7
110328-04 - 2/23
ALTA
Installation, Operating & Service Instructions
Table 3-6: Weights and Volume
Electrical Requirements
: 120 VAC, 60 Hz, 1-ph. 1.8A for boiler and pump + current draw of any external pumps
connected to boiler.
Controls: Boiler flow switch and integrated manual reset high limit provided with boiler are both UL-353 listed.
LP Gas Conversion
: Boiler is shipped from factory configured for natural gas and is field convertible to LP gas. See
Section 14 Start-up and Checkout for instructions to convert to LP gas.
Altitude
: Only part no. ending in -00 (i.e. ALTA-180-1G
00
) is listed for 0 to 10,100 ft. (3,079 m). See Section 14
Start-up and Checkout for altitude conversion instructions.
For part no. ending in -02 (i.e. ALTA-180-1G
02
), boiler is listed for 0 to 2,000 ft. (610 m). Do not install above 2,000
ft. (610 m).
Model
Number
Shipping
Weight lb.
(kg)
Empty Boiler
Weight lb.
(kg)
Shipping
Crate D in.
(mm)
Shipping
Crate W in.
(mm)
Shipping
Crate H in.
(mm)
Water
Content
gal (L)
Heat Exchanger
Surface Area ft
2
(m
2
)
ALTA-080
107 (49)
71 (32)
41.4 (1050) 20.0 (508) 18.3 (465)
0.5 (1.9)
9.99 (0.9)
ALTA-120
ALTA-120B
112 (51)
76 (35)
41.4 (1050) 20.0 (508) 18.3 (465) 0.75 (2.8)
11.99 (1.11)
ALTA-150
132 (60)
103 (47)
41.4 (1050) 20.0 (508) 22.3 (567)
1.0 (3.8)
17.98 (1.67)
ALTA-180
132 (60)
103 (47)
41.4 (1050) 20.0 (508) 22.3 (567)
1.0 (3.8)
17.98 (1.67)
Figure 3-6: Boiler Connections
Air Intake
Vent
Front View
Low Voltage
Knockouts
Boiler
Supply
Boiler
Return
120 VAC
Knockouts
Gas
Condensate Trap
Cleanout
Condensate Drain
Bottom View
3
Specifications
(continued)