background image

PowerSeries Neo Installation Guide

Safety Instructions for Service Personnel

When using equipment connected to the telephone network, always follow the
basic safety instructions provided with this product. Inform the end-user of the
safety precautions that must be observed when operating this equipment.

Before Installing The Equipment

Ensure your package includes the following items:

l

HS2016-4/HS2016/2032/2064/2128 alarm controller

l

Power Supply, direct plug-in

l

Installation and user guides, including the safety instructions

Selecting A Suitable Location For The Alarm Controller

Refer to the following list to find a suitable location to install this equipment:

l

Locate near a telephone socket and power outlet.

l

Select a location free from vibration and shock.

l

Place alarm controller on a flat, stable surface and follow the installation
instructions.

l

Do not locate the equipment where people may walk on the secondary circuit
cable(s).

l

Do not connect alarm controller to the same electrical circuit as large appli-
ances.

l

Do not select a location that exposes your alarm controller to direct sunlight,
excessive heat, moisture, vapors, chemicals or dust.

l

Do not install this equipment near water. (e.g., bath tub, kitchen/laundry
sink, wet basement, near a swimming pool).

l

Do not install this equipment and accessories in areas where risk of explo-
sion exists.

l

Do not connect this equipment to electrical outlets controlled by wall
switches or automatic timers.

l

Avoid interference sources.

l

Avoid installing equipment near heaters, air conditioners, ventilators, and
refrigerators.

l

Avoid locating equipment close to or on top of large metal objects (e.g., wall
studs).

See "Locating Detectors and Escape Plan" on page 17 for information on locating
smoke and CO detectors.

Safety Precautions Required During Installation

l

Never install this equipment and/or telephone wiring during a lightning
storm.

l

Never touch uninsulated telephone wires or terminals unless the telephone
line has been disconnected at the network interface.

l

Position cables so that accidents can not occur. Connected cables must not be
subject to excessive mechanical strain.

l

Use only the power supply provided with this equipment. Use of unau-
thorized power supplies may cause damage.

l

For direct plug-in versions, use the power supply provided with the device.

WARNING:

This equipment has no mains on/off switch. The plug of the direct

plug-in power supply is intended to serve as the disconnecting device if the
equipment must be quickly disconnected. It is imperative that access to the mains
plug and associated mains socket/outlet is never obstructed.

IMPORTANT NOTES

l

This equipment is stationary-fixed with a direct plug-in external transformer
or a permanently connected internal transformer dependent on the region. It
must be installed by Service Persons only (Service Person is defined as a per-
son having the appropriate technical training and experience necessary to be
aware of hazards to which that person may be exposed in performing a task
and of measures to minimize the risks to that person or other persons). It
must be installed and used within an environment that provides the pollution
degree max 2, over voltages category II, in non-hazardous, indoor locations
only.

l

This equipment has no mains on/off switch; if the equipment must be quickly
disconnected, the plug of the direct plug-in power supply is intended to serve
as the disconnecting device. It is imperative that access to the mains plug and
associated mains socket/outlet, is never obstructed.

l

For permanently connected versions, the fuse in the power connector serves
as the disconnecting device. The disconnect device will only remove the
mains power and will not disconnect battery power. The installer is respons-
ible to ensure that a readily accessible mains disconnect device is incor-
porated in the building for permanently connected installations.

l

There are no end user replaceable parts replaceable within this equipment.

l

Before servicing, disconnect the mains power, battery and telephone con-
nections.

l

The equipment enclosure must be secured to the building structure before
operation.

l

All national wiring rules must be observed.

l

The wiring (cables) used for installation of the alarm system and accessor-
ies, shall be insulated with PVC, TFE, PTFE, FEP, Neoprene or Polyamide.

l

Do not route any wiring over circuit boards

l

Ensure that cables are positioned so that accidents cannot occur:
- Internal wiring must be routed in a manner that prevents;
- Excessive strain or loosening of wire on terminal connections;
- Damage of conductor or insulation.

l

Disposal of used batteries must be made in accordance with local waste
recovery and recycling regulations.

l

Use authorized accessories only with this equipment.

l

Do not place any object on the top of the cabinet.

l

Do not spill any liquids on the cabinet.

l

Do not touch the equipment and its connected cables during an electrical
storm; there may be a risk of electric shock.

l

Save these safety instructions for future use.

l

These safety instructions should not prevent you from contacting the dis-
tributor and/or the manufacturer to obtain any further clarification and/or
answers to your concerns.

