background image

General
Description

The Series EC-5, Extended Coverage
Horizontal Sidewall Sprinklers are ex-
tended coverage, decorative 3 mm
glass bulb type spray sprinklers de-
signed for use in hydraulically calcu-
lated sprinkler systems in light hazard,
commercial occupancies such as
churches, restaurant seating areas,
hotels,  educational  facilities,  offices,
etc. With their coverage up to 16 feet
(4,9 m) wide by 24 feet (7,3 m) long
and maximum deflector to ceiling dis-
tance of 18 inches (450 mm), they are
designed for installation along a wall or
the side of a beam and just beneath a
smooth and level ceiling. Horizontal
sidewall sprinklers are commonly used
instead  of pendent  or upright  sprin-
klers due to aesthetics or building con-
struction considerations, where piping
across the ceiling is not desirable.

The fast response thermal sensitivity
rating of the Series EC-5, 3 mm Bulb
Type Sprinklers provides a quick re-
sponse extended coverage (QREC)
rating for many of the coverage areas
detailed in Tables B and C.

The recessed version of  the Series
EC-5 Extended Coverage Horizontal
Sidewall Sprinkler utilizes a two-piece
Style 50 Recessed Escutcheon. The
Style 50 provides up to 3/8 inch (9,5

mm) of total adjustment from the flush
sidewall position. The adjustment pro-
vided by the Recessed Escutcheon re-
duces the accuracy to which the fixed
pipe lengths to the sprinklers must be
cut.

Corrosion resistant  coatings, where
applicable, are utilized to extend the
life of copper alloy sprinklers beyond
that which would otherwise be ob-
tained when exposed to corrosive at-
mospheres. Although corrosion resis-
tant coated sprinklers have passed the
standard corrosion tests of the appli-
cable approval agencies, the testing is
not representative of all possible cor-
rosive atmospheres. Consequently, it
is recommended that the end user be
consulted with respect to the suitability
of these coatings for any given corro-
sive environment. The effects of ambi-
ent temperature, concentration of
chemicals, and gas/chemical velocity,
should be considered, as a minimum,
along with the corrosive nature of the
chemical to which the sprinklers will be
exposed.

WARNINGS

The Series EC-5 Sprinklers described
herein must be  installed and  main-
tained in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association, in addition to the
standards of any other authorities hav-
ing jurisdiction.

Failure to do so may

impair the performance of these de-
vices.

The owner is responsible for maintain-
ing their fire protection system and de-
vices in  proper operating  condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.

Model/Sprinkler
Identification
Numbers

TY3302 - EC HSW, 5.6K

TY3302 is a redesignation for C3302.

Technical
Data

Approvals

UL and C-UL Listed.
FM and NYC Approved.
(Refer to Table A for complete approval
information including corrosion resis-
tant status. The approvals apply to the
service conditions indicated in the De-
sign Criteria section.)

Maximum Working Pressure

175 psi (12,1 bar)

Series EC-5 — 5.6 K-factor
Extended Coverage Horizontal Sidewall Sprinklers
Quick & Standard Response (Light Hazard)

Page 1 of 6

TFP298

JANUARY, 2005

Technical Services:

Tel: (800) 381-9312 / Fax: (800) 791-5500

IMPORTANT

Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.

Summary of Contents for EC-5 Series

Page 1: ...entative of all possible cor rosive atmospheres Consequently it is recommended that the end user be consulted with respect to the suitability of these coatings for any given corro sive environment The effects of ambi ent temperature concentration of chemicals and gas chemical velocity should be considered as a minimum along with the corrosive nature of the chemical to which the sprinklers will be ...

Page 2: ... be installed in accordance with the follow ing instructions NOTES Do not install any bulb type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb With the sprinkler held horizontally a small air bubble should be present The diameter of the air bubble is approximately 1 16 inch 1 6 mm A leak tight 1 2 inch NPT sprinkler joint should be obtained with a torque of 7 to 14 ft ...

Page 3: ...on system main control valve for maintenance work on the fire protection system that it controls permission to shut down the affected fire protection system must be obtained from the proper authorities and all personnel who may be affected by this action must be notified Absence of an escutcheon which is used to cover a clearance hole may delay the time to sprinkler operation in a fire situation S...

Page 4: ... Deflector Sprinkler Minimum Rating Area 1 Flow 2 Pressure 2 To Ceiling Temperature Spacing 4 Ft x Ft m x m GPM LPM PSI BAR Distance 3 In mm Rating F Ft m Quick 16 x 16 4 9 x 4 9 26 98 21 6 1 48 4 to 18 100 to 450 135 155 8 2 4 Quick 16 x 16 4 9 x 4 9 26 98 21 6 1 48 4 to 12 100 to 300 200 8 2 4 Quick 16 x 18 4 9 x 5 5 29 110 26 8 1 85 4 to 18 100 to 450 135 155 8 2 4 Quick 16 x 20 4 9 x 6 1 32 12...

Page 5: ...NSEQUENTIAL DAMAGES INCLUDING BUT NOT LIMITED TO LABOR CHARGES RE GARDLESS OF WHETHER TYCO FIRE PRODUCTS WAS INFORMED ABOUT THE POSSIBILITY OF SUCH DAMAGES AND IN NO EVENT SHALL TYCO FIRE PRODUCTS LI ABILITY EXCEED AN AMOUNT EQUAL TO THE SALES PRICE THE FOREGOING WARRANTY IS MADE IN LIEU OF ANY AND ALL OTHER WARRANTIES EXPRESS OR IMPLIED INCLUDING WARRANTIES OF MERCHANTABILITY AND FIT NESS FOR A P...

Page 6: ...ecessed Escutcheon Chrome Plated PSN 56 711 9 010 White Color Coated PSN 56 711 4 010 White RAL9010 PSN 56 711 3 010 Brass Plated PSN 56 711 2 010 Eastern Hemisphere sales only Sprinkler Wrench Specify W Type 6 Sprinkler Wrench P N 56 000 6 387 Specify W Type 7 Recessed Sprinkler Wrench P N 56 850 4 001 Page 6 of 6 TFP298 TYCO FIRE PRODUCTS 451 North Cannon Avenue Lansdale Pennsylvania 19446 51 XX...

Reviews: