![Tyco DV-5A Manual Download Page 19](http://html1.mh-extra.com/html/tyco/dv-5a/dv-5a_manual_1185740019.webp)
APPENDIX A INSTRUCTIONS
SEPTEMBER 2022
TFP1466
Worldwide
Contacts
www.tyco-fire.com
DV-5
A
Appendix
Poster Printing
Instructions
General
Description
The appendix found at the end of this
document provides valve setting and
testing/inspection procedures summa-
rized from the Care and Maintenance
section.
Some jurisdictions require a copy of the
Summary Instructions appendix to be
displayed in proximity to a DV-5
A
Auto-
matic Control Valve riser supplying a
fire protection system.
Reproduce as an individual poster by
printing on appropriate media.
A form of protection is recommended
to prevent damage which could render
the poster illegible. Conditions to avoid
include moisture infiltration, fading,
mutilation, etc.. Protective measures
may include lamination, placement
within an impact- and water-resistant
frame, etc.
The format shown in this document is
landscape orientation on US Tabloid
size, also known as ANSI B drawing
format, both roughly comparable to
ISO A3 size format.
To avoid potential cropping of content
when printing to A3 format, select
options such as print to fit or scale
to fit. Depending on printer capabil-
ity content will be slightly reduced but
should remain readable.
See Print Format Dimensions Table for
details.
Format
Imperial
in.
Metric
mm
W
H
W
H
US Tabloid
17
11
—
—
ANSI B
ISO A3
—
—
420
297
PRINT FORMAT DIMENSIONS
TFP1485 APPENDIX A
AUGUST 2022
1467 Elmwood Avenue, Cranston, RI 02910 | Tel1-401-781-8220
© 2022 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document
revision date and are subject to change without notice.
Worldwide
Contacts
www.tyco-fire.com
Summary Instructions
DV-5
A
Automatic Water Control Valve
Preaction Type A Systems
(EN12845 Compliance)
Scan the QR code or enter the URL
in a web browser to access the most
up-to-date electronic version of this
document. Data rates may apply.
docs.jci.com/tycofire/tfp1485
NOTICE
The procedures provided are summary instructions of the complete procedures appearing in
Technical Data Sheet TFP1485. If problems occur, consult full document.
Valve Setting Procedure
1.
Close System Main Control Valve (B), Diaphragm Supply Valve (P), and Air Supply Control
Valves (X) and (Y).
2.
Open Main Drain Valve (D), System Drain Valve (E), and all auxiliary drains in system. Also,
remove plug from Air Supply Strainer (W) to drain any water and ensure it is clean and free
of debris. Close auxiliary drain valves, System Drain Valve (E), and reassemble Air Supply
Strainer (W) after water stops discharging. Leave Main Drain Valve (D) open.
3.
Ensure Pressure Gauge Valves and Alarm Control Valve (H), as applicable, are open.
4.
Depress plunger of Automatic Drain Valve (F) to verify it is open.
5.
Clean Diaphragm Supply Strainer (Q). Flush strainer by opening the Diaphragm Supply
Valve (P).
6.
Replace operated automatic sprinklers on system piping.
7.
Reset DV-5
A
Valve Releasing Panel in accordance with manufacturer instructions.
8.
Re-establish system air pressure to reset Model DP-1 Dry Pilot Actuator (T) by opening Air
Supply Control Valve (X). Do not open Air Supply Control Valve (Y) at this time. Observe Dry
Pilot Actuator (T) air pressure on Dry Pilot Gauge (Z).
9.
Open Manual Control Station (M), then open Diaphragm Supply Valve (P). After aerated
water stops discharging from Manual Control Station (M) drain tube, slowly close operating
lever. Do not close hinged cover at this time.
10.
After aerated water stops discharging, reset Manual Reset Actuator (N) until water stops
flowing from its drain tube and pressure reaches approximately 15 psi (1,0 bar) on Diaphragm
Gauge (K).
11.
With diaphragm chamber pressurized, temporarily close Diaphragm Supply Valve (P), and
observe Diaphragm Gauge (K) for a drop in pressure. If pressure drop is noted, replace DV-5
A
Diaphragm and correct any leaks before proceeding.
12.
If Diaphragm Gauge (K) indicates no drop in pressure, re-open Diaphragm Supply Valve
(P) and proceed.
13.
Open Air Supply Control Valve (Y) to pressurize system piping.
14.
Partially open System Main Control Valve (B). Slowly close Main Drain Valve (D) as water
discharges from Main Drain Valve (D). Observe Automatic Drain Valve (F) for leaks. If there
are leaks, correct the leakage problem.
15.
Close hinged cover of Manual Control Station (M) and insert new break rod in small hole
through the top of the enclosing box.
16.
Open System Main Control Valve (B).
17.
After setting fire protection system, notify proper authorities and advise those responsible
for monitoring proprietary and/or central station alarms.
Waterflow Alarm Test Procedure
1.
Open Alarm Test Valve (G), allowing water to flow to Waterflow Pressure Switch (C) and/or
Water Motor Alarm. Close Alarm Test Valve (G) when test is completed.
2.
Depress plunger on the Automatic Drain Valve (F) to drain alarm line.
Solenoid Valve Test Procedure For Electric Actuation
1.
Close System Main Control Valve (B) and open Main Drain Valve (D).
2.
Test deluge releasing panel in accordance with manufacturer’s instructions to energize
the Solenoid Valve (R).
3.
Verify that water is flowing from Solenoid Valve (R) drain connection.
4.
Verify Diaphragm Chamber pressure has decreased to below 25% of water supply pressure.
5.
Reset electric detection system in accordance with manufacturer’s instructions to de-ener-
gize Solenoid Valve (R). Water should top draining from Solenoid Valve (R) but remain draining
from Manual Reset Actuator (N).
6.
Press Reset Knob on Manual Reset Actuator (N) and hold a few seconds until water stops
flowing.
7.
After system pressure is restored, inspect Solenoid Valve (R) and Manual Reset Actuator
(N) for leaks. Correct any leaks before proceeding.
8.
Partially open System Main Control Valve (B). Slowly close Main Drain Valve (D) as water
discharges from Main Drain Valve (D). Observe Automatic Drain Valve (F) for leaks. If there
are leaks, correct the leakage problem. If there are no leaks, place DV-5
A
Valve in service and
open System Main Control Valve (B).
Solenoid Valve and Dry Pilot Actuator Test Procedure
1.
Close System Main Control Valve (B) and open Main Drain Valve (D).
2.
Simulate power failure by disconnecting main power to releasing panel, and disconnecting
battery back-up. Refer to releasing panel manufacturer’s instructions for specific details. This
step allows Solenoid Valve (S) to open.
3.
Open system’s Inspector’s Test Connection to relieve system air pressure.
4.
Verify water flow from Dry Pilot Actuator (T) drain connection.
5.
Verify Diaphragm Chamber pressure decreased to below 25% of water supply pressure.
6.
Close Inspector’s Test Connection and allow the system air pressure to re-establish. Water
stops draining from Dry Pilot Actuator (T) but continues to drain from Manual Reset Actua-
tor (N). Press Reset Knob on Manual Reset Actuator (N) and hold a few seconds until water
stops flowing from drain tube.
7.
Pressure will then build up in DV-5
A
Diaphragm Chamber.
8.
After system pressure is restored, inspect Solenoid Valve (R) and Manual Reset Actuator
(N) for leaks. Any leaks must be corrected before proceeding.
9.
Reestablish battery and main power to releasing panel in accordance with manufacturer’s
instructions.
10.
Partially open System Main Control Valve (B). Slowly close Main Drain Valve (D) as water
discharges from Main Drain Valve (D), then close Main Drain Valve (D). Observe Automatic
Drain Valve (F) for leaks and correct the leakage problem. If there are no leaks, place DV-5
A
Valve in service and open System Main Control Valve (B).
Supervisory Low Pressure Alarm Test Procedure and Validation of Normally Closed
Solenoid Valve (S)
1.
Close System Main Control Valve (B), and open Main Drain Valve (D).
2.
Crack open system’s Inspector’s Test Connection to relieve air pressure from system.
Verify Supervisory Low Pressure Alarm Switch (V) is operational and low pressure set point
is approximately 0,4 bar under minimum system air pressure.
3.
Allow system air pressure to decay to 0 psig. Verify no water draining from Dry Pilot Actu-
ator (T).
4.
Close system’s Inspector’s Test Connection and allow system supervisory pressure to auto-
matically re-established. As necessary, open, then close quick fill air supply control valve in
automatic air maintenance device. Supervisory Low Pressure Alarm Switch (V) should return
to “normal” condition.
5.
Verify system air pressure is normal and DV-5
A
Diaphragm Chamber remains pressurized.
6.
Partially open System Main Control Valve (B). Slowly close Main Drain Valve (D) as water
discharges from Main Drain Valve (D). Observe Automatic Drain Valve (F) for leaks. If there
are leaks, correct the leakage problem. If there are no leaks, place DV-5
A
Valve in service and
open System Main Control Valve (B).
Operation Test Procedure
1.
To prevent water from flowing beyond riser, close System Main Control Valve (B). Open
Main Drain Valve(D).
2.
Open System Main Control Valve (B) one turn beyond which water begins to flow from Main
Drain Valve (D). Slowly close Main Drain Valve (D).
3.
Test deluge releasing panel in accordance with manufacturer’s instructions to energize
Solenoid Valve (R).
4.
Verify DV-5
A
Valve has tripped, as indicated by water flow into system.
5.
Close System Main Control Valve (B).
6.
Close Diaphragm Supply Valve (P) and Air Supply Control Valves (X) and (Y).
7.
Reset DV-5
A
Valve with Preaction Type A Trim in accordance with Valve Setting Procedure.
Internal Valve Inspection
1.
Ensure that Steps 1 to 4 of the Valve Setting Procedure are completed prior to proceeding
with the Internal Valve Inspection.
2.
Ensure Diaphragm Supply Valve (P) is closed. If provided as part of the valve trim, close
Inverted Flare Shut-Off Valve (AA).
3.
Remove the Supply Line between the Diaphragm Supply Valve (P) and the System Main
Control Valve (B). If provided as part of the valve trim, remove the Supply Line between the
Diaphragm Supply Valve (P) and Inverted Flare Shut-Off Valve (AA).
4.
Loosen union securing Actuation Trim and remove Actuation Trim.
5.
Remove union between Diaphragm Cover and MRA-1 Manual Reset Actuator (N). Remove
MRA-1 Manual Reset Actuator (N) subassembly.
6.
Remove Diaphragm Valve Cover hardware, slowly remove Diaphragm Cover and perform
internal valve inspection. Clean valve interior and replace parts as necessary.
7.
Ensure Diaphragm is properly oriented and proper hardware arrangement is utilized.
8.
Insert Long Hex Bolts. Align Diaphragm with Valve Body, and then align Diaphragm Cover
with Valve Body. Insert Short Hex Bolts. Hand-tighten all fasteners.
9.
Using crossdraw sequence, wrench-tighten Long Hex Bolts and Short Hex Bolts. Repeat
crossdraw sequence two to three times at incremental torque valves.
10.
Inspect to assure all Hex Bolts are securely tightened.
11.
Using the union, secure the MRA-1 Manual Reset Actuator (N) to the Diaphragm Cover.
12.
Using union, secure Actuation Trim.
13.
Replace the Supply Line between the Diaphragm Supply Valve and the System Main
Control Valve (B). If provided as part of the valve trim, replace Supply Line between Diaphragm
Supply Valve (P) and Inverted Flare Shut-Off Valve (AA).
14.
Ensure unions and flare fittings are securely tightened.
15.
If provided with the valve trim, and with Diaphragm Supply Valve (P) closed, fully open
Inverted Flare Shut-Off Valve (AA) stainless steel screw (approximately 1/2 in.) until resis-
tance is met.
16.
Proceed with Step 5 of the Valve Setting Procedures.
Item Description
P
Q
R
S
T
U
V
W
X
Y
Z
AA
Diaphragm Supply Valve
Diaphragm Supply Strainer
Solenoid Valve (NC) De-Energized #1
Solenoid Valve (NC) Energized #2
Dry Pilot Actuator
Pressure Relief Valve
Supervisory Low Pressure Alarm Switch
Air Supply Strainer
Air Supply Control Valve "A"
Air Supply Control Valve "B"
Dry Pilot Gauge
Inverted Flare Shut-Off Valve
Item Description
A
B
C
D
E
F
G
H
J
K
L
M
N
DV-5
a
Valve
System Main Control Valve
Waterflow Pressure Switch
Main Drain Valve
System Drain Valve
Automatic Drain Valve
Alarm Test Valve
Alarm Control Valve (Optional)
Water Supply Gauge
Diaphragm Gauge
System Gauge
Manual Control Station
Manual Reset Actuator
A
B
C
J
K
D
E
F
G
N
P
Q
V
X
Y
M
W
S
T
R
L
Z
U
H
AA
W
H
General
Description
The appendix found at the end of this
document provides valve setting and
testing/inspection procedures summa-
rized from the Care and Maintenance
section.
