DESIGN CRITERIA

The 2.8 K-Factor, Model LD-2 Upright, Pendent, and Re-
cessed Pendent Sprinklers are intended for fire protection
systems designed in accordance with the standard instal-
lation rules recognized by the applicable Listing or Ap-
proval agency (e.g., UL Listing is based on NFPA 13 re-
quirements). With the exception of a Starmist Recessed
Escutcheon, only the #2085 Recessed Escutcheon de-
scribed herein is to be used for recessed installations.

INSTALLATION

The 2.8 K-Factor, Model LD-2 Sprinklers must be in-
stalled in accordance with the following instructions:

NOTES

A leak tight 1/2 inch NPT sprinkler joint should be ob-
tained with a torque of 7 to 14 ft.lbs. (9,5 to 19,0 Nm). A
maximum of 21 ft. lbs. (28,5 Nm) of torque may be used
to install sprinklers with 1/2 NPT connections. Higher lev-
els of torque may distort the sprinkler inlet with conse-
quent leakage or impairment of the sprinkler.

Do not attempt to make-up for insufficient adjustment in
the escutcheon plate by under- or over-tightening the
sprinkler. Readjust the position of the sprinkler fitting to
suit.

The

Model LD-2 Pendent and Upright Sprinklers

must

be installed in accordance with the following instructions.

1. Pendent sprinklers are to be installed on the pendent

position, and upright sprinklers are to be installed in the
upright position.

2. With pipe thread sealant applied to the pipe threads, hand

tighten the sprinkler into the sprinkler fitting.

3. Tighten the sprinkler into the sprinkler fitting using only the

W-Type 9 Sprinkler Wrench (Ref. Figure 3), except that an
8 or 10 inch adjustable Crescent wrench is to be used for
wax coated sprinklers. With reference to Figure 1, the
W-Type 9 Sprinkler Wrench is to be applied to the sprinkler
wrenching area, and the adjustable Crescent wrench is to
be applied to the wrenching flanges.

When installing wax coated sprinklers with the adjustable
Crescent wrench, additional care needs to be exercised to
prevent damage to  the wax  coating on the sprinkler
wrenching flanges or frame arms and, consequently, ex-
posure of bare metal to the corrosive environment. The
jaws of the wrench should be opened sufficiently wide to
pass over the wrenching flanges without damaging the
wax coating. Before wrench tightening the sprinkler, the
jaws of the wrench are to be adjusted to just contact the
sprinkler wrenching flanges. After wrench tightening the
sprinkler, loosen the wrench jaws before removing the
wrench.

After  installation,  the sprinkler wrenching flanges and
frame arms must be inspected and the wax coating re-
touched (repaired) whenever the coating has been dam-
aged and bare metal is exposed. The wax coating on the
wrenching flanges can be retouched by gently applying a
heated 1/8 inch diameter steel rod to the areas of wax that
have been damaged, to smooth it back over areas where
bare metal is exposed.

NOTES

Only retouching of the wax coating applied to the wrenching

STAR SPRINKLER

Page 2

1-1.2.70

FIGURE 2

2.8 K-FACTOR, MODEL LD-2 PENDENT

SPRINKLER WITH #2085 RECESSED ESCUTCHEON

FIGURE 1

2.8 K-FACTOR, MODEL LD-2

STANDARD RESPONSE

PENDENT AND UPRIGHT SPRINKLERS

SPRINKLER

FACE OF

FITTING

SURFACE

MOUNTING

1/8"

(3.2 mm)

1-1/4" (31.8 mm)

1-3/4" (44.5 mm)

1/4" (6.4 mm)

3/4" (19.1 mm)

5/8±1/4"

(15.9±6.4 mm)

CLOSURE

PLATE

MOUNTING

LD-2

(57.2 mm)

2-1/4" DIA.

(73.0 mm)

2-7/8" DIA.

FLANGES

WRENCHING

PLATE

SEATING

1/2" NPT

ESCUTCHEON

SURFACE

2"

(50.8 mm)

(66.7 mm)

2-5/8"

7/16" (11.1 mm)

NOMINAL

MAKE-IN

WRENCHING

AREA

WRENCH

RECESS

WRENCH

RECESS

FIGURE 3

W-TYPE 9 (#1849) SPRINKLER WRENCH

AND

W-TYPE 10 (#1948) RECESSED SPRINKLER WRENCH

#1849

#1948

OBSOLETE