UAS CLARCOR SMOG-HOG MSH Series Owner'S Manual Download Page 11

7

revised 03/15

SMoG-HoG

®

electronic air cleaner

HIGH VOLTAGE PROBE MEASUREMENTS 

A high voltage probe (refer to manufacturers 

instructions) is required to measure high voltage output 

from the power pack. the component door should 

be closed with unicell(s) installed, the indicator light 

illuminated and high voltage wires #8 and #7 connected 

to the power pack. refer to figure 3. if the indicator 

light is flashing or not illuminated perform SteP 1 and if 

required SteP 2 as outlined earlier in this section.  
“With Load” is a measurement with high voltage wires 

#8 and #7 connected to the power pack and unicell(s) 

installed. 
1.  Place MSH "on". 
2.  open the lid door to the power pack enclosure and 

connect the ground wire from the high voltage probe 

to the bare metal surface.

3.  Place the tip of the high voltage probe to the ionizer 

door feed through insulator bolt. the high voltage 

measurement should be 10.0 to 11.8 KVDC. 

 

if the ionizer voltage is below specifications refer step 

2, “Ionizer Conditions Causing Failure.” Low ionizer 

voltage will decrease the collector cell voltage but 

low cell voltage will not affect the ionizer voltage.    

4.  Place the tip of the high voltage probe to the collector 

cell door feed through insulator bolt. the high voltage 

measurement should be 5.0 to 7.3 KVDC.  If the 

collector cell voltage is below specifications refer step 

2, “Collector Cell Conditions Causing Failure.” 

“no Load” is a measurement of the power pack with 

high voltage wires #8 and #7 disconnected from the 

power pack. 
1.  Place MSH "off". 

2.  Remove the high voltage wires #8 and #7 from 

the power pack gently bend high voltage wires to 

eliminate the high voltage wires from touching the 

power pack connectors. 

3.  Place MSH "on". 
4.  Place the tip of the high voltage probe to the ionizer 

and to the collector power pack connectors. the high 

voltage measurement should be 10.0 to 11.8 KVDC 

to the ionizer and 5.0 to 7.3 KVDC to the collector 

cell. if high voltage is below specifications to one or 

both circuits replace the power pack.    

Summary of Contents for CLARCOR SMOG-HOG MSH Series

Page 1: ...Industrial Electrostatic Air Cleaner l SMOG HOG MSH Model OWNER S MANUAL ...

Page 2: ...ce have the following information available when contacting UAS UAS ORDER _________________________________________________________________ UNIT MODEL ________________________________________________________________ UNIT SERIAL _________________________________________________________________ SYSTEM ACCESSORIES ______________________________________________________________________________ ________...

Page 3: ...G 2 5 1 Normal Maintenance 2 5 2 Manual Cleaning of SMOG HOG Components 3 5 3 Manual Cleaning Methods 3 5 4 Appearance Of Components After Cleaning 4 5 5 Replacing Damaged Ionizer Wires 4 6 TROUBLESHOOTING 4 6 1 Tools Required 4 6 2 Perform Before Troubleshooting 4 6 3 Troubleshooting Procedures 5 6 4 Troubleshooting Table 8 7 REPLACEMENT PARTS 9 7 1 Replacement Parts List 9 8 FIGURES 10 12 9 WIRI...

Page 4: ...cessive accumulation which may result in flash over or fire damage The air cleaner should not be used for support of personnel or material Operate only in a safe and serviceable condition DANGER WARNING CAUTION C A U T I O N This is the safety alert symbol This symbol alerts you to potential hazards that can kill or hurt you and others All safety messages will follow the safety alert symbol and th...

Page 5: ...en using power pack 21 1216 and 5 6mA when using power pack 21 1234 In the event of a short circuit or other overload condition the power supply is designed to cause the high voltage to collapse When the voltage collapses the indicator light will blink When the overload is removed the voltage will automatically build up to normal and the indicator light will illuminate The power supply is self pro...

Page 6: ...ions Periodically momentary shorts will occur indicated by the flickering indicator light If the light is dim fails to glow or continues to flicker the components may need cleaning or servicing see Cleaning Instructions Section 5 2 and 5 3 5 MAINTENANCE AND MANUAL CLEANING 5 1 Normal Maintenance Once the unit is operational periodic maintenance is necessary to assure proper performance Follow a re...

Page 7: ...mation or some other undesirable condition Time is necessary for effective cleaning Soaking may seem slower and less effective than high impingement and or hot water above 180 F for cleaning action so personnel should be forewarned about using excessive pressure or temperature to shortcut the cleaning process High pressure or stream spray cleaning until plate edges are shiny is not effective Not o...

Page 8: ...kets are cleaned and intact 3 Component tracks are free of contaminant build up for unicell grounding 4 Module drain sump is cleaned and free flowing 5 Interior is free of extreme contaminant build up 6 Blower wheel is free of contaminant build up 5 5 REPLACING DAMAGED IONIZER WIRES 1 Remove the damaged wire from each spring Also replace spring if it is damaged 2 Loop one end of the new wire over ...

Page 9: ...high voltage The grounding procedure statement is not identified within the troubleshooting steps but should be performed The power pack total current output is limited to a maximum of 5 milliamps to assure personnel safety A high voltage probe is required to measure high voltages to the ionizer and collector circuits to the unit As an accessory a high voltage probe can be purchased for a multimet...

Page 10: ...ar itself by removing the unicell s from the module and then installing the unicell s back into the module Place MSH off connect all wires which have been disconnected and install unicell s b Indicator light is illuminated with the high voltage wire 7 connected to the collector cell connector on the power pack Place MSH off and connect high voltage wire 8 to the ionizer connector on the power pack...

Page 11: ... 11 8 KVDC If the ionizer voltage is below specifications refer step 2 Ionizer Conditions Causing Failure Low ionizer voltage will decrease the collector cell voltage but low cell voltage will not affect the ionizer voltage 4 Place the tip of the high voltage probe to the collector cell door feed through insulator bolt The high voltage measurement should be 5 0 to 7 3 KVDC If the collector cell vo...

Page 12: ...fective Unicell dirty Unicell malfunction Unicell installed backwards or upside down High voltage contacts dirty Loss of input voltage Unicell malfunctioning Power supply defective POSSIBLE SOLUTIONS Replace lamp Check connection to lamp Check power supply Replace air mover Clean foreign object from air mover Replace control switch Check connection at control switch Correct wiring Engage safety in...

Page 13: ...r 33Ͳ10116 33Ͳ10121 2 Unicell 02Ͳ10429Ͳ0001ͲS 02Ͳ1921ͲS 3 Mesh AfterͲFilter 33Ͳ10110 33Ͳ10120 4 Inlet Cone Ring 32Ͳ10053 32Ͳ10067 5 Motorized Impeller Fan 32Ͳ10052 32Ͳ10065 6 Ionizer Spring 36Ͳ0068 36Ͳ0068 7 Cell Spring 36Ͳ0012 36Ͳ0012 8 Cell Ground Spring 36Ͳ0016 36Ͳ0016 9 Interlock Switch 20Ͳ0005 20Ͳ0005 10 Filter Door Latch 39Ͳ10055 39Ͳ10055 11 Feed Through Insulator 37Ͳ0026 37Ͳ0026 12a Power P...

Page 14: ...10 Revised 03 15 SMOG HOG Electronic Air Cleaner Figure 1 Unit Components ...

Page 15: ...1 Revised 03 15 SMOG HOG Electronic Air Cleaner Figure 2 Drain Loop Assembly Figure 4 Replacing Ionizer Section Figure 3 Ionizer and Cell Voltage Measurement Figure 5 Grounding The Collector Cell Section ...

Page 16: ...12 Revised 03 15 SMOG HOG Electronic Air Cleaner Figure 6 Grounding the Ionizing Section Figure 7 Power Pack Input Output Connections ...

Page 17: ...13 Revised 03 15 SMOG HOG Electronic Air Cleaner MSH 05 ...

Page 18: ...14 Revised 03 15 SMOG HOG Electronic Air Cleaner MSH 05 M ...

Page 19: ...15 Revised 03 15 SMOG HOG Electronic Air Cleaner MSH 11 ...

Page 20: ...16 Revised 03 15 SMOG HOG Electronic Air Cleaner MSH 11 M ...

Page 21: ...17 Revised 03 15 SMOG HOG Electronic Air Cleaner MSH 11 w Optional ON OFF Switch ...

Page 22: ...18 Revised 03 15 SMOG HOG Electronic Air Cleaner MSH 05 1PH Interconnect MSH 11 1PH Interconnect ...

Page 23: ...19 Revised 03 15 SMOG HOG Electronic Air Cleaner MSH 05 3PH Interconnect MSH 11 3PH Interconnect ...

Page 24: ...dified except by a written instrument signed by the President or Vice President of Sales of UAS THIS WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES WHETHER WRITTEN ORALOR IMPLIED INCLUDINGANYIMPLIED WARRANTYOF MERCHANTABILITY FITNESS FOR A PARTICULAR PURPOSE OR NONINFRINGEMENT As Purchaser s exclusive remedy for any defects in the equipment UAS will exchange or repair any defective part...

Reviews: