INSTALLATION: 

Before plugging in the model to an AC outlet, please make sure that the proper input 

voltage is selected on the rear of the unit. Select 115V for 100/110/120 AC operation 

or 230V for 200/220/240 AC operation. The factory default setting is 230V. 

Then, connect your device to the  LOAD terminal and connect a lead acid battery to 

the  BATTERY  terminal,  make  sure  the  polarity  of  battery  is  correctly  connected, 

select WET for wet battery, GEL for GEL or AGM battery. 

You may connect a solar panel or wind turbine to the BATTERY terminal at the same 

time by connecting a solar panel or wind turbine controller to the battery terminals, 

please make sure it is as the same polarity as battery. 

Now, plug in the power cord to AC outlet, turn the PWR switch to the “ON” position. 

Turn on your device now. 

 

 

OPERATION: 

The  PS  works  as  a  DC  UPS  (Uninterruptible  Power  Supply)  or  as  a  backup  power 

supply  system.  When  AC  power  is  applied  normally,  the  model  offers  a  regulated 

48V  DC  output  at  LOAD  terminal  for  devices  and  a  charging  current  output  on 

BATTERY terminal for charging a lead acid battery at the same time. Once AC fails, 

the battery will replace the AC to power the model immediately without interruption. 

The LOAD terminal will remain at 48VDC output for a while till the battery voltage 

reduces  to  lower  than  40V,  the  duration  time  depends  on  the  volume  of  the  battery 

and  the  size  of  the  load.  When  AC  returns,  AC  takes  over  the  battery  to  power  the 

load automatically, and start to charge the battery.   

Summary of Contents for TP-BC48-300

Page 1: ... Net weight only 4 63 lbs 2 1kg Dimensions 252 54 190 m m W H D Over Voltage protection Over Current protection Quiet Internal Cooling Fan Input Voltage Selectable AC input voltage 115 Vac at 50 60Hz 230 Vac at 50 60Hz Super Regulation Works with AC input from 90 to 265Vac Back up Power Supply System Compatible with Solar and Wind Charge Controllers ...

Page 2: ...n is incorrect 3 4 CHD Floating Indicator Light GREEN when battery is in floating mode 3 5 CHG Charging Indicator Light YELLOW when battery is in charging mode 3 6 WET Battery Type Indicator Green LED light on when battery type selector is set on WET position 3 7 GEL Battery Type Indicator Yellow LED light on when battery type selector is set on GEL position 4 LOAD Output Terminal Block For connec...

Page 3: ...ke sure it is as the same polarity as battery Now plug in the power cord to AC outlet turn the PWR switch to the ON position Turn on your device now OPERATION The PS works as a DC UPS Uninterruptible Power Supply or as a backup power supply system When AC power is applied normally the model offers a regulated 48V DC output at LOAD terminal for devices and a charging current output on BATTERY termi...

Page 4: ...be up to 6A maximum The output voltage on LOAD terminal is regulated at 48V 0 5V with over voltage protection over current protection and short circuit protection The charge voltage for wet battery is 58V floating voltage is 53V The charge voltage for gel battery is 56 8V floating voltage is 54V When the charger is in charging mode and charge current is more than 1 4A the CHG indicator light will ...

Page 5: ... battery type selector when charging 4 The model has a 6 amp AC input fuse inside of the unit To replace the fuse you should remove the old fuse by opening the case and replace it with a new 6 amp fuse 5 The cables for battery connection or device to the PS should be 18AWG min Please keeping the connect points clean to avoid spark or electrical leakage 6 Use the proper voltage solar panel or wind ...

Page 6: ...s causing a spark Battery Low Voltage protection When the AC is OFF or has failed if the battery voltage is lower than 40V 0 2V the model will turn off the output on LOAD When AC returns or the battery voltage returns to 51V 0 2V then the output on LOAD will recover automatically Load Over Current Protection the model will automatically shut down if the load is over 4A when the load is reduced the...

Reviews: