www.U-LineService.com
6
02/2005
WH95TP, BI95BTP and BCM95 Ice Makers
9. Gently slide upper hinge through flange and fasten
upper hinge to unit (three screws). Partially tighten
screws. See
Figure 11
.
10. Place door on lower hinge pin.
11. Align door pivot hole
with pivot hole in upper
hinge and insert pivot
screw into upper hinge
and tighten securely.
See
Figure 12
.
12. Adjust door to assure
proper seal. Tighten
upper and lower hinge
screws securely.
13. Gently slide travel pin
assembly through
flange and then fasten
to unit. Make sure
travel pin in door
engages the closer in the assembly, then tighten screws
on travel pin assembly securely. See
Figure 13
.
Other Site Requirements
Power Supply
The unit requires a grounded and polarized 115 VAC,
60 Hz, 15A circuit (normal household current) or 220 VAC,
50/60 Hz. See Electrical Specifications on
Page
9
.
Water Supply
The unit requires a 1/4-inch OD water supply line and a
shut-off valve. For more information see
Page 8
.
Environmental Requirements
The surrounding air temperature must be at least 45°F
(7°C) but must not exceed 110°F (40°C). Units may be
installed outdoors in a covered area. The unit must not be
located near heat-generating equipment or in direct
sunlight.
Figure 11
Figure 12
Figure 13