background image

General
Description

The Central Model K11 ECLH, 11.2
K-Factor, Quick Response, Extended
Coverage Light Hazard (ECLH) Pen-
dent and Recessed Pendent Sprin-
klers are decorative glass bulb sprin-
klers designed for use in light hazard
occupancies such as churches, hos-
pitals, offices, and restaurants.

They are intended for use in automat-
ic sprinkler systems designed in ac-
cordance with standard installation
rules (e.g., NFPA 13) for the protec-
tion of light hazards up to a maxi-
mum coverage area of 400 ft

2

(37,2

m

2

), as compared to the maximum

coverage area of 225 ft

2

(20,9 m

2

)

for standard coverage sprinklers.

The recessed version of the Models
K11 ECLH Sprinklers using a two-
piece Series 4221 Recessed Es-
cutcheon provides up to 1/2 inch
(12,7 mm) of total adjustment from
the flush pendent position. The ad-
justment provided by the Recessed
Escutcheon reduces the accuracy to
which the fixed pipe drops to the
sprinklers must be cut.

Operation.

The glass bulb contains

a fluid which expands when exposed
to heat. When the rated temperature
is reached, the fluid expands suffi-
ciently to shatter the glass bulb,
which then allows the sprinkler to ac-
tivate and flow water.

WARNINGS

The Model K11 ECLH Sprinklers de-
scribed herein must be installed and
maintained in compliance with this
document, as well as with the appli-
cable standards of the National Fire
Protection Association, in addition to
the standards of any other authori-
ties having jurisdiction. Failure to do
so may impair the integrity of these
devices.

The owner is responsible for main-

taining their fire protection system
and devices in proper operating con-
dition. The installing contractor or
sprinkler manufacturer should be
contacted relative to any questions.

Technical
Data

Sprinkler Identification Number

SIN C5232

Approvals

UL and C-UL Listed. FM Approved.
(Refer to Table A. The approvals ap-
ply only to the service conditions indi-
cated in the Design Criteria section.)

Maximum Working Pressure

175 psi (12,1 bar)

Pipe Thread Connection

3/4 inch NPT or ISO 7-R3/4

Nominal Discharge Coefficients

K = 11.2 GPM/psi

1/2

(161,3 LPM/bar

1/2

)

Temperature Ratings

135°F/57°C to 200°F/93°C

Finishes

Sprinkler: White Polyester, Chrome
Plated, Natural Brass
Recessed Escutcheon: White
Coated or Chrome Plated
(Other finishes are available on re-
quest.)

Physical Characteristics

The K11 ECLH utilizes a dezincifica-
tion resistant (DZR) bronze frame, a
brass button, and a 3 mm bulb. The
frame orifice is sealed with a gas-
keted spring plate (Belleville Seal)
consisting of a beryllium nickel disc
spring that is sealed on both its in-
side and outside edges with a Tef-
lon

†

gasket. The compression screw

is bronze, and the deflector is brass.

No. 2-6.1

K11 ECLH
Quick
Response
Pendent &
Rec. Pendent
Sprinklers

Model K11 ECLH

Quick Response
Extended Coverage
Light Hazard Sprinklers

Tyco Fire Products — www.centralsprinkler.com
451 North Cannon Avenue, Lansdale, Pennsylvania 19446
Customer Services/Sales: Tel: (215) 362-0700 / Fax: (215) 362-5385
Technical Services: Tel. (800) 381-9312 / Fax: (800) 791-5500

CENTRAL

K11 ECLH

2-01