plied to the pipe threads, hand tighten
the sprinkler into the sprinkler fitting.

Step 3.

Tighten the sprinkler into the

sprinkler fitting using only the W-Type
6  Sprinkler Wrench  (Ref. Figure  5).
With reference to Figure 1, the W-Type
6 Sprinkler Wrench is to be applied to
the sprinkler wrench flats.

The

Series TY300-B Recessed Pen-

dent Sprinklers

must be installed in

accordance with the following instruc-
tions.

Step A.

After installing the Style 10

Mounting Plate over the sprinkler
threads and with pipe thread sealant
applied to the pipe threads, hand
tighten the sprinkler into the sprinkler
fitting.

Step B

. Tighten the sprinkler into the

sprinkler fitting using only the W-Type
7  Recessed Sprinkler Wrench  (Ref.
Figure 6). With reference to Figure 1,
the W-Type 7 Recessed Sprinkler
Wrench is to be applied to the sprinkler
wrench flats.

Step C.

After the ceiling has been in-

stalled or the finish coat has been ap-
plied, slide on the Style 10 Closure
over the Series TY300-B Sprinkler and
push the Closure over the Mounting
Plate until its flange comes in contact
with the ceiling.

The

Series TY300-B Horizontal Side-

wall Sprinklers

must be installed in

accordance with the following instruc-
tions.

Step 1.

Horizontal sidewall sprinklers

are  to  be installed in the  horizontal

TFP640

Page 3 of 6

FIGURE 1

STANDARD RESPONSE SERIES TY300-B UPRIGHT (TY3104) AND PENDENT (TY3204) SPRINKLERS

5.6 K-FACTOR, 1/2 INCH NPT

1 - Frame
2 - Button

3 - Sealing

Assembly

4 - Bulb
5 - Compression

Screw

6 - Deflector

*

Temperature rating is indicated on deflector or adjacent to

orifice seat on frame.

**

Pipe thread connections per ISO 7/1 can be provided on

special request.

2

4

5

6

PENDENT

CROSS SECTION

(55,6 mm)

2-3/16"

(38,1 mm)

1-1/2"

PLATE SEATING

ESCUTCHEON

7/16" (11,1 mm)

NOMINAL

MAKE-IN

FLATS

WRENCH

SURFACE

1

3

NPT

1/2"

RECESSED PENDENT

UPRIGHT

2-7/8" (73,0 mm) DIA.

(11,1 mm)

NOMINAL

MAKE-IN

7/16"

RECESSED

STYLE 10

ESCUTCHEON

(55,6 mm)

2-3/16"

1/2" NPT

DEFLECTOR

SSU

SSP DEFLECTOR

**

**

*

*

*

FIGURE 2

STANDARD RESPONSE SERIES TY300-B

HORIZONTAL SIDEWALL (TY3304) SPRINKLERS

5.6 K-FACTOR, 1/2 INCH NPT

1 - Frame
2 - Button
3 - Sealing

Assembly

4 - Bulb
5 - Compression

Screw

6 - Deflector

*

Temperature rating is indicated on deflector or adjacent to orifice seat on frame.

**

Pipe thread connections per ISO 7/1 can be provided on special request.

2

4

5

6

(11,1 mm)

NOMINAL

MAKE-IN

1

3

WRENCH

FLATS

1-1/2"

(38,1 mm)

2-3/16"

(55,6 mm)

7/16"

1-13/16"

(46,0 mm)

CENTERLINE

WATERWAY

OF SPRINKLER

HAT

DEFLECTOR

1/2"

NPT

*

9/16"

(14,3 mm)

**

PLATE

ESCUTCHEON

SEATING

SURFACE

OBSOLETE