Model TY-QRF – 5.6 K-factor 

Flush Pendent Sprinkler 

Quick Response, Standard Coverage

Page 1 of 4 

AUGUST 2018 

TFP190

IMPORTANT

Refer to Technical Data Sheet 

TFP2300 for warnings pertaining to 

regulatory and health information.
Always refer to Technical Data 

Sheet TFP700 for the “INSTALLER  

WARNING” that provides cautions 

with respect to handling and instal-

lation of sprinkler systems and com-

ponents. Improper handling and 

installation can permanently damage 

a sprinkler system or its compo-

nents and cause the sprinkler to fail  

to operate in a fire situation or cause  

it to operate prematurely.

Worldwide 

Contacts

www.tyco-fire.com

Sprinkler 

Identification 

Number (SIN)

TY3261

Technical

Data

Approvals

UL and ULC Listed

Maximum Working Pressure

175 psi (12,1 bar)

Discharge Coefficient

K=5.6 gpm/psi

½

 (80,6 lpm/bar

½

)

Temperature Rating

162°F (72°C)

Vertical Adjustment

3/8 in. (9,5 mm)

Finishes

Sprinkler and Escutcheon: 

Signal White or Chrome

Physical Characteristics

Body   . . . . . . . . . . . . . . . . . . . . . . . . Copper Alloy

Deflector . . . . . . . . . . . . . . . . . . . . . . . . .  Copper

Valve Cap  . . . . . . . . . . . . . . . . . . . . Copper Alloy

Orifice Seal . . . . . . . . . . . . . . . . . . . . . . . . . PTFE

Heat Collectors . . . . . . . . . . . . . . . . . . . .  Copper

Operation

The sprinkler assembly contains a 

small fusible solder element. When 

exposed to sufficient heat from a fire, 

the solder melts and enables the inter-

nal components of the sprinkler to fall 

away. At this point the sprinkler acti-

vates with the deflector dropping into 

its operated position (Ref. Figure 1C), 

permitting water to flow.

General 

Description

TYCO Model TY-QRF 5.6K Quick 

Response, Standard Coverage, Flush 

Pendent Sprinklers are decorative, 

fusible solder-type sprinklers. They are 

designed for use in commercial light 

and ordinary hazard occupancies such 

as offices and restaurants. When aes-

thetics is the major consideration, the 

TY-QRF should be your first choice.
The TY-QRF features a separa-

ble escutcheon providing 3/8 in. 

 

(9,5 mm) vertical adjustment. This 

adjustment reduces the accuracy 

to which the fixed pipe drops to the 

sprinklers must be cut to help assure 

a perfect fit installation.

NOTICE

The Model TY-QRF Flush Pendent 

Sprinklers described herein must be 

installed and maintained in compli-

ance with this document, as well as 

with the applicable standards of the 

National Fire Protection Associa-

tion, in addition to the standards of 

any authorities having jurisdiction. 

Failure to do so may impair the perfor-

mance of these devices.
The owner is responsible for main-

taining their fire protection system 

and devices in proper operating con-

dition. Contact the installing contrac-

tor or product manufacturer with any 

questions.

Design 

Criteria

TYCO Model TY-QRF 5.6K Quick 

Response, Standard Coverage, Flush 

Pendent Sprinklers are intended for 

fire protection systems designed in 

accordance with the standard instal-

lation rules recognized by the appli-

cable listing or approval agency 

(e.g., UL Listing is based on NFPA 13 

requirements).

Precautionary Warnings for 
Corrosive Environments

The Model TY-QRF Flush Pendent 

Sprinklers must be installed in a non-

corrosive environment. The improper 

use of corrosive agents such as flux, 

other products that contain chlo-

ride ions described, whether applied 

internally or externally to the sprin-

kler system, may result in corrosion 

of the sprinkler head, or stress corro-

sion cracking, which in turn may cause 

the sprinklers heads to develop leaks, 

operate unexpectedly, or not operate 

properly.
Accordingly, it is essential that the 

Model TY-QRF Flush Pendent Sprin-

klers be installed only by experienced 

fire sprinkler engineers, who comply 

fully with NFPA 13 and 25, ASTM B813, 

ASTM B828 and Copper Development 

Association (CDA).