Tyco Fire Product Gem TY-B Instruction Manual Download Page 6

thread sealant applied to the pipe
threads, hand tighten the sprinkler into
the sprinkler fitting.

Step B

. Tighten the sprinkler into the

sprinkler fitting using only the W-Type
7  Recessed Sprinkler Wrench  (Ref.
Figure 7). With reference to Figure 1 or
2, the W-Type 7 Recessed Sprinkler
Wrench is to be applied to the sprinkler
wrench flats.

Step C.

After the ceiling has been in-

stalled or the finish coat has been ap-
plied, slide on the Style 10 or 40 Clo-
sure over the Series TY-B Sprinkler
and push the Closure over the Mount-
ing Plate until its flange comes in con-
tact with the ceiling.

Care and
Maintenance

The Series TY-B Sprinklers must be
maintained and  serviced in accord-
ance with the following instructions:

NOTES

Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shut down the
affected fire protection system must be
obtained from the proper authorities
and all personnel who may be affected
by this action must be notified.

Absence of an escutcheon, which is
used to cover a clearance hole, may
delay the time to sprinkler operation in
a fire situation.

Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.

Automatic sprinklers must  never be
shipped or stored where their tempera-
ture will exceed 100°F/38°C and they
must never be painted, plated, coated
or otherwise altered after leaving the
factory. Modified sprinklers must be re-
placed. Sprinklers that have been ex-
posed to corrosive products of com-
bustion, but have not operated, should
be  replaced  if  they cannot  be  com-
pletely cleaned by wiping the sprinkler
with a cloth or by brushing it with a soft
bristle brush.

Care must be exercised to avoid dam-
age to the sprinklers - before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be re-
placed. Also, replace any sprinkler that
has a cracked bulb or that has lost
liquid from its bulb. (Ref. Installation
Section).

Frequent  visual inspections are rec-
ommended to be initially performed for

corrosion resistant coated sprinklers,
after  the  installation has  been com-
pleted, to verify the integrity of the cor-
rosion resistant coating. Thereafter,
annual inspections per NFPA 25
should suffice; however, instead of in-
specting from the floor level, a random
sampling of close-up visual inspec-
tions should be made, so as to better
determine the exact sprinkler condi-
tion and the long term integrity of the
corrosion resistant coating, as it may
be affected by the corrosive conditions
present.

The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in  compliance with this  docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
facturer should be contacted relative to
any questions.

It is recommended that automatic
spr inkler systems be inspected,
tested, and maintained by a qualified
Inspection Service.

Limited
Warranty

Products manufactured by Tyco Fire
Products are warranted solely to the
original Buyer for ten (10) years
against defects in material and work-
manship when paid for and properly
installed and maintained under normal
use and service. This warranty will ex-
pire ten (10) years from date of ship-
ment by Tyco Fire Products. No war-
ranty

is

given

for

products

or

components manufactured by compa-
nies not affiliated by ownership with
Tyco Fire Products or for products and
components which have been subject
to misuse, improper installation, corro-
sion, or which have not been installed,
maintained, modified or repaired in ac-
cordance with applicable Standards of
the National Fire Protection Associa-
tion, and/or the standards of any other
Authorities Having Jurisdiction. Mate-
rials found by Tyco Fire Products to be
defective shall be either repaired or
replaced, at Tyco Fire Products’ sole
option. Tyco Fire Products neither as-
sumes, nor authorizes any person to
assume for it, any other obligation in
connection with the sale of products or
parts of products. Tyco Fire Products
shall not be responsible for sprinkler
system design errors or inaccurate or
incomplete information supplied by
Buyer or Buyer’s representatives.

IN NO EVENT SHALL TYCO FIRE
PRODUCTS BE LIABLE, IN CON-
TRACT, TORT, STRICT LIABILITY OR
UNDER ANY OTHER LEGAL THE-
ORY, FOR INCIDENTAL, INDIRECT,
SPECIAL OR CONSEQUENTIAL
DAMAGES, INCLUDING BUT NOT
LIMITED TO LABOR CHARGES, RE-
GARDLESS OF WHETHER TYCO
FIRE PRODUCTS WAS INFORMED
ABOUT THE POSSIBILITY OF SUCH
DAMAGES, AND IN NO EVENT
SHALL TYCO FIRE PRODUCTS’ LI-
ABILITY EXCEED   AN   AMOUNT
EQUAL TO THE SALES PRICE.

THE FOREGOING WARRANTY IS
MADE IN LIEU OF ANY AND ALL
OTHER WARRANTIES EXPRESS OR
IMPLIED, INCLUDING WARRANTIES
OF MERCHANTABILITY AND FIT-
NESS FOR A PARTICULAR PUR-
POSE.

Page 6 of 8

TFP151

OBSOLETE

Summary of Contents for Gem TY-B

Page 1: ...te level version of the Series TY B Pendent Sprinkler can be obtained by utilizing the Series TY B Pendent Sprinkler in combination with the Model S2 Shield WARNINGS The Series TY B Sprinklers described herein must be installed and main tained in compliance with this docu ment as well as with the applicable standards of the National Fire Protec tion Association in addition to the standards of any ...

Page 2: ... orifice seat on frame Pipe thread connections per ISO 7 1 can be provided on special request 2 4 5 6 PENDENT CROSS SECTION 58 7 mm 2 5 16 39 7 mm 1 9 16 PLATE SEATING ESCUTCHEON 1 2 12 7 mm NOMINAL MAKE IN SURFACE 1 3 NPT 3 4 RECESSED PENDENT UPRIGHT 12 7 mm NOMINAL MAKE IN 1 2 RECESSED STYLE 40 ESCUTCHEON 57 2 mm 2 1 4 3 4 NPT DEFLECTOR SSU SSP DEFLECTOR 7 FLATS WRENCH 2 7 8 73 0 mm DIA FIGURE 2...

Page 3: ...position of the sprinkler fitting to suit The Series TY B Pendent and Up right Sprinklers must be installed in accordance with the following instruc tions Step 1 Pendent sprinklers are to be installed in the pendent position and upright sprinklers are to be installed in the upright position Step 2 With pipe thread sealant ap plied to the pipe threads hand tighten the sprinkler into the sprinkler f...

Page 4: ...orrosion Resistant Sprinklers Installed with Style 10 1 2 NPT or Style 40 3 4 NPT 3 4 Total Adjustment Recessed Escutcheon as applicable 150 F 66 C Maximum Ceiling Temperature White or Any Color Frame and Deflector only N A Not Available TABLE A LABORATORY LISTINGS AND APPROVALS 1 2 5 WAX OVER LEAD COATED LEAD COATED WAX COATED N A 1 2 3 5 1 2 3 5 1 2 3 5 1 2 3 5 1 2 3 5 N A 5 6 1 2 NPT PENDENT TY...

Page 5: ...gled downward and then touch the wax stick to the rod approximately one half inch away from the area re quiring retouching The wax will melt and run down onto the sprinkler The Series TY B Recessed Pendent Sprinklers must be installed in ac cordance with the following instruc tions Step A After installing the Style 10 or 40 Mounting Plate as applicable over the sprinkler threads and with pipe TFP1...

Page 6: ...pec tions should be made so as to better determine the exact sprinkler condi tion and the long term integrity of the corrosion resistant coating as it may be affected by the corrosive conditions present The owner is responsible for the in spection testing and maintenance of their fire protection system and de vices in compliance with this docu ment as well as with the applicable standards of the N...

Page 7: ...ify Specify color color coded Wax Stick for retouching specify tem perature rating temperature rated Se ries TY B Sprinklers P N specify Black for 135 F P N 56 065 1 135 Red for 155 F P N 56 065 1 155 Yellow for 175 F P N 56 065 1 175 Blue for 200 F and 286 F P N 56 065 1 286 NOTES Each wax stick is suitable for retouch ing up to twenty five sprinklers The wax used for 286 F sprinklers is the same...

Page 8: ...Page 8 of 8 TFP151 TYCO FIRE PRODUCTS 451 North Cannon Avenue Lansdale Pennsylvania 19446 O B S O L E T E ...

Reviews: