32 

 

 

 

 
Checks and troubleshooting. 
In the case of incorrect operation, first check: 

• 

That the control panel and steam generator are 
connected correctly in accordance with the wiring 
diagram. 

• 

That the steam generator is installed correctly in 
accordance with these instructions. 

• 

That the drainage piping has a definite down-slope to 
the drain. 

• 

That the dirt filter is clean. The filter is positioned at the 
connection point for incoming water. During cleaning, 
unscrew the pipe connection, take out the dirt filter and 
clean out limescale and particles. 

• 

There must not be any water pockets in the steam 
piping or any ventilation ducts leading from the steam 
room. 

• 

That the steam piping does not have any sharp bends 
(min. radius 50 mm). 

• 

That any tap in the water line to the steam generator is 
not closed. 

• 

That the construction and ventilation of the steam room 
are in accordance with our instructions. 

 
Troubleshooting list with alternative causes of faults and 
suggested remedies. 
 

The desired temperature (40-50°C) is maintained in the 
steam room, but there is no steam inside the room. 

Fault cause: Insufficient ventilation in the steam room. 

Remedy: Increase the amount of ventilation. If the air 
exhaust valve extracts less than 10-20 m³ of air per person 
per hour, there is insufficient ventilation. Can occur if the air 
exhaust valve is not connected to a mechanical exhaust, or if 
a water pocket is blocking the ventilation duct. 

Fault cause: The incoming air temperature to the steam 
room is too high. 

Remedy: Reduce the temperature of the incoming air to max. 
35°C. 

Fault cause: The air temperature surrounding the steam 
room is higher than 35°C. 

Remedy: Ensure that the surrounding temperature does not 
exceed 35°C. 

Fault cause: Thermometer is faulty or incorrectly located. 

Remedy: The thermometer must be located approx. 150 - 
170 cm above floor level and as far away from the steam jet 
as possible. 
 
The steam room is taking an abnormally long time to 
warm up. 

Fault cause: In the case of steam generator low power, refer 
to the table. 

Remedy: Change to a higher power steam generator. 

Fault cause: Too much ventilation in the steam room. 

Remedy: Reduce the amount of ventilation. Must be 10-20 
m³ air per person per hour. 

Fault cause: Fuses in the distribution board have 
blown/tripped. 

Remedy: Change the fuse(s). 

Fault cause: The air temperature surrounding the steam 
room is lower than 15°C. 

Remedy: Raise the surrounding temperature or change to a 
higher power steam generator. 

Fault cause: Pipe element broken. 

Remedy: Change the pipe element. 

Fault cause: The sensor has been placed too close to the 
steam jet, see test 2. 

Remedy: Move the sensor or change the direction of the 
steam jet. 

 

Neither steam nor heat are present in the steam room. 

Fault cause: Fuses in the distribution board have 
blown/tripped. 

Remedy: Change the fuse(s). 

Fault cause: Water is not leaving the steam generator. 

Remedy: Open the tap that is connected to the pipe for 
incoming water to the steam generator, and inspect the hose 
for a kink or similar. 

Fault cause: The control panel is set incorrectly. 

Remedy: Check the time and temperature settings on the 
control panel. 

Fault cause: The dirt filter is clogged. 

Remedy: Remove the filter, that is placed in connection to 
the incoming water and clean foreign objects and particles 
from it. 

Fault cause: The feed water solenoid valve has jammed. 

Remedy: Remove the solenoid valve and clean out foreign 
objects and particles. 

Fault cause: Excessive limescale in the steam generator 
water tank, see test 1. 

Remedy: Change the water tank, complete with the element 
and electrodes. 

Fault cause: The steam generator is connected to an 
incorrect supply (voltage). 

Remedy: Check the voltage and the generator connections, 
refer to the wiring diagram. 

Fault cause: The temperature cut-out has tripped, see test 4. 

Remedy: Check for and rectify any faults in the steam pipe, 
e.g. blockage due to several sharp bends, water pockets or 
drastically reduced internal diameter. Alternatively the tank 
may be full of deposits, see above. 

Fault cause: Fault in the circuit board, control panel or 
solenoid valve. 

Remedy: Change the faulty component. 

Fault cause: Pipe element broken. 

Remedy: Change the pipe element. 

 

Hot water runs out through the steam nozzle, no or very 
little steam in the steam room. 

Fault cause: The feed water solenoid valve has jammed due 
to dirt or an electrical fault, see test 3. 

Remedy: Remove and clean the solenoid valve or rectify the 
electrical fault. 

Fault cause: The solenoid valve is broken. 

Remedy: Change the solenoid valve. 

Fault cause: Circuit board fault. 

Remedy: Change the circuit board 

Fault cause: Too much deposit on the electrodes. 

Remedy: Take out and clean the electrodes. Rub with a cloth 
until all deposits have been removed. 

 

Hot water squirts jerkily out through the steam nozzle, or 
in an even trickle, mixed with steam. 

Fault cause: Small water pocket in the steam pipe. 

Remedy: Eliminate the water pocket. 

Fault cause: Excessive length of uninsulated steam pipe. 

Remedy: Insulate the steam pipe. 

Fault cause: Too much deposit on the electrodes. 

Remedy: Take out and clean the electrodes. Rub with a cloth 
until all deposits have been removed. 

 

Hot water runs continuously out from the steam 
generator drain pipe

Fault cause: The automatic draining solenoid valve has 
jammed. 

Remedy: Switch off the steam generator. Test again after 80 
minutes. If the fault persists, remove the motorized ball valve 
for the automatic drain function and clean it. 
 

 

         Troubleshooting 

Summary of Contents for STEAM COMMERCIAL

Page 1: ...1609 Art nr 2900 4160 Steam Home Commercial ...

Page 2: ...ng 22 Descaling 22 Dimensional information 23 Pipework installation 24 Water connection 24 Steam pipe 24 Drainage 25 Electrical installation 26 Steam room wiring diagram 27 Connection terminals 27 Lighting 28 Positioning of thermistor 28 Option 28 Connection to extra equipment 28 Home automation 28 Multisteam 28 Modular connector description 29 Spare parts list 31 Home 31 Commercial 31 Troubleshoo...

Page 3: ...m nozzle There must not be any water pockets in the steam piping or ventilation ducts IMPORTANT There must not be any kind of blockage in the steam piping e g taps or valves The internal diameter of the steam piping must not be reduced All steam rooms in continuous use for more than two hours must have an air exchange rate of 10 20 m air per person per hour The power supply for the steam generator...

Page 4: ...control panel has a processor and an operative system which enables many advanced functions In addition to a number of personal settings the Elite can also be programmed to suit your personal timetable Added to this are such functions as extra fans fragrance pumps and lighting The panel has energy saving functions and the possibility of connection to a wireless network It can be located inside or ...

Page 5: ...a minimum of 10 and a maximum of 20 m per person per hour The steam generator functions All Tylö steam generators of the Home and Commercial type are equipped with A stainless steel water tank Acid proof stainless steel tube elements Automatic emptying 60 minutes after the steam bath has been switched off Automatic flushing clean after emptying 3 division output Electronic water level regulation E...

Page 6: ...ol panel and wait about 5 minutes Slacken the lock nut on the 3 way connection at the top of the steam generator Use a funnel to pour the descaling agent into the tank via the 3 way connection Screw the lock nut on the 3 way connection into place and allow time for the descaling agent to work After about 1 hour the steam generator will automatically empty and flush the tank clean and is then ready...

Page 7: ...ed clean Flushing clean prevents metal particles and other foreign objects entering the steam generator system from the piping Also remember to install the accompanying non return valve into the incoming water connection NB In areas with hard water exceeding 4 dH hardness a water softener or a Tylö de calcifier must be installed Tylö Item No 9090 8025 The water softener must not produce foam or gi...

Page 8: ...he steam jet will hit the wall seating area or any other object there must be at least 80 cm clear area in front of the steam nozzle If the steam room is to be used by children or anyone with a reduced reaction ability or similar there must be protection present that will prevent unintentional contact with the steam jet nearest to the steam nozzle If the steam nozzle will be installed in a Tylö st...

Page 9: ...able to temporarily switch off the steam generator during servicing The circuit breaker may be switched off no sooner than 90 minutes after completed use of the steam room The connections diagram in Fig 13shows the connections for both the Commercial and Home type steam generators Up to 3 steam generators can be connected to the same control panel More about this can be found in the section Multis...

Page 10: ...ick connectors refer to the circuit board overview Fig 19 All the connectors must be in place before the power is switched on THE CONTROL PANEL MAY ONLY BE CONNECTED OR DISCONNECTED WHEN THE STEAM GENERATOR IS SWITCHED OFF VIA THE MAIN POWER SWITCH OTHERWISE THE CONTROL PANEL WILL BE DAMAGED ALL LOW POWER CABLING MUST BE ENCLOSED IN THE ACCOMPANYING CABLE SLEEVING IN ACCORDANCE WITH FIG 16 I Fig 1...

Page 11: ...ector description Additional external switches must be connected in parallel Door contact Prevents unintended starting of the steam room while the door is open Connected directly by means of a control board and a RJ10 connector with low power wiring and pin connections as in the section Modular connector description Connection to extra equipment Possibility to connect extra equipment such as fans ...

Page 12: ...cted by removing the cable from between the circuit boards Fig 18 If the generator that is to be serviced is set as the primary do as follows 1 Use the circuit breaker to switch off the generator 2 Disconnect the cable that connects the control circuit boards Fig 18 3 Select a secondary steam generator and change the DIP switch settings to primary according to the appropriate type Refer to Fig 17 ...

Page 13: ...connected at Position 4 External switch without LED indication 2 3 4 Both constant and impulse deactivation work External switch with LED indication 2 2 3 4 12VDC maximum 40mA Tylö external switch item number 9090 8045 Door contact without alarm for door status 3 3 4 Of type NO Normally Open Tylö door contact Item No 9090 8035 Door contact with alarm for door status 3 2 3 4 12VDC max 40mA ...

Page 14: ...31 Home Commercial Spare parts list ...

Page 15: ...or or change the direction of the steam jet Neither steam nor heat are present in the steam room Fault cause Fuses in the distribution board have blown tripped Remedy Change the fuse s Fault cause Water is not leaving the steam generator Remedy Open the tap that is connected to the pipe for incoming water to the steam generator and inspect the hose for a kink or similar Fault cause The control pan...

Page 16: ...r each steam bath session Such a switch must not be switched off before not less than 80 minutes have elapsed since the control panel has switched off TEST 2 Functional check of the sensor Soak a small hand towel in cold water Hang the wet towel over the sensor If the steam generator begins to produce steam within 20 minutes the sensor is serviceable but positioned incorrectly or the temperature h...

Page 17: ...ement should show approx 10kΩ at 25 C and approx 677Ω at 100 C Also check the water quality and that automatic emptying is activated so that the level electrodes are not misleading the system due to foam in the tank so that they believe that sufficient water is available At off Cannot be triggered when the system is off 10 Contact with the add on board has been lost During operation Operation inte...

Page 18: ...te calendar entries deleted If it is known that the door was closed all the time test by disconnecting and reconnecting the RJ10 connector Check is the distance between the switch and the magnet set correctly Check that one of the pins in the female RJ10 connector on the circuit board may have become misaligned or displaced so that contact with the connected RJ10 cable has been lost Pins 3 4 must ...