Tyco DV-5A Manual Download Page 7

TFP1466

Page 7 of 18

open. After the ten minute duration, at 

which point should the Solenoid Valve 

become de-energized and close (espe-

cially while operating under battery 

back-up), the MRA-1 will have already 

automatically opened, thereby prevent-

ing the DV-5

a

 Diaphragm Chamber 

from becoming re-pressurized, and 

preventing an inadvertent closing of 

the DV-5

a

 during a fire event.

WARNING

If the delay between electric actua-

tion and subsequent sprinkler activa-

tion is anticipated to be greater then 

10 minutes, adjust the battery back-up 

calculation accordingly. Inadequate 

battery back-up may result in failure of 

the system to operate in the event of a 

fire during a power failure.

Releasing Circuit

The recommened arrangement is to 

equip the releasing circuit with a Potter 

RCDS-1 Releasing Circuit Switch, or 

equivalent. The RCDS-1 provides for a 

temporary disconnect (de-energized) of 

the Solenoid Valve during Step 9 of the 

Valve Resetting Procedure.

System Air Pressure Requirements

The recommended system air pres-

sure for the Double Interlock Preaction 

System with Electric/Electric Actuation 

is nominally 15 psi (1,0 bar), irrespective 

of the water supply pressure. The use 

of a higher system air pressure may or 

may not adversely affect water deliv-

ery time, and the use of a lower system 

air pressure may prevent clearing the 

alarm of the Low Pressure Switch on 

increasing pressure. The Low Pressure 

Switch is field set to alarm at nominally 

12 psi (0,8 bar) on decreasing pres-

sure when using a nominal system air 

pressure of 15 psi (1,0 bar). It is recom-

mended that the system air pressure 

be maintained by either of the follow-

ing methods:
•  A maximum 200 psi (13,8 bar) plant 

air supply in combination with the 

Model AMD-1 Air Maintenance 

Device described in Technical Data 

Sheet TFP1221

•  A maximum 3000 psi (206,9 bar) 

nitrogen cylinder in combination with 

the Model AMD-3 Nitrogen Mainte-

nance Device described in Technical 

Data Sheet TFP1241

NOTES:

It is recommended that the pressure 

maintenance device be of a type that 

maintains a constant system pressure, i.e., 

a pressure maintenance device that utilizes 

a pressure regulator versus a pressure 

switch (e.g., the AMD-1 or AMD-3). Use 

of a pressure switch operated pressure 

maintenance device with a cut-in/cut-

out differential may result in a delay in 

the operation of the system due to a fire, 

because of the cut-out pressure being 

higher than the recommended nominal 

system air pressure.
The dew point of the air or nitrogen 

supply, for a system exposed to freezing 

conditions, must be maintained below the 

lowest ambient temperature to which the 

system piping will be exposed. Introduction 

of moisture into the system piping can 

create ice build up which could prevent 

proper operation of the system.

The Air Pressure Relief Valve is typi-

cally field set to crack open at a pres-

sure of about 20 psi (1,4 bar) when 

using a nominal system air pressure of 

15 psi (1,0 bar).

Installation

The TYCO DV-5

a

 

Valve is to be installed 

in accordance with this section.

NOTICE

DV-5A Automatic Water Control Valves 

are designed to be used in freshwater 

systems. When the supply is from an 

alternative source such as brackish 

water, saltwater, or contains additives 

such as foam, the limited warranty is 

reduced to one year from the time of 

installation. An increase in frequency of 

inspections is required when the valve 

is exposed to such supplies and other 

corrosive conditions or chemicals that 

could impact valve materials or the 

operation of the assembly. The system 

and all components must be designed 

accordingly for the increased demand. 

It is required to thoroughly flush the 

valve and trim assembly with freshwa-

ter and reset to the set condition after 

each operation.
Proper operation of the DV-5

a

 Valves 

depends upon their trim being installed 

in accordance with the instructions 

given in this technical data sheet. 

Failure to follow the appropriate trim 

diagram may prevent the DV-5

a

 Valve 

from functioning properly, as well as 

void approvals and the manufacturer’s 

warranties.
The DV-5

a

 

Valve must be installed in a 

readily visible and accessible location.
The DV-5

a

 Valve and associated trim 

must be maintained at a minimum tem-

perature of 40

°

F (4°C).

Heat tracing of the DV-5

a

 Valve or its 

associated trim is not permitted. Heat 

tracing can result in the formation of 

hardened mineral deposits that are 

capable of preventing proper operation.
Always open the system control valves 

slowly to avoid a sudden rush of water 

entering the system.

The DV-5

a

 Valve is to be installed in 

accordance with the following criteria:

Step 1.

 All nipples, fittings, and devices 

must be clean and free of scale and 

burrs before installation. Use pipe 

thread sealant sparingly on male pipe 

threads only.

Step 2.

 The DV-5

a

 Valve must be 

trimmed in accordance with one of the 

trim illustrations shown in Figure 5.

Note:

 If the addition of an Alarm Control 

Valve is desired or required by the local 

AHJ, the Alarm Control Valve noted as 

Item H in Figure 8 is to be a separately 

ordered electronically supervised normally 

open valve.

Step 3.

 Care must be taken to ensure 

that check valves, strainers, globe 

valves, etc., are installed with the flow 

arrows in the proper direction.

Step 4.

 Drain tubing to the Drip Funnel 

must be installed with smooth bends 

that will not restrict flow.

Step 5.

 The Main Drain and Drip Funnel 

Drain may be interconnected provided 

a check valve is located at least 12 in. 

(300 mm) below the Drip Funnel.

Step 6.

 Suitable provision must be 

made for disposal of drain water. Drain-

age water must be directed such that 

it will not cause accidental damage to 

property or danger to persons.

Step 7.

 Connect the Diaphragm Supply 

Valve to the inlet side of the System 

Main Control Valve in order to facilitate 

setting of the DV-5

a

 Valve (see Figure 

8).

Step 8.

 An Inspector’s Test Connection 

is to be located on the sprinkler system 

at the most hydraulically demanding 

location.

Step 9.

 A suitable automatic air (nitro-

gen) supply, as described in the appli-

cable Electric/Electric Actuation 

sub-section, is to be installed in accor-

dance with the applicable technical 

data sheet. The minimum air pressure 

is to be in accordance with the refer-

enced sub-sections.

Step 10.

 A desiccant dryer, when spec-

ified, is to be installed between a drip 

leg and the Air Maintenance Device.

Step 11.

 The Low Pressure Switch on 

falling pressure in the Electric/Electric 

Actuation is to be adjusted so that the 

low pressure alarm setting is set at 

3 psi (0,21 bar) below the system air 

pressure.

Step 12.

 Unused Pressure Alarm 

Switch connections must be plugged.

Step 13.

 The Pressure Relief Valve on 

rising pressure is to be at 5 psi (0,34 bar) 

higher than the required system air 

pressure, or be reset in accordance 

with the requirements of the authority 

having jurisdiction.
To reset the Pressure Relief Valve, first 

loosen the jam nut and then adjust the 

Summary of Contents for DV-5A

Page 1: ...llations The DV 5a Valves are offered with the DV 5a Valve and separately ordered semi assembled trim shown in Figures 6 and 7 or for ease of installation with DV 5a Valve completely trimmed with or w...

Page 2: ...Numbers given do not replace Hex Bolt Hex Nut Lift Washer or Hoist Ring with common hardware parts e Also applicabale to metric 165 1 mm size 1 1 2 AND 2 INCH VALVES ONLY 6 AND 8 INCH VALVES ONLY 7 9...

Page 3: ...TEM OPEN TO ATMOSPHERE ALARM PORT WATERFLOW TO ALARM WATER SUPPLY PRESSURE ALARM TEST SYSTEM DRAIN OPEN SYSTEM DRAIN OPEN MAIN DRAIN CLOSED MAIN DRAIN OPEN DIAPHRAGM CHAMBER SUPPLY FROM UPSTREAM SIDE...

Page 4: ...es are pressure rated to 16 bar Valve Trim The maximum pressure rating for the Electric Electric Double Interlock Pre action Trim is dependent on separately ordered solenoid valve per Technical Data S...

Page 5: ...ed below the valve trip point The water supply pressure then forces the Diaphragm open permitting water to flow into the system piping as well as through the Alarm Port to actuate the system alarms se...

Page 6: ...s that may be used with this trim package is given in Technical Data Sheet TFP2180 Nominal installation dimensions for the Double Interlock Preaction System With Electric Electric Actuation Trim are s...

Page 7: ...uired when the valve is exposed to such supplies and other corrosive conditions or chemicals that could impact valve materials or the operation of the assembly The system and all components must be de...

Page 8: ...ating lever by pushing it up Do not close the hinged cover at this time Step 11 After allowing water to flow out of the Manual Reset Actuator N drain tube until aerated water ceases to dis charge rese...

Page 9: ...e and Item A7 is provided as P N 52 287 1 124 described in Technical Data Sheet TFP2180 4 When ordering DV 5A Trim separately from the DV 5A Valve Items A1 through A10 are separately ordered as applic...

Page 10: ...CHECK VALVE 923221003 923221003 923221003 923221003 923221003 923221003 10 1 1 2 SWING CHECK VALVE 460491007 460491007 460491007 460491007 460491007 460491007 11 1 1 2 Y STRAINER 523531006 523531006 5...

Page 11: ...x 5 1 2 x 5 1 2 x 5 1 2 1 2 x 5 1 2 1 2 x 5 1 2 1 2 x 6 1 2 52 1 PIPE NIPPLE 1 2 x 5 1 2 x 5 1 2 x 4 1 2 1 2 x 5 1 2 x 7 1 2 1 2 x 9 1 2 53 1 PIPE NIPPLE 3 4 x 5 3 4 x 5 3 4 x 6 3 4 x 7 3 4 x 9 3 4 x...

Page 12: ...3 6 91 4 100 4 5 114 11 9 302 12 6 320 16 5 419 21 0 533 5 5 140 16 8 427 4 54 115 4 3 109 63 150 5 7 145 13 4 340 14 5 368 18 4 467 24 8 630 3 8 97 22 4 569 5 83 148 5 7 145 8 200 6 8 174 16 1 409 16...

Page 13: ...ividual instructions for the solenoid valve dry pilot actuator manual control station switches and pressure maintenance device should be reviewed The following procedures pertain to the automatic cont...

Page 14: ...matic Drain Valve Alarm Test Valve Alarm Control Valve Optional Water Supply Gauge Diaphragm Gauge System Gauge Manual Control Station Item Description N P Q R S T U V W X Manual Reset Actuator Diaphr...

Page 15: ...ed to the Model MRA 1 Manual Reset Actuator N That the Waterflow Pressure Switch C and its associated alarms prop erly operate That the Water Motor Alarm if appli cable properly operates NOTE Thisproc...

Page 16: ...4 in DN100 550011540 6 in DN150 550011560 8 in DN200 550011580 Flange x Flange ANSI 3 in DN80 550021530 4 in DN100 550021540 6 in DN150 550021560 8 in DN200 550021580 Flange x Grooved ANSI 3 in DN80...

Page 17: ...External Trim Connections drains pressure switches water motor alarms etc APAC DV 5A Valves with Galvanized Trim Specify Size specify DV 5a Auto matic Water Control Valve specify end connection with a...

Page 18: ...DV 5a Valve Trim P N See Figure 6 DV 5A Valve Trim Accessories for separately ordered valve trim Specify Specify Accessory Descrip tion P N specify Model QRS Quick Refer to Technical Release Switch Q1...

Page 19: ...Valve Optional Water Supply Gauge Diaphragm Gauge System Gauge Manual Control Station Manual Reset Actuator A B C J K D E F G N P Q V X Y M W S T R L Z U H AA W H General Description The appendix fou...

Page 20: ...ure is within normally expected range 2 If below normal range correct any leakage from diaphragm chamber prior to resetting the system 3 When water supply pressure is restored reset DV 5a Valve in acc...

Reviews: