INSTALLATION
Connection of the safety heat exchanger (Quenching coil)
(Only for boilers provided with safety heat exchanger)
The boiler has a build-in safety
heat exchanger which cools the
boiler in case of pump failure or
the like. The system will be
activated if the water
temperature in the boiler
exceeds 95°C.
The thermal safety valve must
be connected to constant water
pressure from a G¾”/22mm
pipe. The water pressure must
be minimum 2 bar and the
temperature maximum 15°C
There must be no shutoff valves
on the pipe supplying the valve.
Flush the pipes before
connecting to the thermal safety
valve. Dirt or metal shavings
can cause the valve to
malfunction.
The return drain from the safety heat exchanger G¾” must be connected to a
drain.
The pipe used to connect to the drain must have a sufficient size to avoid the
emergence of backpressure.
After installation the system must be tested to ensure free passage trough the
safety heat exchanger. The thermal safety valve can be manually activated by
pressing the red cap.
Thermal safety valve - 95°C
Supply cold water for
quenching coil
Temperature sensor
for thermal safety valve
Drain from quenching coil