Tyco Frostex 9800 Installation Instructions And User Manual Download Page 2

Contents

Five Important Safety Warnings

1

General Instructions

2

Installation Instructions

2

Periodic Inspections

8

Troubleshooting

8

Limited Warranty

9

Before You Begin

Make sure your 9800 FlexFit Plug Kit is complete. It should contain:

1 9800 FlexFit plug
1 Push-on end seal
2 Orange warning labels in English 
2 Orange warning labels in French 
1 White tape strip
1 Installation instruction

Make sure you have sufficient braided Frostex heating
cable for the job. 

Do not use earlier versions of Frostex

heating cable that have no braid. 

Also make sure you

have the following items:

*Frostex 9610 application tape is recommended. 

Two 10" (25 cm) plastic cable ties (not included) may be used
to secure ground-fault unit to pipe insulation.

If you have any questions after reading this guide, call this 
toll-free Tyco Thermal Controls number: (800) 545-6258.

Save this installation instruction and user guide. It con-
tains important safety warnings and maintenance infor-
mation.

Table des matières

Cinq avertissements de sécurité importants

1

Directives générales

10

Directives d’installation

10

Inspections périodiques

16

Dépannage

16

Garantie limitée

17

Avant de débuter

Assurez-vous que votre kit 9800 FlexFit contient tout ce qui
suit:

1 Fiche 9800 FlexFit
1 Obturateur à pousser
2 Étiquettes oranges d’avertissement en anglais
2 Étiquettes oranges d’avertissement en français
1 Bande de ruban blanc
1 Manuel des directives d’installation

Assurez-vous d’avoir suffisamment de câble chauffant tressé
Frostex pour effectuer le travail. 

N’employez pas les versions

antérieures des câbles chauffants Frostex sans tresses.

Ayez également les articles suivants en main:

*Le ruban de fixation Frostex 9610 est recommandé.

Deux colliers de serrage en plastique de 25 cm (10 po) (non
inclus) peuvent être utilisés pour fixer le disjoncteur différentiel
à l’isolant de tuyaux.

Si vous avez des questions après la lecture du présent guide,
contactez le numéro sans frais de Tyco Thermal Controls au :
(800) 545-6258.

Conservez ces directives d’installation ainsi que le
guide de l’utilisateur. Ils contiennent d’importants
avertissements de sécurité et une notice d’entretien.

Un
coupe-câble

Tournevis 
Phillips°2

Du ruban *
de 13 mm-25 mm
(1/2-1po)

Wire cutters

#2 Phillips
screwdriver

1/2"–1"
(13 mm–25 mm)
tape*

ENGLISH

FRANÇAIS

9800 FlexFit plug

Reset button

Test button

Ground-fault unit

Indicator
light

TES

T

Gel-filled end seal

Kee

p dr

y

Ga

rder

au

sec

Summary of Contents for Frostex 9800

Page 1: ...9800 FlexFit Plug Kit Directives d installation et Guide de l Utilisateur du Syst me Frostex de Protection Anti gel des Tuyaux Utilis avec le Kit Frostex 9800 FlexFit Keep pipes from freezing Protecti...

Page 2: ...D pannage 16 Garantie limit e 17 Avant de d buter Assurez vous que votre kit 9800 FlexFit contient tout ce qui suit 1 Fiche 9800 FlexFit 1 Obturateur pousser 2 tiquettes oranges d avertissement en ang...

Page 3: ...quat Employez uniquement les versions tress es des c bles chauffants Frostex Les versions ant rieures des c bles chauffants Frostex sans tresses ne sont pas compatibles 2 Utilisez la fiche et l obtur...

Page 4: ...nt safety warnings and maintenance information If you have any difficulty installing the system please contact Tyco Thermal Controls for information at 800 545 6258 or call a professional service pers...

Page 5: ...rostex heating cable installed along the entire length of the pipe Table 2 The total length of heating cable equals 32 ft 10 m 2 runs x 16 ft 5 m of pipe 1 ft 0 3 m for one ball valve 1 ft 0 3 m for o...

Page 6: ...able 2C Remove the plastic wrap Cut and remove the clear plastic wrap Do not cut into the blue jacket 2E Secure the braid Slide the braid up against the end seal and wrap it securely with a 4 10 cm st...

Page 7: ...The clear plastic wrap does not need to be removed 3C Complete the connection Screw down the cable guide alternating between the two screws until the cable guide is flush with the indicator posts and...

Page 8: ...cable in the 4 o clock and 8 o clock positions as shown in Figure 4 When three runs are required install the heating cable as shown in Figure 5 Figure 4 Double runs Figure 5 Triple runs 4C Tape the he...

Page 9: ...lower than 30 F run water through the pipe before plugging in the unit This will warm up the pipe and help avoid blowing the nonreplace able fuse in the 9800 FlexFit plug The signal light will go on i...

Page 10: ...e replaced Problem The signal light does not light up What to do Check to be sure the outlet has power If you are not certain how to do this call a professional service person If the outlet has no pow...

Page 11: ...goods to Tyco Thermal Controls postage prepaid at 300 Constitution Drive Menlo Park California 94025 1164 USA and c Tyco Thermal Controls examination of such goods estab lishes to Tyco Thermal Control...

Reviews: