Instructions Before Proceeding with DC Wiring 

The pump needs to be electrically bonded to a vehicle frame for mobile tanks or a ground rod for stationary tanks. To electrically bond pump for mobile 
application, remove the external factory installed green bonding screw located on the junction box cover (Diagram 3). Insert this screw through eyelet of 
furnished green bonding wire assembly and refasten it securely to the junction box. The other end of the wire is to be stripped of insulation and the bare wire 
securely bonded to the vehicle or on/off road trailer frame for mobile tanks (Diagram 4). For bonding with stationary tanks, attach a ground wire to a ground 
rod and the tank itself (Diagram 5). The distance may be greater than the supplied grounding wire.

DC Wiring Instructions 

Diagram 5

ATTACH GROUND WIRE 
TO GROUND ROD

1. Remove pump’s electrical junction box cover and straighten the red and black wire.
2. Screw the furnished cable connector into 1/2

"

 NPT conduit opening on the junction box.

3. Strip 3

"

 of the outer covering from one end of the furnished electrical supply cable.* Be careful not to damage the black and red wire insulation.

4. Loosen cable connector nut and pass the stripped end of the furnished cable through the cable connector. Tighten the cable connector nut.
5. Strip 1/2

"

 of the insulation from the ends of the red and black cable wires. Using the furnished wire nuts, connect the cable wires to the pump wires 

matching the colors.  

IMPORTANT: be sure no bare wire is exposed. 

6. Fold wires into junction box and replace, making sure the cover gasket is in place. Make sure all screws are seated so there is no space between the 

frame and the junction box (see Step 6 diagram on 

Page 6

). 

*12 AWG cable not supplied with pump only models

ATTACH GROUND WIRE TO VEHICLE BODY

½" NPT 

CONDUIT HOLE, 

THREADED

(2) T-25

TORX SCREWS

EXTERNAL GREEN 

GROUND SCREW

JUNCTION 

BOX GASKET

JUNCTION BOX CAP 

(CAN BE ROTATED 180°)

EARTH GROUND 

SYMBOL

Diagram 3

Diagram 4

Mobile Tank Wiring to a Vehicle Electrical System

 

1. Before electrical installation, place the switch lever into the OFF position to prevent accidental spillage once power is engaged to the motor.
2. Pass the electrical wires to the source of the vehicle power system, supporting as necessary and protecting them from sharp edges, heat, or anything 

that could cause damage.

3. To determine if the vehicle electrical system is negative (-) or positive (+) ground, check the battery marking of the terminal that is wired to the vehicle 

frame or motor block. The red wire from the pump will connect to positive battery post and the black wire from the pump will connect to negative battery 
post. These instructions focus on COMMON negative ground systems. UNCOMMON positive systems are a rare occurrence. Reference the drawing on 

Page 9

 for information on positive ground systems.  

4. Tuthill requires installing a fuse holder and fuse (not provided) for protection of the purchased pump. Attach one end of the fuse holder to the end of 

the ungrounded wire, making a solid connection. The other end of the fuse holder is then attached to the ungrounded side of the battery, as close to 
the battery as possible. Make a solid electrical connection to the grounded side of the battery with the remaining wire. Utilizing a battery terminal 
connection (not provided by Tuthill) is required for completion of the electrical circuit. 

5. Check all connections to make sure they are connected per instructions and all electrical codes. Install fuse (30 amp fuse for 12V DC; 20 amp fuse for 

24V DC) into the fuse holder. Installation is now complete.

Summary of Contents for FILL-RITE FR1200

Page 1: ...MADE IN USA H SERIES FUEL TRANSFER PUMPS FR1200 FR2400 FR4200 FR4400 FR600 SD1200 SD600 Installation and Operation Manual ...

Page 2: ...umber and purchase date of your fuel transfer pump Protect yourself as well as those around you by observing all safety instructions and adhering to all danger warning and caution symbols Please register your Fill Rite product via info tuthill com product_registration IMPORTANT RETURN POLICY Please do not return this product to the store For all warranty and product questions please contact Tuthil...

Page 3: ... from 20 to 34 inches in length allowing for universal installation on a multitude of tank sizes and shapes Not included with SD models Intake Strainer Safeguard Protects the pump by blocking particles created by contamination Certifications UL cUL Symbols and Definitions Indicates a hazardous situation which if not avoided will result in death or serious injury Indicates a hazardous situation whi...

Page 4: ...static wire conductive hose when pumping flammable liquid Improper mechanical installation or use can result in serious injury or death Never smoke around or near a fuel tank or transfer pump Open flames or a spark when pumping a flammable liquid will result in a fire Improper electrical wiring or installation will result in serious injury or death Threaded pipe joints and connections must be seal...

Page 5: ...an integral bypass valve to recirculate the fluid when the pump is operating with the nozzle closed Diagram 2 1 2 Min 1 2 Min Stationary Tank For stationary fuel tanks the pump mounts to the tank bung by way of the pump inlet flange Given the different sizes of stationary fuel tanks a custom suction or inlet pipe may be necessary We recommend 1 NPT black iron pipe that is extended to a length of a...

Page 6: ...5 screws and locate wires DC Voltage 2 wires Black and Red AC Voltage 3 wires Black White and Green which is attached to internal ground screw Ensure that gasket remains in place upon re attachment of junction box Step 6 Feed wires from power source through NPT opening into junction box For DC models use the black cable connector For AC models attach conduit directly to NPT opening Step 7 Nozzle b...

Page 7: ...ed for 24V DC Regardless of how supply line power is provided i e via a battery or hard line Tuthill requires the circuit contain a fuse to prevent against electrical shorts For 12V DC a 30 amp fuse is necessary while for the 24V DC circuit a 20 amp fuse Voltage drop in wiring varies depending on the distance from the battery to the pump and the gauge of the wire used If the distance is greater th...

Page 8: ...between the frame and the junction box see Step 6 diagram on Page 6 12 AWG cable not supplied with pump only models ATTACH GROUND WIRE TO VEHICLE BODY NPT CONDUIT HOLE THREADED 2 T 25 TORX SCREWS EXTERNAL GREEN GROUND SCREW JUNCTION BOX GASKET JUNCTION BOX CAP CAN BE ROTATED 180 EARTH GROUND SYMBOL Diagram 3 Diagram 4 Mobile Tank Wiring to a Vehicle Electrical System 1 Before electrical installati...

Page 9: ...f the wiring from the power source to the pump is greater than 18 refer to the applicable Electrical Code national international or local to ensure the wire is of the correct size for the application Negative Ground System Common This electrical system is common within most vehicles utilizing a 12V DC power source In this instance the positive battery terminal supplies power to all devices such as...

Page 10: ...dous locations Class I Division 1 It is highly recommended that any repairs be done by an authorized distributor to avoid voiding the warranty It is very important to maintain the explosion proof integrity of the motor and system components Electrical wiring should be performed ONLY by a licensed electrician in compliance with local state and national electrical codes NEC ANSI NFPA 70 NFPA30 and N...

Page 11: ...Be certain to properly insulate the connections with the appropriate wire nuts or other connectors Note the ground wire MUST be connected Ground wire connection is inside the junction box Diagram 6b 4 Fold the wires back into the junction box and replace the cover making sure the cover gasket is in place 115V AC Pump Junction Box FR SD600 Series AC Fuel Transfer Pumps 115V AC Wiring Diagram for FR...

Page 12: ...h or serious injury Troubleshooting The following troubleshooting guide is provided to offer basic diagnostic assistance in the event you encounter abnormal service from your Fill Rite fuel transfer pump If you have questions please feel free to contact Tuthill Customer Service at 1 800 634 2695 M F 8am 6pm EST EDT or by email at fillritesales tuthill com Please disconnect all power supply sources...

Page 13: ... Tuthill Customer Service at 1 800 634 2695 M F 8am 6pm EST EDT Motor stalls fuse blows thermal protector trips repeatedly Bypass valve sticking Remove and inspect valve must move freely and be free of debris Low voltage Check incoming supply line voltage Excessive rotor or vane wear Check rotor and vanes for excessive wear or damage Debris in pump cavity Clean debris from pump cavity Motor overhe...

Page 14: ...0 13 20 15 13 Bypass Pressure 16 PSI Minimum Dry Vac 5 IN HG At Sea Level 70 F 21 1 C Suction Lift 8 Maximum Outlet Head 37 Maximum Inlet 1 NPT Outlet 3 4 NPT 1 NPT 3 4 NPT 1 NPT 3 4 NPT Mount 2 NPT Inlet Bung Warranty Limited Lifetime Warranty 1 Year Limited Lifetime Warranty 1 Year Product Parts Product Materials Pump Housing Cast Iron Rotor Powdered Iron Vane Sintered Bronze Strainer Mesh Stain...

Page 15: ... H SERIES FUEL TRANSFER PUMPS INSTALLATION AND OPERATION MANUAL FR4200 Dimensions displayed in inches 3 4 4 3 2 5 8 4 13 0 11 1 4 2 8 4 2 5 4 3 11 8 13 7 FR1200 FR2400 FR4400 FR600 SD1200 and SD600 Dimensions displayed in inches ...

Page 16: ...07CL FR4204H Pump Only Model 12V DC 1 FR4210H Manual 12 Metal Telescoping 20 34 12 AWG at 18 FR4210HARC Auto Arctic 20 Swivel FR4210HB Ultra Hi Flow 12 FR4210HD Auto Diesel 12 FR4210HDS Auto Diesel 12 Swivel FR4210HBFQ Ultra Hi Flow 18 10 AWG at 25 with clamps Filter FR4210HN 12 AWG at 18 FR4211H Manual 12 901C FR4211HL Manual 12 901CL FR4211HLN 901CL FR4211HN 901C FR4219H Manual 12 TT10AN FR4406H...

Page 17: ...fillrite com tuthill com 17 H SERIES FUEL TRANSFER PUMPS INSTALLATION AND OPERATION MANUAL 1200 Series Performance Curve 2400 Series Performance Curve ...

Page 18: ...fillrite com tuthill com 18 H SERIES FUEL TRANSFER PUMPS INSTALLATION AND OPERATION MANUAL 4200 Series Performance Curve 4400 Series Performance Curve ...

Page 19: ...m 19 H SERIES FUEL TRANSFER PUMPS INSTALLATION AND OPERATION MANUAL 600 Series Performance Curve METER STRAIGHT PIPE FILTER HEAD STREET ELBOW NOZZLE FILTER HOSE STRAIGHT PIPE SWIVEL Proper Accessory Configuration Accessories ...

Page 20: ...erosene and Petroleum Oils compatible 12 FRH07512 FRH10012 14 FRH07514 FRH10014 20 FRH07520 FRH10020 Meter Mechanical 800 807CMK Gallons 807CLMK Liters 900 901CMK4200 Gallons 901CLMK4200 Liters Digital 900 900CD Programmable 900CDP Programmable with Integral Pulsar TT TT10AB BSPP Aluminum TT10ABC BSPP Nickel Plated TT10AN NPT Aluminum TT10ANC NPT Nickel Plated Swivel Multi Plane S075H1314 S100H131...

Page 21: ...ction Cover Kit Junction cover seal fasteners 4 KIT120SL Seal Kit O ring shaft seals retainer clip 5 KIT120BV Bypass Service Kit Bypass valve valve spring bypass cap O ring seal 6 KIT120NB Nozzle Boot Kit Nozzle boot attaching hardware 7 KIT120BG Inlet Flange Kit Inlet flange bung attaching hardware inlet seal screen 8 KIT120SG Inlet Gasket and Screen Gasket for inlet bung and screen 9 KIT120SWH S...

Page 22: ...ins affixed to the pump at all times Safety Testing Approvals The Fill Rite line of pumps have been safety tested for regulatory compliance This product family is approved by Underwriters Laboratories UL Tuthill Corporation 8825 Aviation Drive Fort Wayne Indiana 46809 USA P 800 634 2695 01 260 747 7524 F 800 866 4681 tuthill com fillrite com sotera com ...

Reviews: