The  TYCO  Model  AMD-1  Automatic 

Air Maintenance Device must be main-

tained and serviced in accordance with 

the following instructions, in addition to 

any specific requirements of the NFPA. 

Any impairment must be immediately 

corrected.

NOTICE

Before closing a fire protection system 

main  control  valve  for  maintenance 

work  on  the  fire  protection  system 

that  it  controls,  obtain  permission  to 

shut  down  the  affected  fire  protec-

tion  system  from  the  proper  authori-

ties and notify all personnel who may 

be affected by this action.

It  is  recommended  that  accumulated 

moisture be removed from air supply 

moisture  filtration  equipment  at  least 

quarterly.  More  frequent  inspections 

may be necessary in particularly humid 

environments.
After placing a fire protection system 

in service, notify the proper authorities 

and advise those responsible for mon-

itoring proprietary and/or central sta-

tion alarms. 
Responsibility lies with owners for the 

inspection, testing, and maintenance of 

their fire protection system and devices 

in compliance with this document, as 

well as with the applicable standards of 

the National Fire Protection Association 

(for example, NFPA 25), in addition to 

the standards of any other authorities 

having jurisdiction. Contact the install-

ing  contractor  or  sprinkler  manufac-

turer regarding any questions.
Automatic  sprinkler  systems  are  rec-

ommend to be inspected, tested, and 

maintained  by  a  qualified  Inspec-

tion Service in accordance with local 

requirements and/or national code. 
The  Model  AMD-1  Device  must  be 

inspected quarterly in accordance with 

the following instructions. 
1.  Verify  that  the  By-Pass  Valve  is 

closed. 

2.  Close the Model AMD-1 Air Supply 

Control Valve and clean out the 1/4 

inch Strainer located at the inlet to 

the Restrictor Check Valve. Be sure 

to reinstall the strainer screen and 

tighten the cap securely. 

3.  Open  the  Model  AMD-1  Air  Sup-

ply  Valve  and  verify  that  the  con-

trol valve in the air supply trim to the 

system to pressurize is open. 

4.  Verify  that  the  system  pressure  is 

essentially the same as the previ-

ously  established  requirement.  If 

not, adjust the system pressure as 

follows: 
a. Close  the  system’s  main  con-

trol  valve  and  open  the  main 

drain  valve.  If  the  system  is  so 

equipped, close the Accelerator 

Control Valve. 

b. Follow Steps 1 through 14 in the 

Setting Procedure section.

c. Slowly open the Accelerator Con-

trol Valve, as applicable.

d. Slowly  open  the  main  control 

valve. After water begins to flow, 

slowly close the main drain valve, 

then  completely  open  the  main 

control valve. The Model AMD-1 

Automatic 

Air 

Maintenance 

Device is now ready for service. 

Limited  

Warranty

Products  manufactured  by  Tyco  Fire 

Suppression  &  Building  Products 

(TFSBP)  are  warranted  solely  to  the 

original Buyer for ten (10) years against 

defects  in  material  and  workmanship 

when  paid  for  and  properly  installed 

and maintained under normal use and 

service.  This  warranty  will  expire  ten 

(10)  years  from  date  of  shipment  by 

TFSBP. No warranty is given for prod-

ucts or components manufactured by 

companies not affiliated by ownership 

with TFSBP or for products and com-

ponents  which  have  been  subject  to 

misuse,  improper  installation,  corro-

sion, or which have not been installed, 

maintained,  modified  or  repaired  in 

accordance with applicable Standards 

of the National Fire Protection Associa-

tion, and/or the standards of any other 

Authorities Having Jurisdiction. Mate-

rials found by TFSBP to be defective 

shall be either repaired or replaced, at 

TFSBP’s  sole  option.  TFSBP  neither 

assumes,  nor  authorizes  any  person 

to assume for it, any other obligation 

in  connection  with  the  sale  of  prod-

ucts or parts of products. TFSBP shall 

not be responsible for sprinkler system 

design errors or inaccurate or incom-

plete information supplied by Buyer or 

Buyer’s representatives. 
In  no  event  shall  TFSBP  be  liable,  in 

contract,  tort,  strict  liability  or  under 

any  other  legal  theory,  for  incidental, 

indirect, special or consequential dam-

ages, including but not limited to labor 

charges, regardless of whether TFSBP 

was informed about the possibility of 

such damages, and in no event shall 

TFSBP’s  liability  exceed  an  amount 

equal to the sales price. 

The foregoing warranty is made in lieu 

of any and all other warranties, express 

or implied, including warranties of mer-

chantability and fitness for a particular 

purpose.
This  limited  warranty  sets  forth  the 

exclusive remedy for claims based on 

failure of or defect in products, materi-

als or components, whether the claim is 

made in contract, tort, strict liability or 

any other legal theory. 
This  warranty  will  apply  to  the  full 

extent permitted by law. The invalidity, 

in whole or part, of any portion of this 

warranty will not affect the remainder.

Ordering  

Procedure

Contact your local distributor for avail-

ability.  When  placing  an  order,  indi-

cate the full product name, including 

description and Part Number (P/N).

Model AMD-1 Device

Specify: Model AMD-1 Automatic Air 

Maintenance Device, 

P/N 52-324-2-002.

Replacement Parts

Specify: (description) for use with the 

Model  AMD-1  Automatic  Air  Mainte-

nance Device, P/N (from Figure 1). 