Installation

Mounting the Enclosure

Locate the panel in a dry area, preferably near an unswitched AC power source
and the incoming telephone line. Complete all wiring before applying AC or
connecting the battery.

Terminal Descriptions

The following terminals are available on the PowerSeries Neo alarm controller.

Terminal Description

BAT+,
BAT-

Battery terminals. Use to provide backup power and additional current
when system demands exceed the power output of the transformer, such
as when the system is in alarm.

Do not connect the battery until all other wiring is complete.

AC

Power terminals.

Connect the battery before connecting the AC. Do not connect the battery
or transformer until all other wiring is complete.

AUX+,
AUX-

Auxiliary terminals. Use to power modules, detectors, relays, LEDs, etc.
(700mA MAX). Connect the positive side of device to AUX+, the
negative side to AUX-.

BELL+,
BELL-

Bell/Siren power (700mA MAX). Connect the positive side of any alarm
warning device to BELL+, the negative side to BELL-.

RED, BLK,
YEL, GRN

Corbus terminals. Use to provide communication between the alarm
controller and connected modules. Each module has four Corbus
terminals that must be connected to the Corbus.

PGM1 to
PGM4

Programmable output terminals. Use to activate devices such as LEDs.

(PGM1, PGM3, and PGM4: 50mA PGM2: 300mA or can be configured
as an input)

Z1 to Z8

COM

Zone input terminals. Ideally, each zone should have one detection
device; however, multiple detection devices can be wired to the same
zone.

EGND

Earth ground connection.

TIP, RING,
T-1, R-1

Telephone line terminals.

PCLINK_1

DLS/SA

PCLINK_2

DLS/SA, Alternate Communicator

Corbus Wiring

The RED and BLK Corbus terminals are used to provide power while YEL and
GRN are used for data communications. The 4 Corbus terminals of the alarm
controller must be connected to the 4 Corbus terminals or wires of each module.

The following conditions apply:

l

Corbus should be run with minimum 22 gauge quad, two pair twisted pre-
ferred.

l

The modules can be home run to the panel, connected in series or can be T-
tapped.

l

Do not use shielded wire for Corbus wiring.

Note:

Any module can be connected anywhere along the Corbus. Separate wire

runs for keypads, zone expanders etc. are not necessary.

Note:

No module can be more than 1,000'/305m (in wire length) from the panel.

Do not use shielded wire for Corbus wiring.

- 2 -

Summary of Contents for DSC PowerSeries Neo

Page 1: ...expander HSM2208 Power supply HSM2300 4 high current output expander HSM2204 Alternate communicator 3G2080E 3G2080RE TL280E TL280RE LE2080 R TL280LE R TL2803GE TL2803GRE TL8803G TL880LT TL880LE PCL 4...

Page 2: ...e will only remove the mains power and will not disconnect battery power The installer is respons ible to ensure that a readily accessible mains disconnect device is incor porated in the building for...

Page 3: ...e Corbus Current Calculation Chart For UL ULC and Commercial Listed applications the total standby and alarm current cannot exceed 700mA Table 1 2 Corbus Current Calculation Chart Item Current mA x Qu...

Page 4: ...2 wire smoke detectors 24 hr burglary input alarm Note Use SEOL resistors on Fire zones only Figure 1 2 LED Output with Current Limiting Resistor and Optional Relay Driver Output Single End of Line SE...

Page 5: ...e ID 804 001 716 Every wireless device has an ID printed on the sticker attached to the device The format is XXX YYYY where l XXX identifies the type or model of the device l YYYY is a short encrypted...

Page 6: ...0 551 556 000 Set up partition account codes 310 001 008 Set up partition timers l Entry exit delay settle delay 005 001 008 l Automatic arming disarming schedule 151 158 001 002 l Auto disarming holi...

Page 7: ...s 2 to enter the Trouble menu l On an LCD keypad scroll to a trouble type then press to view the spe cific trouble The zone name and trouble condition for each trouble are dis played on the screen l O...

