background image

the wetting (i.e., cold soldering) of the heat responsive
element (Bulb) of a non-operated Star Galaxy SG-R,
which is adjacent to one which has operated.

Heat Source Criteria.

Refer to NFPA 13D or NFPA 13R

for the requirements relating to preventing the possible re-
lease of a Star Galaxy SG-R heat responsive element
(Bulb), due to exposure to heat sources other than abnor-
mal fire.

INSTALLATION

The Star Galaxy SG-R must be installed in accordance
with the following instructions:

NOTES

Do not install any bulb type sprinkler if the bulb is
cracked or there is a loss of liquid from the bulb. With
the sprinkler held horizontally, a small air bubble with
an approximate diameter of 1/16 inch should be pre-
sent.

A leak tight 1/2 inch NPT sprinkler joint should be ob-
tained with a torque of 7 to 14 ft.lbs. (9,5 to 19,0 Nm).
A maximum of 21 ft.lbs. (28,5 Nm) of torque is to be
used to install sprinklers. Higher levels of torque may
distort the sprinkler inlet with consequent leakage or
impairment of the sprinkler.

Do not attempt to compensate for insufficient adjust-
ment in an Escutcheon Plate by under- or over-tight-
ening the Sprinkler. Readjust the position of the sprin-
kler fitting to suit.

1. The sprinkler must only be installed in the pendent position

and with the deflector parallel to the mounting surface.

2. After installing the #2084 mounting plate (or other accept-

able escutcheon, as applicable) over the sprinkler pipe
threads and with pipe thread sealant applied to the pipe
threads, hand tighten the sprinkler into the sprinkler fitting.

3. Wrench tighten the sprinkler using only a W-Type 9 Sprin-

kler Wrench (Ref. Figure 3) for pendent sprinkler installa-
tions or the W-Type 10 Wrench (Ref. Figure 4) for re-
cessed pendent sprinkler installations. The wrench recess
is to be applied to the sprinkler wrench flats (Ref. Figure
1).

STAR SPRINKLER

1-3.2.10

Page 3

FIGURE 3

W-TYPE 9

SPRINKLER

WRENCH

FIGURE 4

W-TYPE 10

RECESSED

SPRINKLER

WRENCH

WRENCH

RECESS

FIGURE 1

STAR GALAXY SG-R RESIDENTIAL

PENDENT SPRINKLER

2-3/16"

(55.7 mm)

WRENCHING

AREA

NOMINAL MAKE-IN

7/16" (11.1 mm)

(38.1 mm)

1-1/2"

PLATE

SEATING

ESCUTCHEON

SURFACE

NPT

1/2"

SPRINKLER

FACE OF

FITTING

SURFACE

MOUNTING

1/8"

(3.2 mm)

1" (25.4 mm)

1-1/4" (31.8 mm)

1/4" (6.4 mm)

1/2" (12.7 mm)

1/2±1/8"

(12.7±3.2 mm)

CLOSURE

PLATE

MOUNTING

2-1/4" DIA.

(57.2 mm)

(73.0 mm)

2-7/8" DIA.

SG-R

FIGURE 2

STAR GALAXY SG-R RESIDENTIAL SPRINKLER

WITH #2084 RECESSED ESCUTCHEON

OBSOLETE

Summary of Contents for Star Galaxy SG-R

Page 1: ...he above cited stipulations and the var ied nature of residential type architecture there will be some compartment designs which cannot be fully sprinklered in accordance with the recommendations of N...

Page 2: ...rge from each of the total number of design sprinklers as speci fied in NFPA 13D or 13R TIA 99 1 Tentative Interim Amendment with an effective date of May 22 2000 states that the minimum required disc...

Page 3: ...r tight ening the Sprinkler Readjust the position of the sprin kler fitting to suit 1 The sprinkler must only be installed in the pendent position and with the deflector parallel to the mounting surfa...

Page 4: ...STAR SPRINKLER Page 4 1 3 2 10 FIGURE 5 PLAN VIEW ILLUSTRATIONS OF SPRINKLER TO WALL AND SPRINKLER TO SPRINKLER POSITIONING O B S O L E T E...

Page 5: ...IRED HORIZONTAL DISTANCE BETWEEN TWO SPRINKLERS LOCATED ON THE SAME ELEVATION ON OPPOSING SLOPED CEILINGS FIGURE 7 MAXIMUM PERMITTED VERTICAL DISTANCE BETWEEN THE SPRINKLER DEFLECTOR AND THE BOTTOM OF...

Page 6: ...EQUIRED HORIZONTAL DISTANCE BETWEEN A SPRINKLER LOCATED ON A LEVEL CEILING AND AN INTERSECTING SLOPED CEILING FIGURE 9 MINIMUM REQUIRED SLANT DISTANCE BETWEEN A LEVEL CEILING AND A SPRINKLER LOCATED O...

Page 7: ...be painted plated coated or otherwise al tered after leaving the factory Modified sprinklers must be replaced Sprinklers that have been exposed to corro sive products of combustion but have not operat...

Page 8: ...le of products or parts of products Tyco Fire Products shall not be responsible for sprinkler sys tem design errors or inaccurate or incomplete information supplied by Buyer or Buyer s representatives...

Reviews: