Ordering Information:  When placing
an order, indicate the full product
name.  Please specify the quantity,
model, style, orifice size, temperature
rating, type of finish or coating, and
sprinkler wrench. Refer to price list for
complete listing of Part Numbers.

Teflon is a trademark of the DuPont Corp.

Ordering
Information

Care &
Maintenance

(Continued)

Sprinklers which are found to be
leaking or exhibiting visible signs of
corrosion must be replaced.

Automatic sprinklers must never be
shipped or stored where its tempera-
ture will exceed 100

°

F/38

°

C and they

must never be painted, plated, coated,
or otherwise altered after leaving the
factory. Modified sprinklers must be
replaced. Sprinklers that have been
exposed to corrosive products of
combustion, but have not operated,
should be completely cleaned by
wiping the sprinkler with a cloth or by
brushing it with a soft bristle brush.

Care must be exercised to avoid
damage - before, during, and after
installation. Sprinklers damaged by
dropping, striking, wrench twist/
slippage, or the like, must be re-
placed. Also, replace any sprinkler
that has a cracked bulb or that has
lost liquid from its bulb (Ref. Installa-
tion Section).
The Central Model BV-R1 must only
be replaced with pendent sprinklers
which are listed for residential fire
protection service and which have the
same nominal K-factor, the same
coverage area, and the same or lower
flow ratings (as indicated under
"Design Criteria").
When remodeling, such as by adding
false beams or light fixtures or
changing the location of compartment
walls, first verify that the new con-
struction will not violate the installation
requirements stated under WARN-
INGS. Alter the new construction and/
or the sprinkler system to suit the
requirements of this document.

The owner is responsible for the
inspection, testing, and maintenance
of their fire protection system and
devices in compliance with this
document, as well as with the appli-
cable standards of the National Fire
Protection Association (e.g., NFPA
25), in addition to the standards of any
other authorities having jurisdiction.
The installing contractor or sprinkler
manufacturer should be contacted
relative to any questions.

It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
Inspection Service.

Products manufactured by Tyco Fire
Products are warranted solely to the
original Buyer for ten (10) years
against defects in material and
workmanship when paid for and
properly installed and maintained
under normal use and service. This
warranty will expire ten (10) years
from date of shipment by Tyco Fire
Products. No warranty is given for
products or components manufac-
tured by companies not affiliated by
ownership with Tyco Fire Products or
for products and components which
have been subject to misuse, im-
proper installation, corrosion, or which
have not been installed, maintained,
modified or repaired in accordance
with applicable Standards of the
National Fire Protection Association,
and/or the standards of any other
Authorities Having Jurisdiction.
Materials found by Tyco Fire Products
to be defective shall be either repaired
or replaced, at Tyco Fire Products'
sole option. Tyco Fire Products
neither assumes, nor authorizes any
person to assume for it, any other
obligation in connection with the sale
of products or parts of products. Tyco
Fire Products shall not be responsible
for sprinkler system design errors or
inaccurate or incomplete information
supplied by Buyer or Buyer's repre-
sentatives.

IN NO EVENT SHALL TYCO FIRE
PRODUCTS BE LIABLE, IN CON-
TRACT, TORT, STRICT LIABILITY
OR UNDER ANY OTHER LEGAL
THEORY, FOR INCIDENTAL,
INDIRECT, SPECIAL OR CONSE-
QUENTIAL DAMAGES, INCLUDING
BUT NOT LIMITED TO LABOR
CHARGES, REGARDLESS OF
WHETHER TYCO FIRE PRODUCTS
WAS INFORMED ABOUT THE
POSSIBILITY OF SUCH DAMAGES,
AND IN NO EVENT SHALL TYCO
FIRE PRODUCTS' LIABILITY
EXCEED AN AMOUNT EQUAL TO
THE SALES PRICE.

THE FOREGOING WARRANTY IS
MADE IN LIEU OF ANY AND ALL
OTHER WARRANTIES EXPRESS
OR IMPLIED, INCLUDING WARRAN-
TIES OF MERCHANTABILITY AND
FITNESS FOR A PARTICULAR
PURPOSE.

Limited
Warranty

OBSOLETE

Summary of Contents for CENTRAL BV-R1

Page 1: ...ls They are to be used in wet pipe residential sprinkler systems for one and two family dwellings and mobile homes per NFPA 13D wet pipe residential sprinkler systems for residential occupancies up to...

Page 2: ...Pendent UL Specific Application Sloped Ceiling Hydraulic Design Requirements for NFPA 13D NFPA 13R Occupancies For use with Figure 4 Table 1 BV R1 Pendent Recessed Pendent Hydraulic Design Requirement...

Page 3: ...and with pipe thread sealant applied to the pipe threads hand tighten the sprinkler into the sprinkler fitting Step 3 Wrench tighten the sprinkler using only a BV Sprinkler Wrench 1099 Ref Figure 3 T...

Page 4: ...inimum of 4 verify G dimension minimum of 4 maximum 1 2 of the Listed spacing that the sprinkler was calculated for i e 18 x 18 spacing is maximum of 9 0 from a wall B For angles 0 to 39 minimum B 8 0...

Page 5: ...he minimum distance between sprinklers is measured horizon tally shown as dimension E Staggering the sprinklers will help maintain minimum horizontal distances in difficult situations Dimensions A and...

Page 6: ...secting a Flat Ceiling First verify that D is Acceptable or Obstructed per Figure 13 If Acceptable Figure 11 applies If Ob structed additional sprinklers will be necessary to protect the flat ceiling...

Page 7: ...s Obstructed 10 15 20 25 30 35 40 45 Acceptable 20 x 20 18 x 18 16 x 16 14 x 14 12 x 12 The Central Model BV R1 must be maintained and serviced in accordance with the following instructions NOTES Wet...

Page 8: ...standards of the National Fire Protection Association e g NFPA 25 in addition to the standards of any other authorities having jurisdiction The installing contractor or sprinkler manufacturer should b...