Page 8: ...ate communicator has stopped responding 10 Alt Comm FTC Trouble The alternate communicator has failed to communicate an internal event not generated by the panel Trouble 12 Not Networked Troubles 01 Z...

Page 9: ...e l Battery capacity l 12 hours EN50131 l 24 hours INCERT Belgium Note For T 014 compliance INCERT certification only 14Ah 2x7Ah batteries were tested and are accepted for INCERT certified systems l M...

Page 10: ...Times Partition 1 8 Entry Delay 1 030 sec Entry Delay 2 045 sec CP 01 030 sec Exit Delay 120 sec CP 01 060 sec Settle Delay 010 sec CP 01 000 sec 900 Bell Delay Partition Mask Y Y Y Y Y Y Y Y 901 Day...

Page 11: ...ence Chime During Quick Exit Delay 8 Bell Squawk on Away Arm Disarm Only 018 System Options 6 1 Test Transmission Exception 2 Real Time Bypass Reporting 3 Armed State PGM ON at End of Exit Delay 4 Not...

Page 12: ...er Lead OUT 03 DLS Lead IN 04 DLS Lead OUT 05 SA Lead IN 06 SA Lead OUT 07 Event Buffer 75 Full 313 Maintenance Events 3 01 Firmware Update Begin 02 Firmware Update Success 03 Firmware Update Fail 314...

Page 13: ...0 102 Interval 1 End Time 0000 103 Interval 1 Days Assignment 01 Sunday 02 Monday 03 Tuesday 04 Wednesday 05 Thursday 06 Friday 07 Saturday 104 Interval 1 Holiday Assignment 09 Holiday 1 10 Holiday 2...

Page 14: ...stem Information and Testing 900 System Information 000 Control Panel Version 001 016 Keypad 1 16 Version Info 101 116 8 HSM2108 1 16 Version Info 201 216 HSM2208 Version Information 460 Alternate Com...

Page 15: ...011 012 013 014 015 016 017 018 019 020 021 022 023 024 025 026 027 028 029 030 031 032 033 034 035 036 037 038 039 040 041 042 043 044 045 046 047 048 049 050 051 052 053 054 055 056 057 058 059 060...

Page 16: ...110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 Module Record Module Type Slot Serial Number Module Type Slot Serial Number Wireless Device Record Device Type Zone Serial...

Page 17: ...on within the house Since many fires occur at night special attention should be given to the escape routes from sleeping quarters 3 Escape from a bedroom must be possible without opening the interior...

Page 18: ...equipment as per EN50131 1 2006 A1 2009 EN50131 3 2009 EN50131 6 2008 A1 2014 Type A EN50136 1 1 1997 EN50136 2 1 EN50136 2 3 ATS2 Standards This device is suitable for use in systems with the followi...

Page 19: ...hods a push button switch mounted outside the supervised premises Instructions to be provided for the zone type to be programmed for the key arming or b protective switch i e door contact fitted to th...

Page 20: ...of merchantability or fitness for a particular purpose and of all other obligations or liabilities on the part of Digital Security Controls Digital Security Controls neither assumes responsibility fo...

Page 21: ...tuation SOFTWARE PRODUCT LICENSE EULA The SOFTWARE PRODUCT is protected by copyright laws and international copyright treaties as well as other intellectual property laws and treaties The SOFTWARE PRO...

Page 22: ...OTHER OBLIGATIONS OR LIABILITIES ON THE PART OF DSC DSC MAKES NO OTHER WARRANTIES DSC NEITHER ASSUMES NOR AUTHORIZES ANY OTHER PERSON PURPORTING TO ACT ON ITS BEHALF TO MODIFY OR TO CHANGE THIS WARRA...

Page 23: ...cipient agrees to the terms of this EULA If the SOFTWARE PRODUCT is an upgrade any transfer must also include all prior versions of the SOFTWARE PRODUCT f Termination Without prejudice to any other ri...

Page 24: ...ing pursuit of criminal prosecution wherever necessary All trademarks not owned by Tyco are the property of their respective owners and are used with permission or allowed under applicable laws Produc...

Reviews: