TYCO SAFETY PRODUCTS
QE90 BATTERY INSTALLATION / WIRING GUIDE
Version 1.00
18 April 2007
Page 6 OF 20
KT0501 KIT,INTER-CABINET M6 BATTERY LINK KIT
, consisting of:
KT0499 KIT,M5/M6 BATTERY TERMINAL HARDWARE KIT
1 OFF
LM0379 LOOM,156AUTO,RED/BLK,0.35M,BOTH:CRIMP M6 LUG
1 OFF
LM0380 LOOM,158AUTO,RED,1.2M,BOTH:CRIMP M6 LUG
1 OFF
LM0381 LOOM,158AUTO,BLK,1.2M,BOTH:CRIMP M6 LUG
1 OFF
Photo of KT0501
6.
INTER-CABINET
WIRING
If there are multiple cabinets with batteries, the batteries in all cabinets need to be wired in
parallel. You will need to make matching holes in the sides of the cabinets so that the
required wires can be passed out of the right side of one cabinet and into the left side of the
adjacent cabinet.
The diagrams and text below describe how to connect one pair of wires for multiple cabinets.
This wiring is what is required if there are
two
cabinets with batteries.
If there are
three
or more cabinets with batteries, you will need to connect a second set of
inter-cabinet wires to the batteries in the “middle” cabinets. This set can be connected to the
same terminals as the first set of inter-cabinet wires, or to the same terminals as the PSU
wires, whichever is most convenient.