background image

TFP1100

Page 13 of 16

Setting 

Procedure 

(Dry Pipe 

System)

The Dry Pipe System and the TYCO 

Model QRS Electronic Accelerator 

must be reset and restored to service 

as soon as possible after an operation.

NOTICE

The system must be completely drained 

before proceeding.

In the case of one panel serving mul-

tiple risers, whenever the Program 

Switch is set to the PROGRAM posi-

tion (Steps 4 and 7), the QRS Electronic 

Accelerators are taken out of service 

for all connected system risers. There-

fore, the proper authorities and all per-

sonnel who may be affected must be 

notified. In the event of a fire and where 

a QRS Electronic Accelerator has been 

taken out of service, an increased time 

in water delivery can be expected.

Step 1.

 Until the system is to be set 

for service, the internal audible buzzer 

may be silenced by momentarily press-

ing the BUZZER SILENCE button 

(Figure 7).

Step 2.

 Locate all of the system’s low 

point drain valves to help facilitate 

resetting the system.

Step 3.

 Follow the resetting procedure 

for the Dry Pipe Valve using the instruc-

tions provided in the Technical Data 

Sheet for the Dry Pipe Valve. When 

prompted to pressurize the system 

piping with air, proceed with Step 4.

Step 4.

 Momentarily press the SYSTEM 

RESET button (Figure 7) and then set 

the Program Switch to the PROGRAM 

position. The display will read “OK to 

charge system.” Begin applying air 

pressure to the system.

  At this point 

the solenoid valve will be de-ener gized 

and allowed to close to enable pressur-

ization of the system piping, and a 30 

minute countdown to repres surize the 

system will be displayed.

NOTICE

If within 30 minutes, the Program 

Switch is not returned to the RUN 

position during the upcoming Step 6, 

the Releasing Panel will automatically 

re vert to a normal condition. If at least 8 

psi has not been reached, the solenoid 

valve will be energized and open. If at 

least the low air pressure threshold of 

Table A has not been reached, a super-

visory condition will occur.
If more than 30 minutes is required, the 

counter can be restarted before the 30 

minutes has elapsed. In order to reset 

the counter, the system must be pres-

surized to at least 8 psi, at which time 

the Program Switch can be set to the 

RUN position and then quickly back to 

the PROGRAM position. A 30 minute 

countdown will then be restarted.

Step 5.

 When the system reaches an 

air pressure of approximately 10 psi, 

and while the system is in process of 

reaching its intended pressure, “blow-

down” each drain valve one at a time, 

including the low body drain or priming 

level valve, at the dry pipe valve and 

the Inspector’s Test Connection by 

opening each drain valve until water 

ceases to drain and then closing the 

drain valve. The blow-down proce-

dure that will assure complete drain-

ing of the system will be more easily 

ac complished with 10 psi air pressure 

in the system.

Step 6.

 When the system reaches the 

intended pressure and the pressure is 

stabilized, return the Program Switch 

(Figure 7) to the RUN position.

Step 7.

 After waiting at least 60 

 

seconds, open the Inspector’s Test 

Connection, wait 5 seconds, and then 

close the Inspector’s Test Connection.
Verify that the time to Accelerator trip 

is essentially the same as in previous 

tests. A momentary burst of air from a 

dry pipe valve’s Automatic Drain Valve 

indicates that the QRS has tripped. In 

addition, the display on the Operat-

ing Interface of the Releasing Panel 

will indicate operation. This procedure 

clears any scale and debris from the 

pipe and nipples that are connected to 

the solenoid valve.
Momentarily press the SYSTEM RESET 

button and then set the Program Switch 

to the PROGRAM position. The display 

will read “OK to charge system”. At 

this point, the solenoid valve will be 

de-energized and allowed to close to 

enable pressurization of the system 

piping.

Allow the system to automatically 

return to its intended pressure via its 

automatic air supply, and, after waiting 

for the pressure to stabilize, return the 

Program Switch to the RUN position.

Step 8.

 Partially open the Main Control 

Valve. Slowly close the system’s Main 

Drain Valve as soon as water dis-

charges from the drain connection.
Depress the plunger on the dry pipe 

valve’s Automatic Drain Valve to make 

sure that it is open and that no water 

discharges. The absence of water dis-

charge from the Automatic Drain Valve 

is an indication of a properly set water 

seat within the dry pipe valve. If water 

is discharging, refer to the Care and 

Maintenance section of the Technical 

Data Sheet for the dry pipe valve to 

determine and correct the cause of the 

leakage problem.
If there are no leaks, the system’s Main 

Control Valve must be fully opened.
The system is now set for service.

NOTE:

 After setting a fire protection 

system, notify the proper authorities 

and advise those responsible for moni-

toring proprietary and/or central station 

alarms.

Setting 

Procedure 

(Preaction 

System)

The Double Interlock Electric/Electric 

Preaction System and the Model QRS 

Electronic Accelerator must be reset 

and restored to service as soon as pos-

sible after an operation.

Follow the Valve Setting Procedure 

instructions provided in the Technical 

Data Sheet TFP1450. When prompted 

to reset the actuation system, momen-

tarily press the SYSTEM RESET button 

(Figure 7), and assuming that the Zone 

1 Alarm and Zone 2 Low Air Alarm 

are clear, proceed with the remaining 

instructions provided in Technical Data 

Sheet TFP1450.

NOTE:

 After setting a fire protec-

tion system, notify the proper authori-

ties and advise those responsible for 

monitoring proprietary and/or central  

station alarms.

Summary of Contents for QRS

Page 1: ...e from the automatic control valve deluge valve to permit the automatic control valve deluge valve to open The Model QRS Electronic Accelera tor automatically adjusts to both small and slow changes in...

Page 2: ...ion Step 1 The QRS Electronic Accelera tor Riser Components P N 52 312 2001 must be installed per Figure 2 or 8 as applicable The DV 5A Double Interlock Preaction Trim with Electric Electric Actuation...

Page 3: ...79 65 4 48 70 4 83 MODEL DPV 1 DRY PIPE VALVE WITH TRIM 4 INCH DN100 SOLENOID VALVE NORMALLY CLOSED UNTIL ENERGIZED 24 VDC P N 52 287 1 024 MODEL PFC 4410 RC RELEASING PANEL P N 20135 WITH MODEL BT 1...

Page 4: ...stem operation is based on the electric detec tion system operating before a first sprinkler operation 4 The minimum system air pressure must be the greater of that required for the dry pipe preaction...

Page 5: ...DN80 6 INCH DN150 4 INCH DN100 6 7 ACCELERATOR TRIM CONNECTION TO INTERMEDIATE CHAMBER 1 2 NPT 3 4 2 10 7 6 3 QUICK RELEASE SWITCH ACCELERATOR TRIM CONNECTION TO AIR SUPPLY PORT 1 2 NPT 9 5 8 5 1 6 7...

Page 6: ...3 922111003 922111003 16 1 DRIP FUNNEL 923431007 923431007 923431007 923431007 923431007 923431007 17 2 COMP FITTING 90 1 2 MNPT x 1 2 OD TUBE 1001253 01 1001253 01 1001253 01 1001253 01 1001253 01 10...

Page 7: ...000640 535000660 535000680 48 1 TUBING ASSY ALARM TEST INTERCONNECT 535000320 535000320 535000330 535000340 535000360 535000380 49 1 TUBING ASSY SYSTEM DRAIN 535000420 535000420 535000430 535000440 53...

Page 8: ...e System Gauge Item Description M N P Q R S T U V W X Manual Control Station Manual Reset Actuator Diaphragm Supply Valve Diaphragm Supply Strainer Water Supply Shut Off Air Supply Valve Air Pressure...

Page 9: ...NCH DN65 DN80 VALVES 4 INCH DN100 VALVE 6 INCH DN150 VALVE 7 5 16 185 7 mm 19 5 16 490 5 mm 6 3 8 161 9 mm 20 508 0 mm 5 7 16 138 1 mm 21 7 16 544 5 mm FIGURE 4A MODEL DPV 1 DRY PIPE VALVE INSTALLATIO...

Page 10: ...3 0 76 12 2 310 13 1 333 16 5 419 21 0 533 5 1 129 16 8 427 4 5 114 4 3 109 6 150 4 5 114 13 6 345 15 0 381 18 4 467 24 8 630 3 4 86 22 4 569 5 9 150 5 7 145 8 200 5 3 135 16 3 414 17 2 437 19 5 495...

Page 11: ...INSTALL AT PART 3005012 DIODE ASS Y END OF LINE RELEASING SOLENOID 5 1K LOCATION SOLENOID INSTALL AT PART 3005012 DIODE ASS Y END OF LINE RELEASING SOLENOID 5 1K LOCATION SOLENOID INSTALL AT PART 300...

Page 12: ...ZONE 1 SUPERVISORY ABORT BROWN BLUE YELLOW ORANGE VIOLET GREEN BLACK RED EOLR ALARM AIR LOW TAMPER 24VDC JUMPER JUMPER HIGH GREEN BROWN RED BLACK BLUE VIOLET RELEASING SOLENOID 5 1K LOCATION SOLENOID...

Page 13: ...drain valve The blow down proce dure that will assure complete drain ing of the system will be more easily ac complished with 10 psi air pressure in the system Step 6 When the system reaches the inten...

Page 14: ...elerator test procedure be per formed quarterly Step 1 When operation of the dry pipe preaction valve is not intended during the Accelerator trip test close the sys tem s Main Control Valve and open t...

Page 15: ...ded Field fabrication of additional materials will be Some items provided with the Model QRS Trim P N 52 312 2 001 are not used for the 2 Installation notes are typical of all Dry Pipe Valve models sh...

Page 16: ...ctric Actuation Trim When ordering Model QRS Quick Release Switch equipment for use with the DV 5a Valve Double Interlock Pre action Electric Electric Actuation Trim the QRS equipment and DV 5a Valve...

Reviews: