Tyco EC-5 Series Manual Download Page 6

Ordering
Procedure

When placing an order, indicate the full
product name. Refer to the Price List
for complete listing of Part Numbers.

Contact your local distributor for avail-
ability.

Sprinkler Assemblies with NPT
Thread Connections:

Specify: TY3302, 5.6 K-factor, (specify
temperature rating), Series EC-5 Ex-
tended Coverage Horizontal Sidewall
Sprinkler with (specify type of finish or
coating), P/N (specify from Table D).

Recessed Escutcheon:

Specify: Style 50 Recessed Escutch-
eon with (specify finish), P/N (specify).

Style 50 Recessed Escutcheon

Chrome Plated . . . . . . . . . . . . PSN 56-711-9-010
White Color Coated . . . . . . . . PSN 56-711-4-010
White (RAL9010)* . . . . . . . . . PSN 56-711-3-010
Brass Plated . . . . . . . . . . . . . . PSN 56-711-2-010

*Eastern Hemisphere sales only.

Sprinkler Wrench:

Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387.

Specify: W-Type 7 Recessed Sprinkler
Wrench, P/N 56-850-4-001.

Page 6 of 6

TFP298

TYCO FIRE PRODUCTS

, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446

51 — XXX — X — XXX

155°F/68°C

155

TEMPERATURE

RATING

135°F/57°C

135

1

SPRINKLER

TABLE D

PART NUMBER SELECTION

SERIES TY-FRB EXTENDED COVERAGE HORIZONTAL SIDEWALL SPRINKLERS

200°F/93°C

200

WHITE POLYESTER

NATURAL BRASS

9

4

MODEL/SIN

CHROME PLATED

053

5.6K EC HSW

TY3302

3

WHITE (RAL9010)

POLYESTER*

*Eastern Hemisphere sales only.

Summary of Contents for EC-5 Series

Page 1: ...entative of all possible cor rosive atmospheres Consequently it is recommended that the end user be consulted with respect to the suitability of these coatings for any given corro sive environment The effects of ambi ent temperature concentration of chemicals and gas chemical velocity should be considered as a minimum along with the corrosive nature of the chemical to which the sprinklers will be ...

Page 2: ... be installed in accordance with the follow ing instructions NOTES Do not install any bulb type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb With the sprinkler held horizontally a small air bubble should be present The diameter of the air bubble is approximately 1 16 inch 1 6 mm A leak tight 1 2 inch NPT sprinkler joint should be obtained with a torque of 7 to 14 ft ...

Page 3: ...on system main control valve for maintenance work on the fire protection system that it controls permission to shut down the affected fire protection system must be obtained from the proper authorities and all personnel who may be affected by this action must be notified Absence of an escutcheon which is used to cover a clearance hole may delay the time to sprinkler operation in a fire situation S...

Page 4: ... Deflector Sprinkler Minimum Rating Area 1 Flow 2 Pressure 2 To Ceiling Temperature Spacing 4 Ft x Ft m x m GPM LPM PSI BAR Distance 3 In mm Rating F Ft m Quick 16 x 16 4 9 x 4 9 26 98 21 6 1 48 4 to 18 100 to 450 135 155 8 2 4 Quick 16 x 16 4 9 x 4 9 26 98 21 6 1 48 4 to 12 100 to 300 200 8 2 4 Quick 16 x 18 4 9 x 5 5 29 110 26 8 1 85 4 to 18 100 to 450 135 155 8 2 4 Quick 16 x 20 4 9 x 6 1 32 12...

Page 5: ...NSEQUENTIAL DAMAGES INCLUDING BUT NOT LIMITED TO LABOR CHARGES RE GARDLESS OF WHETHER TYCO FIRE PRODUCTS WAS INFORMED ABOUT THE POSSIBILITY OF SUCH DAMAGES AND IN NO EVENT SHALL TYCO FIRE PRODUCTS LI ABILITY EXCEED AN AMOUNT EQUAL TO THE SALES PRICE THE FOREGOING WARRANTY IS MADE IN LIEU OF ANY AND ALL OTHER WARRANTIES EXPRESS OR IMPLIED INCLUDING WARRANTIES OF MERCHANTABILITY AND FIT NESS FOR A P...

Page 6: ...ecessed Escutcheon Chrome Plated PSN 56 711 9 010 White Color Coated PSN 56 711 4 010 White RAL9010 PSN 56 711 3 010 Brass Plated PSN 56 711 2 010 Eastern Hemisphere sales only Sprinkler Wrench Specify W Type 6 Sprinkler Wrench P N 56 000 6 387 Specify W Type 7 Recessed Sprinkler Wrench P N 56 850 4 001 Page 6 of 6 TFP298 TYCO FIRE PRODUCTS 451 North Cannon Avenue Lansdale Pennsylvania 19446 51 XX...

Reviews: