background image

INSTALLATION

NOTE

Do not install any bulb type sprinkler

if the bulb is cracked or there is a loss

of liquid from the bulb. With the

sprinkler held horizontal, a small air

bubble should be present. The diame-

ter of the air bubble is approximately

1/16 inch (1,6 mm) for the

155°F/68°C 200°F/93°C ratings.

The Model F892X Sprinklers must be
installed in accordance with the follow-
ing instructions.

1. With pipe thread sealant applied to

the pipe threads, hand tighten the
F892X Sprinkler into the sprinkler
fitting.

2. Using the W-Type 8 Sprinkler

Wrench (Ref. Fig. B) applied to the
sprinkler Wrench Flats (Ref. Fig. A),
tighten the F892X Sprinkler into the
sprinkler fitting.

NOTE

A leak tight 3/4 inch NPT sprin-

kler joint should be obtained with

a torque of 10 to 20 ft.lbs. (13,4 to

26,8 Nm). Higher levels of torque

may distort the sprinkler inlet

with consequent leakage or im-

pairment of the sprinkler.

CARE AND MAINTENANCE

Model F892X Sprinklers must be
maintained and serviced in accord-
ance with the following instructions:

NOTES

Before closing a fire protection system

control valve for maintenance work

on the fire protection system which it

controls, permission to shut down the

affected fire protection system must be

obtained from the proper authorities

and all personnel who may be affected

by this action must be notified.

Sprinklers which are found to be leak-
ing or exhibiting visible signs of corro-
sion must be replaced.

Automatic sprinklers must never be
shipped or stored where their tempera-
tures will exceed 100°F/38°C and they
must never be painted, plated, coated
or otherwise altered after leaving the
factory.  Modified sprinklers  must be
replaced.  Sprinklers that  have  been
exposed to corrosive products of com-
bustion, but have not operated, should
be  replaced  if they cannot  be  com-
pletely cleaned by wiping the sprinkler
with a cloth or by brushing it with a soft
bristle brush.

Care must be exercised to avoid dam-
age to the sprinklers — before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be re-
placed. Also, replace any sprinkler that
has a cracked bulb or that has lost
liquid from its bulb (ref. Installation
Section Note).

The owner is responsible for the in-
spection, testing, and maintenance of

their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
facturer should be contacted relative
to any questions.

It is recommended that automatic
sprinkler

systems

be

inspected,

tested, and maintained by a qualified
Inspection Service.

P S N 5 1 — X X X — X — X X X

155°F/68°C

155

TEMPERATURE

RATING

887

1

SPRINKLER

FINISH

TABLE B

PRODUCT SYMBOL NUMBER SELECTION

16.8 K-FACTOR MODEL F892X UPRIGHT

SPECIFIC APPLICATION STORAGE

SR UPRIGHT

200°F/93°C

200

NATURAL BRASS

TYPE

FIGURE B

W-TYPE 8 SPRINKLER

WRENCH

OBSOLETE

Close

Reviews: