIONAL IST 3TOP ILTER 3 2 2 7 2 5 4 3 4 42 8 4 2 37 4 4 2 37 4 4 2 43 053 4 4 34 544 3 3 2 2 02 4 2 PTIONAL IST 3TOP ILTER 2 4 4 2 4 2 7 2 5 4 3 4 42 8 4 2 37 4 3 2 2 02 4 2 PTIONAL IST 3TOP ILTER 2 4 2 4 2 4 2 43 053 4 4 34 544 3 7 2 5 4 3 4 4 053 4 4 34 544 053 4 4 34 544 3 2 7 42 8 Smog Hog Electrostatic Precipitator Installation and Service ...

Page 6: ...to the placement of the precipitator to maximize its effectiveness The number of units required to clean the air will depend on the layout of the room and the concentration of pollutants Because it is necessary to develop proper airflow patterns the placement and number of precipitators should be as suggested by UAS or your local representative B Ducted or Source Capture When your Smog Hog is used...

Page 7: ...ufficiently sloped 1 5 inches 38mm diameter and vented All plumbing should conform with all state and local codes Appropriate design criteria as provided by a plumbing mechanical contractor should be utilized to ensure proper control of drainage from the SHN Unit 5 DISCHARGE GRILL The four way adjustable air discharge grill can be set to any open position desired A Unducted Installation for area c...

Page 8: ...nd unit is ready for operation Input to the high voltage power pack should not exceed 130 Volts 60 Hertz This is supplied by a power source or the step down transformer as shown in the wiring diagram inside the main electrical junction box on all units Refer to Appendix B Units are factory wired for the voltage requirement indicated to UAS by the customer The electrical box has knockouts Therefore...

Page 9: ...Revised 09 15 SMOG HOG SHN Series Models 5 SHN 10 Dimensions and Mounting Hole Locations SHN 20 ...

Page 10: ...Revised 09 15 SMOG HOG SHN Series Models 6 SHN 40 Dimensions and Mounting Hole Locations SHN 50 T ...

Page 11: ...ng The insulators along with the cell s long plate design assure maximum efficiency and retention of collected contaminant E Afterfilters Heavy duty reusable industrial aluminum mesh filters aid even air distribution across the cells and trap any collected contaminant that could release from the cells during start and stop operations F Power Supply The proprietary design high voltage power supply ...

Page 12: ...quired for effective cleaning at reasonable detergent cost Typically 20 1 is recommended as a starting point Experimentation is recommended Never mix acid and alkaline detergent for manual cleaning Detergent mixing could cause rapid heat release gel formation or other undesirable conditions Water Temperature Detergents can be up to twice as effective in hot water and hot water alone is very effect...

Page 13: ...ssure Washer A self contained pressure washer with a spray wand can be an effective cleaning method providing it is used with caution Care should be taken not to expose collection cell plates to close up and prolonged blasts of high temperature or high pressure water Cell plates deform under continuous exposure to such conditions C Other Cleaning Considerations The previous methods address the cle...

Page 14: ...or of the cabinet 4 The door gasket should be formed to the complete cabinet lip edge before applying silicone sealant Place the trim edge at the top center of the cabinet lip edge and press gasket in place ending at the same location Do not trim excess 5 Remove door gasket and apply silicone sealant to the inside of gasket or on the inside edge of the cabinet lip edge Place the trim edge at the t...

Page 15: ... can be accomplished by waiting one minute after placing power in the off position or refer to Figures 4 and 5 The power pack total current output is limited to a maximum of 5 milliamps to ensure personnel safety Troubleshooting Procedures High voltage issues can generally be isolated by referring to the indicator light When the light illuminates high voltage is present from the power pack to the ...

Page 16: ...ER PACK The power should be placed in the off position to the power pack Carefully disconnect both high voltage wires Ionizer 8 and Collector 7 from the power pack The high voltage wires should carefully be placed away from the ionizer and collector cell power pack connectors eliminating the high voltage wires from contacting the power pack connectors Place the power to the unit in the on position...

Page 17: ...CATOR LIGHT Sometimes removing the collector cell s and installing the collector cell s into the unit will clear a flashing indicator light condition If not check the causes below Dirty collector cell s contaminant build up requiring manual cleaning Wet collector cell s not properly dried after a wash cycle or manual cleaning procedure Use compressed air to accelerate the drying time Deformed coll...

Page 18: ...llector cell circuit high voltage wire 7 refer to Figure 13 Fluctuating high voltage during a measurement will indicate an arcing circuit 12 Bench Test Procedure TOOLS REQUIRED One power pack Two high voltage wires 6 ft 1829mm in length with test clips at each end of the wire High voltage probe Refer to operating instructions by the manufacturer If a high voltage probe is not available install a U...

Page 19: ...l will not maintain high voltages above 7 5 KVDC The collector cell will continuously arc Usually this condition is caused by a power pack above the High Voltage Specifications The power pack should be replaced There is a high voltage problem if the indicator light is flashing 7 If there is an arcing condition determine the problem and repair 8 Disconnect AC cable plug from the wall outlet COLLECT...

Page 20: ...om component access door and part numbers available when ordering Properly Aligned SHN Assembly QUANTITY ITEM NO PART NO DESCRIPTIONS REQUIRED 1 02 2339 S COLLECTION CELL ASSEMBLY 2 2 02 0037 S IONIZER ASSEMBLY 2 3 37 0027 COLLECTION CELL FEED THRU INSULATOR 1 4 37 0026 IONIZER FEED THRU INSULATOR 1 5 36 0014 CELL IONIZER INSULATOR SPRING 2 6 36 0077 GROUND SPRING 4 7 30 0387 COLLECTION CELL CONTA...

Page 21: ...MIT SWITCH CABINET DOOR INTERLOCK 20 0005 GASKET EDGE BUNA N 42 0168 BLOWER BELT DRIVE 3 4 SGL 9 7 SHN 10 32 0059 BLOWER BELT DRIVE 3 4 DBL 9 7 SHN 20 32 0036 BLOWER BELT DRIVE 1 SGL 15 15 SHN 40 50 T 32 0063 MOTOR 7 1 2HP 208 230 460 3 60 22 0288 MOTOR 5HP 208 230 460 3 60 22 0023 MOTOR 3HP 190 208 230 460 3 50 60 22 0022 MOTOR 1HP 208 3 60 22 0012 MOTOR 2HP 208 230 460 3 60 22 0039 MOTOR 1 2HP 1...

Page 22: ... 1 0 0 6 1 0 0 5 1 0 0 4 1 0 0 3 1 0 0 2 1 0 0 1 1 0 0 0 1 0 0 9 0 0 8 0 0 7 P H 2 P H 1 P H 2 1 SHN 20 3 5 0 0 4 4 0 1 H S 1 0 5 2 1 S S C s l x s e v r u c n a f 0 1 H S H S E V R U C W O L F R I A N 3 5 0 0 4 4 0 1 0 0 5 0 0 1 5 1 0 2 5 2 0 3 0 0 0 2 0 5 7 1 0 0 5 1 0 5 2 1 0 0 0 1 0 5 7 0 0 5 0 5 2 0 M F C w o l F r i A External Static Pressure WG 0 0 0 2 0 0 9 1 0 0 8 1 0 0 7 1 0 0 6 1 0 0 5 ...

Page 23: ... c n a f T 0 5 0 4 H S H S E V R U C W O L F R I A N 5 0 7 0 4 4 T 0 5 0 1 2 3 4 0 0 0 0 1 0 0 0 2 0 0 0 3 0 0 0 4 0 0 0 5 M F C w o l F r i A External Static Pressure WG 0 0 4 1 0 0 3 1 0 0 2 1 0 0 1 1 0 0 0 1 0 0 9 0 0 8 0 0 7 P H 5 P H 3 0 0 6 SHN 50 T SHN 40 SHN SERIES AIRFLOW CURVES ...

Page 24: ...Revised 09 15 SMOG HOG SHN Series Models 20 SHN 10 20 XB SHN 10 20 APPENDIX B WIRING DIAGRAMS ...

Page 25: ...Revised 09 15 SMOG HOG SHN Series Models 21 SHN 40 SHN 10 20 M WIRING DIAGRAMS ...

Page 26: ...Revised 09 15 SMOG HOG SHN Series Models 22 SHN 40 M SHN 40 XB WIRING DIAGRAMS ...

Page 27: ...Revised 09 15 SMOG HOG SHN Series Models 23 SHN 50 T WIRING DIAGRAMS ...

Page 28: ...ods manufactured or supplied by others This warranty is subject to any limitations in UAS quotation and may not be modified except by a written instrument signed by the President or Vice President of Sales of UAS THIS WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES WHETHER WRITTEN ORALOR IMPLIED INCLUDINGANYIMPLIED WARRANTYOF MERCHANTABILITY FITNESS FOR A PARTICULAR PURPOSE OR NONINFRING...

Reviews: