Figure 1

ESLO-20 GB Extended Coverage Ordinary Hazard

Upright

2 1/4"(57.2 mm)

Diameter

3 1/8"

(79.4 mm)

2 3/8"

(60.3 mm)

(Ref.)

1" x 3/4"

(25mm x 20mm)

Reducing

Coupling

ESLO .70

Position of Deflector When Located Above Bottom of Beam

  Distance

Maximum Allowable

  From Sprinkler

Distance Deflector

to Near Side of

Above Bottom of

Beam

Beam

Less than 1'

(< 25.4 mm)

0"

1' to less than 1'-6"

(25.4 < 152.4 mm)

0"

1'-6" to less than 2'

(25.4-152.4 <0.6 m)

 1"

(25.4mm)

2' to less than 2'-6"

(0.6m < 0.8m)

 1"

(25.4mm)

2'-6" to less than 3'

(0.8m < 0.9m)

 1"

(25.4mm)

3' to less than 3'-6"

(0.9m < 1.1m)

 3"

(76.2mm)

3'-6" to less than 4'

(1.1m < 1.2m)

 3"

(76.2mm)

4' to less than 4'-6"

(1.2m < 1.4m)

 5"

(127mm)

4'-6" to less than 5'

(1.4m < 1.5m)

 7"

(177.8mm)

5' to less than 5'-6"

(1.5m < 1.7m)

7"

(177.8mm)

5'-6" to less than 6'

(1.7m < 1.8m)

7"

(177.8mm)

6' to less than 6'-6"

(1.8m < 2.0m)

9"

(228.6mm)

6'-6" to less than 7'

(2.0m < 2.1m)

11"

(279.4mm)

7' and greater

(< 2.1m)

14"

(355.6mm)

For SI Units: 1" = 25.4mm; 1' = 0.3048m

Beam

Ceiling

Not to Exceed Maximum

Specified for type of Construction

Distance from Near

Side of Beam

Maximum Distance Deflector

Above Bottom of Beam