06/2006
11
www.U-LineService.com
1175R, 1175WC and 1175BEV Models
Checking Door Alignment
The unit’s door is aligned at the factory before shipment.
However, its alignment could have been disturbed during
shipment or during door panel installation.
IMPORTANT
Properly aligned, the door's gasket should be firmly in
contact with the cabinet all the way around the door (no
gaps).
1. Carefully examine the door's gasket to assure that it is
firmly in contact with the cabinet.
Note:
When inspecting door alignment, make sure the
light switch bracket makes contact with the light switch
plunger. Also make sure the door gasket is not pinched on
the hinge side of the door
.
2. If the door is properly aligned, go on to
6 Prepare
Power Supply
. If it is not, use the following procedure.
Adjusting Door Alignment
IMPORTANT
Properly aligned, the door’s gasket should be firmly
in contact with the cabinet all the way arond the
door (no gaps). Carefully examine the door’s gasket
to assure that it is firmly in contact with the
cabinet. Also make sure the door gasket is not
pinched on the hinge side of the door.
1175R, 1175WC
and
1175BEV Units
1. Loosen (do not
remove) top and
bottom hinge
screws. See
Figure 16
.
2. Align door squarely
with cabinet. Make
sure gasket is firmly
in contact with
cabinet all the way
around the door (no
gaps).
3. Tighten bottom hinge screws.
4. Tighten top hinge screws. Go on to
6 Prepare Power
Supply
.
Electrical Specifications
CAUTION
Electrical installation must observe all state and local
codes. This unit requires connection to a grounded (three-
prong), polarized receptacle that has been placed by a
qualified electrician.
The unit requires a grounded and polarized 115 VAC,
60 Hz, 15A power supply (normal household current).
An individual, properly grounded branch circuit or circuit
breaker is recommended. GFCI (ground fault circuit
interrupter) is usually not required for fixed location
appliances and is not recommended for your unit because
a GFCI could be prone to nuisance tripping. However, be
sure to consult your local codes.
See
Figure 17
for recommended receptacle location.
WARNING
SHOCK HAZARD — Electrical Grounding Required.
• Never remove the round grounding prong from
the plug and never use a two-prong grounding
adapter.
• Never use an extension cord to connect power to
the unit.
Go on to
7 Level the Unit
.
5 Adjust Door
ULIN_0104_
Figure 16
6 Prepare Power Supply
4"
7"
23-7/16"
Figure 17