Do not attempt to replace sprinklers
without first removing the fire protec-
tion system from service. Be certain
to secure permission from all
Authori-
ties Having Jurisdiction, and notify all
personnel who may be affected
during system shutdown. A fire
watch during maintenance periods is
a recommended precaution.
To remove the system from service
mode, first refer to the system
operating guide and valve instruction.
Drain water and relieve pressure in
the pipes. Remove the existing unit
and install the replacement, using
only the recommended sprinkler
wrench. Be certain to match model,
style, orifice, and temperature rating.
A fire protection system that has
been shut off after an activation
should be repaired and returned to
service immediately. Inspect the
entire system for damage and replace
or repair as necessary. Sprinklers
that did not operate but were sub-
jected to corrosive elements of
combustion or excessive tempera-
tures should be inspected, and
replaced if need be. The
Authority
Having Jurisdiction will detail mini-
mum replacement requirements and
regulations.
Guarantee: Central Sprinkler
Company will repair and/or replace
any products found to be defective in
material or workmanship within a
period of one year from the date of
shipment. Please refer to the current
Price List for further details of the
warranty.
©1998 Central Sprinkler Company
Printed in U.S.A.
Model A (RF).5
Central Sprinkler Company
451 North Cannon Avenue, Lansdale, PA 19446
PHONE (215) 362-0700
FAX (215) 362-5385
Ordering Information: When
placing an order, indicate the full
product name. Please specify the
quantity, model, style, orifice size,
temperature rating, sprinkler finish,
cover plate finish, and sprinkler
wrench.
For special painted cover plate
finishes, the customer must supply a
quick-drying paint, preferably in a
lacquer-base finish to insure proper
color duplication. Without such a
guide, Central Sprinkler Company
cannot be responsible for acceptable
color matching.
Availability and Service: Central
sprinklers, valves, accessories and
other products are available through-
out the U.S. and Canada, and
internationally, through a network of
Central Sprinkler distribution centers.
You may write directly to Central
Sprinkler Company, or call 215-362-
0700 for the distributor nearest you.
Patents: Patents are pending.
Conversion Table:
1 inch = 25.400 mm
1 foot = 0.3048 m
1 pound = 0.4536 kg
1 foot pound = 1.36 Nm
1 psi = 6.895 kpa
= 0.0689 bar
= 0.0703 kg/cm
2
1 U.S. gallon = 3.785 dm
3
= 3.785 liters
Conversions are approximate.
Ordering
Information
OBSOLETE