A high value = low O2 = fat combustion, where the flames have reddish / black
tips
A low value = high O2 = meagre combustion where the flames have yellow / blue
tips
When the boiler is running, you will read
O2 MAN
instead of
O2 Auto
in the display.
The measured O2 value is shown, but not used by the controller.
If the boiler is set to
Manuel operation
when set to the fuel type
Other
please be
aware, that the
Man. Fac.
value is a percentage of the stoker pulse, this means that
if the stoker pulse is increased the adjusted fuel amount will increase also
The real feeding time is calculated as : Stoker pulse x boiler load x Man. Fac.
Example
Stoker pulse adjusted : 1,1 sec.
Man. Fac. adjusted: 70%
Reel feeding = 1,1
0,7
0,65 = 0,5 second
Actual boiler load = 65%
The cursor must be placed by the line
Setting
Press
to choose
setting
Press
to
O2 regul. On/off
Press
to choose
O2 regulator menu
Press
to
Man. Fac.
Press
Now the amount of fuel can be adjusted between 0-100% by
Confirm the new setting with
Leave the menu by pressing
1.6 Adjustment of the fuel program “Other”
In the
Settings menu
under
Other fuel
you can adjust the relevant parameters
for the fuel program
Other
.
Before you begin to make a program for the alternative fuel type, you must
understand the importance of the 8 parameters to adjust
(see section 1.7 Parameter list)
The cursor must be placed by the line
Setting
Press
to choose
setting
Press
to
Other fuel
Press
to choose
Other fuel menu
The parameters are adjusted by pressing
at the current parameter, here after the
value can be set by pressing
Confirm the new setting with
Leave the menu by pressing
Section 1 – The control panel