Some jurisdictions require a copy of the
Summary Instructions appendix to be
displayed in proximity to a DV-5
A
Auto-
matic Control Valve riser supplying a
fire protection system.
Reproduce as an individual poster by
printing on appropriate media.
A form of protection is recommended
to prevent damage which could render
the poster illegible. Conditions to avoid
include moisture infiltration, fading,
mutilation, etc.. Protective measures
may include lamination, placement
within an impact- and water-resistant
frame, etc.
The format shown in this document is
landscape orientation on US Tabloid
size, also known as ANSI B drawing
format, both roughly comparable to
ISO A3 size format.
To avoid potential cropping of content
when printing to A3 format, select
options such as print to fit or scale
to fit. Depending on printer capabil-
ity content will be slightly reduced but
should remain readable.
See Print Format Dimensions Table for
details.
Format
Imperial
in.
Metric
mm
W
H
W
H
US Tabloid
17
11
—
—
ANSI B
ISO A3
—
—
420
297
PRINT FORMAT DIMENSIONS
TFP1485 APPENDIX A
AUGUST 2022
1467 Elmwood Avenue, Cranston, RI 02910 | Tel1-401-781-8220
© 2022 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document
revision date and are subject to change without notice.
Worldwide
Contacts
www.tyco-fire.com
Summary Instructions
DV-5
A
Automatic Water Control Valve
Preaction Type A Systems
(EN12845 Compliance)
Scan the QR code or enter the URL
in a web browser to access the most
up-to-date electronic version of this
document. Data rates may apply.
docs.jci.com/tycofire/tfp1485
NOTICE
The procedures provided are summary instructions of the complete procedures appearing in
Technical Data Sheet TFP1485. If problems occur, consult full document.
Valve Setting Procedure
1.
Close System Main Control Valve (B), Diaphragm Supply Valve (P), and Air Supply Control
Valves (X) and (Y).
2.
Open Main Drain Valve (D), System Drain Valve (E), and all auxiliary drains in system. Also,
remove plug from Air Supply Strainer (W) to drain any water and ensure it is clean and free
of debris. Close auxiliary drain valves, System Drain Valve (E), and reassemble Air Supply
Strainer (W) after water stops discharging. Leave Main Drain Valve (D) open.
3.
Ensure Pressure Gauge Valves and Alarm Control Valve (H), as applicable, are open.
4.
Depress plunger of Automatic Drain Valve (F) to verify it is open.
5.
Clean Diaphragm Supply Strainer (Q). Flush strainer by opening the Diaphragm Supply
Valve (P).
6.
Replace operated automatic sprinklers on system piping.
7.
Reset DV-5
A
Valve Releasing Panel in accordance with manufacturer instructions.
8.
Re-establish system air pressure to reset Model DP-1 Dry Pilot Actuator (T) by opening Air
Supply Control Valve (X). Do not open Air Supply Control Valve (Y) at this time. Observe Dry
Pilot Actuator (T) air pressure on Dry Pilot Gauge (Z).
9.
Open Manual Control Station (M), then open Diaphragm Supply Valve (P). After aerated
water stops discharging from Manual Control Station (M) drain tube, slowly close operating
lever. Do not close hinged cover at this time.
10.
After aerated water stops discharging, reset Manual Reset Actuator (N) until water stops
flowing from its drain tube and pressure reaches approximately 15 psi (1,0 bar) on Diaphragm
Gauge (K).
11.
With diaphragm chamber pressurized, temporarily close Diaphragm Supply Valve (P), and
observe Diaphragm Gauge (K) for a drop in pressure. If pressure drop is noted, replace DV-5
A
Diaphragm and correct any leaks before proceeding.
12.
If Diaphragm Gauge (K) indicates no drop in pressure, re-open Diaphragm Supply Valve
(P) and proceed.
13.
Open Air Supply Control Valve (Y) to pressurize system piping.
14.
Partially open System Main Control Valve (B). Slowly close Main Drain Valve (D) as water
discharges from Main Drain Valve (D). Observe Automatic Drain Valve (F) for leaks. If there
are leaks, correct the leakage problem.
15.
Close hinged cover of Manual Control Station (M) and insert new break rod in small hole
through the top of the enclosing box.
16.
Open System Main Control Valve (B).
17.
After setting fire protection system, notify proper authorities and advise those responsible
for monitoring proprietary and/or central station alarms.
Waterflow Alarm Test Procedure
1.
Open Alarm Test Valve (G), allowing water to flow to Waterflow Pressure Switch (C) and/or
Water Motor Alarm. Close Alarm Test Valve (G) when test is completed.
2.
Depress plunger on the Automatic Drain Valve (F) to drain alarm line.
Solenoid Valve Test Procedure For Electric Actuation
1.
Close System Main Control Valve (B) and open Main Drain Valve (D).
2.
Test deluge releasing panel in accordance with manufacturer’s instructions to energize
the Solenoid Valve (R).
3.
Verify that water is flowing from Solenoid Valve (R) drain connection.
4.
Verify Diaphragm Chamber pressure has decreased to below 25% of water supply pressure.
5.
Reset electric detection system in accordance with manufacturer’s instructions to de-ener-
gize Solenoid Valve (R). Water should top draining from Solenoid Valve (R) but remain draining
from Manual Reset Actuator (N).
6.
Press Reset Knob on Manual Reset Actuator (N) and hold a few seconds until water stops
flowing.
7.
After system pressure is restored, inspect Solenoid Valve (R) and Manual Reset Actuator
(N) for leaks. Correct any leaks before proceeding.
8.
Partially open System Main Control Valve (B). Slowly close Main Drain Valve (D) as water
discharges from Main Drain Valve (D). Observe Automatic Drain Valve (F) for leaks. If there
are leaks, correct the leakage problem. If there are no leaks, place DV-5
A
Valve in service and
open System Main Control Valve (B).
Solenoid Valve and Dry Pilot Actuator Test Procedure
1.
Close System Main Control Valve (B) and open Main Drain Valve (D).
2.
Simulate power failure by disconnecting main power to releasing panel, and disconnecting
battery back-up. Refer to releasing panel manufacturer’s instructions for specific details. This
step allows Solenoid Valve (S) to open.
3.
Open system’s Inspector’s Test Connection to relieve system air pressure.
4.
Verify water flow from Dry Pilot Actuator (T) drain connection.
5.
Verify Diaphragm Chamber pressure decreased to below 25% of water supply pressure.
6.
Close Inspector’s Test Connection and allow the system air pressure to re-establish. Water
stops draining from Dry Pilot Actuator (T) but continues to drain from Manual Reset Actua-
tor (N). Press Reset Knob on Manual Reset Actuator (N) and hold a few seconds until water
stops flowing from drain tube.
7.
Pressure will then build up in DV-5
A
Diaphragm Chamber.
8.
After system pressure is restored, inspect Solenoid Valve (R) and Manual Reset Actuator
(N) for leaks. Any leaks must be corrected before proceeding.
9.
Reestablish battery and main power to releasing panel in accordance with manufacturer’s
instructions.
10.
Partially open System Main Control Valve (B). Slowly close Main Drain Valve (D) as water
discharges from Main Drain Valve (D), then close Main Drain Valve (D). Observe Automatic
Drain Valve (F) for leaks and correct the leakage problem. If there are no leaks, place DV-5
A
Valve in service and open System Main Control Valve (B).
Supervisory Low Pressure Alarm Test Procedure and Validation of Normally Closed
Solenoid Valve (S)
1.
Close System Main Control Valve (B), and open Main Drain Valve (D).
2.
Crack open system’s Inspector’s Test Connection to relieve air pressure from system.
Verify Supervisory Low Pressure Alarm Switch (V) is operational and low pressure set point
is approximately 0,4 bar under minimum system air pressure.
3.
Allow system air pressure to decay to 0 psig. Verify no water draining from Dry Pilot Actu-
ator (T).
4.
Close system’s Inspector’s Test Connection and allow system supervisory pressure to auto-
matically re-established. As necessary, open, then close quick fill air supply control valve in
automatic air maintenance device. Supervisory Low Pressure Alarm Switch (V) should return
to “normal” condition.
5.
Verify system air pressure is normal and DV-5
A
Diaphragm Chamber remains pressurized.
6.
Partially open System Main Control Valve (B). Slowly close Main Drain Valve (D) as water
discharges from Main Drain Valve (D). Observe Automatic Drain Valve (F) for leaks. If there
are leaks, correct the leakage problem. If there are no leaks, place DV-5
A
Valve in service and
open System Main Control Valve (B).
Operation Test Procedure
1.
To prevent water from flowing beyond riser, close System Main Control Valve (B). Open
Main Drain Valve(D).
2.
Open System Main Control Valve (B) one turn beyond which water begins to flow from Main
Drain Valve (D). Slowly close Main Drain Valve (D).
3.
Test deluge releasing panel in accordance with manufacturer’s instructions to energize
Solenoid Valve (R).
4.
Verify DV-5
A
Valve has tripped, as indicated by water flow into system.
5.
Close System Main Control Valve (B).
6.
Close Diaphragm Supply Valve (P) and Air Supply Control Valves (X) and (Y).
7.
Reset DV-5
A
Valve with Preaction Type A Trim in accordance with Valve Setting Procedure.
Internal Valve Inspection
1.
Ensure that Steps 1 to 4 of the Valve Setting Procedure are completed prior to proceeding
with the Internal Valve Inspection.
2.
Ensure Diaphragm Supply Valve (P) is closed. If provided as part of the valve trim, close
Inverted Flare Shut-Off Valve (AA).
3.
Remove the Supply Line between the Diaphragm Supply Valve (P) and the System Main
Control Valve (B). If provided as part of the valve trim, remove the Supply Line between the
Diaphragm Supply Valve (P) and Inverted Flare Shut-Off Valve (AA).
4.
Loosen union securing Actuation Trim and remove Actuation Trim.
5.
Remove union between Diaphragm Cover and MRA-1 Manual Reset Actuator (N). Remove
MRA-1 Manual Reset Actuator (N) subassembly.
6.
Remove Diaphragm Valve Cover hardware, slowly remove Diaphragm Cover and perform
internal valve inspection. Clean valve interior and replace parts as necessary.
7.
Ensure Diaphragm is properly oriented and proper hardware arrangement is utilized.
8.
Insert Long Hex Bolts. Align Diaphragm with Valve Body, and then align Diaphragm Cover
with Valve Body. Insert Short Hex Bolts. Hand-tighten all fasteners.
9.
Using crossdraw sequence, wrench-tighten Long Hex Bolts and Short Hex Bolts. Repeat
crossdraw sequence two to three times at incremental torque valves.
10.
Inspect to assure all Hex Bolts are securely tightened.
11.
Using the union, secure the MRA-1 Manual Reset Actuator (N) to the Diaphragm Cover.
12.
Using union, secure Actuation Trim.
13.
Replace the Supply Line between the Diaphragm Supply Valve and the System Main
Control Valve (B). If provided as part of the valve trim, replace Supply Line between Diaphragm
Supply Valve (P) and Inverted Flare Shut-Off Valve (AA).
14.
Ensure unions and flare fittings are securely tightened.
15.
If provided with the valve trim, and with Diaphragm Supply Valve (P) closed, fully open
Inverted Flare Shut-Off Valve (AA) stainless steel screw (approximately 1/2 in.) until resis-
tance is met.
16.
Proceed with Step 5 of the Valve Setting Procedures.
Item Description
P
Q
R
S
T
U
V
W
X
Y
Z
AA
Diaphragm Supply Valve
Diaphragm Supply Strainer
Solenoid Valve (NC) De-Energized #1
Solenoid Valve (NC) Energized #2
Dry Pilot Actuator
Pressure Relief Valve
Supervisory Low Pressure Alarm Switch
Air Supply Strainer
Air Supply Control Valve "A"
Air Supply Control Valve "B"
Dry Pilot Gauge
Inverted Flare Shut-Off Valve
Item Description
A
B
C
D
E
F
G
H
J
K
L
M
N
DV-5
a
Valve
System Main Control Valve
Waterflow Pressure Switch
Main Drain Valve
System Drain Valve
Automatic Drain Valve
Alarm Test Valve
Alarm Control Valve (Optional)
Water Supply Gauge
Diaphragm Gauge
System Gauge
Manual Control Station
Manual Reset Actuator
A
B
C
J
K
D
E
F
G
N
P
Q
V
X
Y
M
W
S
T
R
L
Z
U
H
AA
W
H