Make sure the remote control is not off.
1. Make sure no crossing of connections of the receiver or damper took place, e.g. receiver

no. 1 was connected to inlet T1 and  the damper is connected to inlet D2+ and D2-.

2. Make sure the connections of the receiver to the power supply box are orderly (see solution

no. 2).

3. If the connections were checked and were OK as detailed above, operate the damper with

the AUTO button on the receiver. If the damper reacts, check the batteries in the remote
control.

3.  Checking the Proper Installation of the System

3.1.1 Connections

Ascertain:
-

Receiver no. 1 (T1) is connected to entry no. 1 (T1) and motor no. 1 (T1) is connected to terminals D1 +, D1

-

Receiver no. 2 (T2) is connected to entry no. 2 (T2) and motor no. 2 (T2) is connected to terminals D2 +, D2 

-

Receiver no. 3 (T3) is connected to entry no. 3 (T3) and motor no. 3 (T3) is connected to terminals D3 +, D3 

-

Receiver no. 4 (T4) is connected to entry no. 4 (T4) and motor no. 4 (T4) is connected to terminals D4 +, D4 

-

With the connection of the power supply box to line voltage ensure that the red indicator light on the power
supply box is on.

-

Wait 70 seconds and switch the remote control off. Make sure that  the damper is switched off (closed). In case
the damper is open, cross the two wires that reach the motor or the two wire conneD and 

D.

-

Move between status 1/3 and 2/3 and make sure the damper actually moves.

3.1.2 Communication between Remote  Control and Receiver.
-

When finishing the installation of the receiver and the holder of the Remote Control unit, try to activate the
receiver with the remote control when it is still in the holder.

-

On the remote control press the ON button and check whether the red light on the receiver is blinking. The
blinking of the red on the Receiver informs that, the receiver absorbed the transmission from the remote control.

-

In case there is no red light blinking on the receiver, change the required temperature on the remote control
and/or transfer the operational status from heating to cooling. Then check once again if the red lamp is blinking
in the receiver. If the receiver is not blinking, change the location of the remote control holder.

-

Make sure to explain to the customer that the place for the remote control is in the holder unit. Keeping the
remote control in the holder, ensures the constant reception of reliable signals and enables a correct operation
of the system. In addition, this ensures the remote control will not be damaged.

3.2 Troubleshooting

Problem

Solution

The indicator lamp on the
power supply box is not on

Check for 230 V electricity outlet.
1.Check that the connection of the power supply box to the 230v.

No ON/STBY indicator
on the receiver is alight.

The damper does not
react in spite of switching
from 1/3 to 2/3 and
changing the MODE
(heating / cooling)

1. Make sure that the snap connections are connected properly to the receiver and to the power

supply box.

2. Ensure that the indicator light in the power supply box is on, if not see solution to problem

6

Summary of Contents for OPAL RC-11

Page 1: ...OPAL RC 11 Operating And Manual instructions...

Page 2: ...rs for quick and easy installation and optimum performance to assure perfect and uniform air conditioning Contents Part 1 Before Installation Part 2 Installation of Receiver for the Proportional Dampe...

Page 3: ...es to connect up to four remote controls and dampers to one power supply box and thus provides flexibility and comfort in installation according to the requirements on site The connection possibilitie...

Page 4: ...certified technician For the connection between the receiver and the power supply box use only cables with quick connecting connectors supplied by the manufacturer The connection to the supply voltag...

Page 5: ...nder the receiver It can also be installed in another place only in a straight visual line from the receiver For the installation of the remote control holder use two screws 2 1 2 Installation of the...

Page 6: ...r to the power supply box C315 4 four channels Connection diagrams Connection details Receiver connection Connection to motor Damper motor Power supply box Receiver T1 T2 T3 T4 D1 D1 D2 D2 D3 D3 D4 D4...

Page 7: ...n Remote Control and Receiver When finishing the installation of the receiver and the holder of the Remote Control unit try to activate the receiver with the remote control when it is still in the hol...

Page 8: ...C to 30 C Accuracy is 1 C Includes an internal temperature receiver Operates on heating and cooling Manual or Automatic mode 4 2 C315 Power Supply Box Characteristics Fire proof plastic V0 Protection...

Page 9: ...w the real time press SET 14 for setting the time The real time clock can also be set using the CLOCK button 12 and then the same procedure using the buttons 2 and SET 14 Please pay attention to the f...

Page 10: ...Mode Display Set Temperature Display Room Temperature icon Low battery icon Sleep mode icon Real time clock Display ON off Timers Display Real time clock button Timer select button Timer Set button R...

Page 11: ...temperature heat indicators on the I R receiver will light The OPERATION MODE should be always the same as the OPERATION MODE of the A C Unit The OPERATION MODE selected will be shown on the operatio...

Page 12: ...room button once again will show the set temperature SLEEP MODE This mode is designed to create comfortable sleeping conditions Pressing the sleep button 17 will activate the sleep mode In this mode w...

Page 13: ...operation of the Damper Press SET button 14 to activate the timer To set the ON timer press TIMER button 13 The ON icon on the ON OFF Timers Display 11 will blink Pressing the buttons will adjust the...

Page 14: ...the ON and OFF timers press TIMER button 13 The ON icon on the ON OFF Timers Display 11 will blink Press TIMER button 13 again The OFF icon on the ON OFF Timers Display 11 will blink And the ON icon w...

Page 15: ...ill show 00 blinking By pressing the code is selected The ID CODE range is from 00 to 08 Pressing SET button will store the ID CODE and the display is back to normal operation with the last temperatur...

Page 16: ...mote control is indicated by a blinking of the light led 2 3LIGHT LED The light indicates that the DAMPER unit is operating in MANUAL mode and the DAMPER is open Recieving signal from the Remote contr...

Page 17: ...Notes 16...

Page 18: ...Modular Damper OPAL C 128DD Wall mounted thermostat for propotional Modular Damper OPAL 650DD Flush Mount Electronic Thermostat for Propotional Modular Damper OPAL C 210RF Wall Thermostat Radio Freque...

Page 19: ...Also Available OPAL EL Opal 680 RF OPAL RC 11 Opal 650DD...

Reviews: