Tyco DV-5A Manual Download Page 1

DV-5a Automatic Water Control Valve Electric/

Electric Double Interlock Preaction Fire Protection

Systems 1 1/2 Inch to 8 Inch (DN40 to DN200)

Page 1 of 18 

SEPTEMBER 2022 

TFP1466

Worldwide 

Contacts

www.tyco-fire.com

IMPORTANT

Refer to Technical Data Sheet 

TFP2300 for warnings pertaining to 

regulatory and health information.

Scan the QR code or enter the URL 

in a web browser to access the most 

up-to-date electronic version of this 

document. Data rates may apply.

docs.jci.com/tycofire/tfp1466

General 

Description

The TYCO DV-5

a

 Automatic Water 

Control Valves are diaphragm type 

valves that can be used in double inter-

lock preaction fire protection systems. 

When properly trimmed, the double 

seat design of the DV-5

a

 Valve also 

provides actuation of fire alarms upon 

system operation.
The diaphragm style design of the 

DV-5

a

 Valve allows external resetting, 

providing for easy resetting of a deluge 

system without having to open a valve 

handhole cover to manually reposition 

a clapper and/or latch mechanism. 

Simply re-pressurizing the diaphragm 

chamber resets the valve.
The DV-5

a

 features internal and exter-

nal coating of the valve to provide 

corrosion resistance. The external cor-

rosion resistance of the epoxy coating 

permits the use of the DV-5

a

 in cor-

rosive atmospheres associated with 

many types of industrial processing 

plants and outdoor installations.
The DV-5

a

 Valves are offered with the 

DV-5

a

 Valve and separately ordered 

semi-assembled trim shown in Figures 

6 and 7, or, for ease of installation, with 

DV-5

a

 Valve completely trimmed with or 

without a System Main Control Valve.
Double interlock preaction systems are 

designed for use in applications, such 

as refrigerated areas, requiring the 

maximum degree of protection against 

inadvertent flooding of the sprinkler 

system piping. In order for a double 

interlock preaction system to automat-

ically activate, two independent events 

must occur. First, the electric detection 

system must operate, and secondly, 

an automatic sprinkler on the system 

piping must operate. Typically, the 

electric detection system is designed to 

operate before any automatic sprinkler. 

Operation of just the electric detection, 

or just the opening of a sprinkler will 

not allow the DV-5

a

 Valve to open and 

permit water to flow into the normally 

dry sprinkler system piping. However, 

operation of just the electric detec-

tion system or the opening of a sprin-

kler (loss of system air pressure) will 

result in a supervisory alarm to notify 

the building occupants of a condition 

Available End Connections and Weights — lb/(kg)

End Connection

Nominal Valve Size 

ANSI Inches 

(DN)

Inlet

Outlet

1 1/2 

(40)

(50)

(80)

(100)

(150)

165,1 

mm

(200)

Thread

Thread

26 

(11,8)

25 

(11,3)

N/A

N/A

N/A

N/A

N/A

Groove

Groove

25 

(11,3)

25 

(11,3)

60 

(27,2)

95 

(43,1)

177 

(80,3)

177 

(80,3)

327 

(148,3)

Flange

Groove

N/A

N/A

66 

(30,0)

106 

(48,1)

190 

(86,2)

N/A

346 

(157,0)

Flange

Flange

N/A

N/A

72 

(32,7)

116 

(52,6)

204 

(92,5)

N/A

365 

(165,6)

Summary of Contents for DV-5A

Page 1: ...llations The DV 5a Valves are offered with the DV 5a Valve and separately ordered semi assembled trim shown in Figures 6 and 7 or for ease of installation with DV 5a Valve completely trimmed with or w...

Page 2: ...Numbers given do not replace Hex Bolt Hex Nut Lift Washer or Hoist Ring with common hardware parts e Also applicabale to metric 165 1 mm size 1 1 2 AND 2 INCH VALVES ONLY 6 AND 8 INCH VALVES ONLY 7 9...

Page 3: ...TEM OPEN TO ATMOSPHERE ALARM PORT WATERFLOW TO ALARM WATER SUPPLY PRESSURE ALARM TEST SYSTEM DRAIN OPEN SYSTEM DRAIN OPEN MAIN DRAIN CLOSED MAIN DRAIN OPEN DIAPHRAGM CHAMBER SUPPLY FROM UPSTREAM SIDE...

Page 4: ...es are pressure rated to 16 bar Valve Trim The maximum pressure rating for the Electric Electric Double Interlock Pre action Trim is dependent on separately ordered solenoid valve per Technical Data S...

Page 5: ...ed below the valve trip point The water supply pressure then forces the Diaphragm open permitting water to flow into the system piping as well as through the Alarm Port to actuate the system alarms se...

Page 6: ...s that may be used with this trim package is given in Technical Data Sheet TFP2180 Nominal installation dimensions for the Double Interlock Preaction System With Electric Electric Actuation Trim are s...

Page 7: ...uired when the valve is exposed to such supplies and other corrosive conditions or chemicals that could impact valve materials or the operation of the assembly The system and all components must be de...

Page 8: ...ating lever by pushing it up Do not close the hinged cover at this time Step 11 After allowing water to flow out of the Manual Reset Actuator N drain tube until aerated water ceases to dis charge rese...

Page 9: ...e and Item A7 is provided as P N 52 287 1 124 described in Technical Data Sheet TFP2180 4 When ordering DV 5A Trim separately from the DV 5A Valve Items A1 through A10 are separately ordered as applic...

Page 10: ...CHECK VALVE 923221003 923221003 923221003 923221003 923221003 923221003 10 1 1 2 SWING CHECK VALVE 460491007 460491007 460491007 460491007 460491007 460491007 11 1 1 2 Y STRAINER 523531006 523531006 5...

Page 11: ...x 5 1 2 x 5 1 2 x 5 1 2 1 2 x 5 1 2 1 2 x 5 1 2 1 2 x 6 1 2 52 1 PIPE NIPPLE 1 2 x 5 1 2 x 5 1 2 x 4 1 2 1 2 x 5 1 2 x 7 1 2 1 2 x 9 1 2 53 1 PIPE NIPPLE 3 4 x 5 3 4 x 5 3 4 x 6 3 4 x 7 3 4 x 9 3 4 x...

Page 12: ...3 6 91 4 100 4 5 114 11 9 302 12 6 320 16 5 419 21 0 533 5 5 140 16 8 427 4 54 115 4 3 109 63 150 5 7 145 13 4 340 14 5 368 18 4 467 24 8 630 3 8 97 22 4 569 5 83 148 5 7 145 8 200 6 8 174 16 1 409 16...

Page 13: ...ividual instructions for the solenoid valve dry pilot actuator manual control station switches and pressure maintenance device should be reviewed The following procedures pertain to the automatic cont...

Page 14: ...matic Drain Valve Alarm Test Valve Alarm Control Valve Optional Water Supply Gauge Diaphragm Gauge System Gauge Manual Control Station Item Description N P Q R S T U V W X Manual Reset Actuator Diaphr...

Page 15: ...ed to the Model MRA 1 Manual Reset Actuator N That the Waterflow Pressure Switch C and its associated alarms prop erly operate That the Water Motor Alarm if appli cable properly operates NOTE Thisproc...

Page 16: ...4 in DN100 550011540 6 in DN150 550011560 8 in DN200 550011580 Flange x Flange ANSI 3 in DN80 550021530 4 in DN100 550021540 6 in DN150 550021560 8 in DN200 550021580 Flange x Grooved ANSI 3 in DN80...

Page 17: ...External Trim Connections drains pressure switches water motor alarms etc APAC DV 5A Valves with Galvanized Trim Specify Size specify DV 5a Auto matic Water Control Valve specify end connection with a...

Page 18: ...DV 5a Valve Trim P N See Figure 6 DV 5A Valve Trim Accessories for separately ordered valve trim Specify Specify Accessory Descrip tion P N specify Model QRS Quick Refer to Technical Release Switch Q1...

Page 19: ...Valve Optional Water Supply Gauge Diaphragm Gauge System Gauge Manual Control Station Manual Reset Actuator A B C J K D E F G N P Q V X Y M W S T R L Z U H AA W H General Description The appendix fou...

Page 20: ...ure is within normally expected range 2 If below normal range correct any leakage from diaphragm chamber prior to resetting the system 3 When water supply pressure is restored reset DV 5a Valve in acc...

Reviews: