Tyco EC-5 Series Manual Download Page 4

ommended to be initially performed for
corrosion resistant coated sprinklers,
after  the  installation has  been com-
pleted, to verify the integrity of the cor-
rosion resistant coating. Thereafter,
annual inspections per NFPA 25
should suffice; however, instead of in-
specting from the floor level, a random
sampling of close-up visual inspec-
tions should be made, so as to better
determine the exact sprinkler condi-
tion and the long term integrity of the
corrosion resistant coating, as it may
be affected by the corrosive conditions
present.

The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in  compliance with this  docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-

stalling contractor or sprinkler manu-
facturer should be contacted relative to
any questions.

It is recommended that automatic
spr inkler systems be inspected,
tested, and maintained by a qualified
Inspection Service in accordance with
local requirements and/or national
code.

Page 4 of 6

TFP298

5.6 K EXTENDED COVERAGE HORIZONTAL SIDEWALL SPRINKLER (TY3302)

AND RECESSED HORIZONTAL SIDEWALL SPRINKLER (TY3302)

Response

Coverage

Minimum

Minimum

Deflector-

Sprinkler

Minimum

Rating

Area

(1)

,

Flow

(2)

,

Pressure

(2)

,

To-Ceiling

Temperature

Spacing

(4

),

Ft. x Ft. (m x m)

GPM (LPM)

PSI (BAR)

Distance

(3)

,  In. (mm)

Rating, °F

Ft. (m)

Quick

16 x 16 (4,9 x 4,9)

26 (98)

21.6 (1,48)

4 to 18 (100 to 450)

135, 155

8 (2,4)

Quick

16 x 16 (4,9 x 4,9)

26 (98)

21.6 (1,48)

4 to 12 (100 to 300)

200

8 (2,4)

Quick

16 x 18 (4,9 x 5,5)

29 (110)

26.8 (1,85)

4 to 18 (100 to 450)

135, 155

8 (2,4)

Quick

16 x 20 (4,9 x 6,1)

32 (121)

32.7 (2,25)

4 to 18 (100 to 450)

135, 155

8 (2,4)

Standard

16 x 18 (4,9 x 5,5)

29 (110)

26.8 (1,85)

4 to 12 (100 to 300)

200

8 (2,4)

Standard

16 x 20 (4,9 x 6,1)

32 (121)

32.7 (2,25)

4 to 12 (100 to 300)

200

8 (2,4)

5.6 K EXTENDED COVERAGE HORIZONTAL SIDEWALL SPRINKLER (TY3302)

Quick

16 x 22 (4,9 x 6,7)

36 (136)

41.3 (2,85)

4 to 18 (100 to 450)

135

8 (2,4)

Standard

16 x 24 (4,9 x 7,3)

39 (148)

48.5 (3,34)

4 to 18 (100 to 450)

135

8 (2,4)

TABLE B

UL AND C-UL LISTING COVERAGE AND FLOW RATE CRITERIA

NOTES

1. Backwall (where sprinkler is located) by sidewall (length of throw).

2. Requirement is based on minimum flow in GPM from each sprinkler. The indicted residual pressures are based on the nominal
K-factor.

3. The centerline of the sprinkler waterway is located 7/16 inch (11,1 mm) below the deflector (Ref. Figures 1 and 2).

4. Minimum spacing is for lateral distance between sprinklers located along a single wall. Otherwise adjacent sprinklers (i.e., sidewall
sprinklers on an adjacent wall, on an opposite wall, or pendent sprinklers) must be located outside of the maximum listed protection
area of the extended coverage sidewall sprinkler being utilized.

Summary of Contents for EC-5 Series

Page 1: ...entative of all possible cor rosive atmospheres Consequently it is recommended that the end user be consulted with respect to the suitability of these coatings for any given corro sive environment The effects of ambi ent temperature concentration of chemicals and gas chemical velocity should be considered as a minimum along with the corrosive nature of the chemical to which the sprinklers will be ...

Page 2: ... be installed in accordance with the follow ing instructions NOTES Do not install any bulb type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb With the sprinkler held horizontally a small air bubble should be present The diameter of the air bubble is approximately 1 16 inch 1 6 mm A leak tight 1 2 inch NPT sprinkler joint should be obtained with a torque of 7 to 14 ft ...

Page 3: ...on system main control valve for maintenance work on the fire protection system that it controls permission to shut down the affected fire protection system must be obtained from the proper authorities and all personnel who may be affected by this action must be notified Absence of an escutcheon which is used to cover a clearance hole may delay the time to sprinkler operation in a fire situation S...

Page 4: ... Deflector Sprinkler Minimum Rating Area 1 Flow 2 Pressure 2 To Ceiling Temperature Spacing 4 Ft x Ft m x m GPM LPM PSI BAR Distance 3 In mm Rating F Ft m Quick 16 x 16 4 9 x 4 9 26 98 21 6 1 48 4 to 18 100 to 450 135 155 8 2 4 Quick 16 x 16 4 9 x 4 9 26 98 21 6 1 48 4 to 12 100 to 300 200 8 2 4 Quick 16 x 18 4 9 x 5 5 29 110 26 8 1 85 4 to 18 100 to 450 135 155 8 2 4 Quick 16 x 20 4 9 x 6 1 32 12...

Page 5: ...NSEQUENTIAL DAMAGES INCLUDING BUT NOT LIMITED TO LABOR CHARGES RE GARDLESS OF WHETHER TYCO FIRE PRODUCTS WAS INFORMED ABOUT THE POSSIBILITY OF SUCH DAMAGES AND IN NO EVENT SHALL TYCO FIRE PRODUCTS LI ABILITY EXCEED AN AMOUNT EQUAL TO THE SALES PRICE THE FOREGOING WARRANTY IS MADE IN LIEU OF ANY AND ALL OTHER WARRANTIES EXPRESS OR IMPLIED INCLUDING WARRANTIES OF MERCHANTABILITY AND FIT NESS FOR A P...

Page 6: ...ecessed Escutcheon Chrome Plated PSN 56 711 9 010 White Color Coated PSN 56 711 4 010 White RAL9010 PSN 56 711 3 010 Brass Plated PSN 56 711 2 010 Eastern Hemisphere sales only Sprinkler Wrench Specify W Type 6 Sprinkler Wrench P N 56 000 6 387 Specify W Type 7 Recessed Sprinkler Wrench P N 56 850 4 001 Page 6 of 6 TFP298 TYCO FIRE PRODUCTS 451 North Cannon Avenue Lansdale Pennsylvania 19446 51 XX...