Model TY-QRF – 5.6 K-factor
Flush Pendent Sprinkler
Quick Response, Standard Coverage
Page 1 of 4
AUGUST 2018
TFP190
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Worldwide
Contacts
www.tyco-fire.com
Sprinkler
Identification
Number (SIN)
TY3261
Technical
Data
Approvals
UL and ULC Listed
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficient
K=5.6 gpm/psi
½
(80,6 lpm/bar
½
)
Temperature Rating
162°F (72°C)
Vertical Adjustment
3/8 in. (9,5 mm)
Finishes
Sprinkler and Escutcheon:
Signal White or Chrome
Physical Characteristics
Body . . . . . . . . . . . . . . . . . . . . . . . . Copper Alloy
Deflector . . . . . . . . . . . . . . . . . . . . . . . . . Copper
Valve Cap . . . . . . . . . . . . . . . . . . . . Copper Alloy
Orifice Seal . . . . . . . . . . . . . . . . . . . . . . . . . PTFE
Heat Collectors . . . . . . . . . . . . . . . . . . . . Copper
Operation
The sprinkler assembly contains a
small fusible solder element. When
exposed to sufficient heat from a fire,
the solder melts and enables the inter-
nal components of the sprinkler to fall
away. At this point the sprinkler acti-
vates with the deflector dropping into
its operated position (Ref. Figure 1C),
permitting water to flow.
General
Description
TYCO Model TY-QRF 5.6K Quick
Response, Standard Coverage, Flush
Pendent Sprinklers are decorative,
fusible solder-type sprinklers. They are
designed for use in commercial light
and ordinary hazard occupancies such
as offices and restaurants. When aes-
thetics is the major consideration, the
TY-QRF should be your first choice.
The TY-QRF features a separa-
ble escutcheon providing 3/8 in.
(9,5 mm) vertical adjustment. This
adjustment reduces the accuracy
to which the fixed pipe drops to the
sprinklers must be cut to help assure
a perfect fit installation.
NOTICE
The Model TY-QRF Flush Pendent
Sprinklers described herein must be
installed and maintained in compli-
ance with this document, as well as
with the applicable standards of the
National Fire Protection Associa-
tion, in addition to the standards of
any authorities having jurisdiction.
Failure to do so may impair the perfor-
mance of these devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
Design
Criteria
TYCO Model TY-QRF 5.6K Quick
Response, Standard Coverage, Flush
Pendent Sprinklers are intended for
fire protection systems designed in
accordance with the standard instal-
lation rules recognized by the appli-
cable listing or approval agency
(e.g., UL Listing is based on NFPA 13
requirements).
Precautionary Warnings for
Corrosive Environments
The Model TY-QRF Flush Pendent
Sprinklers must be installed in a non-
corrosive environment. The improper
use of corrosive agents such as flux,
other products that contain chlo-
ride ions described, whether applied
internally or externally to the sprin-
kler system, may result in corrosion
of the sprinkler head, or stress corro-
sion cracking, which in turn may cause
the sprinklers heads to develop leaks,
operate unexpectedly, or not operate
properly.
Accordingly, it is essential that the
Model TY-QRF Flush Pendent Sprin-
klers be installed only by experienced
fire sprinkler engineers, who comply
fully with NFPA 13 and 25, ASTM B813,
ASTM B828 and Copper Development
Association (CDA).
OBSOLETE