For your safety

Intended use

The HMIs (Human Machine Interfaces) of the TX700 family are used to control, 

operate and monitor machine processes. 

The HMI/PLC operator panels of the F&B series are suitable for use in the F&B 

industry and comply with the standards and guidelines for hygienic design  

DIN EN1672-2 and EHEDG/FDA 21 CFR 177.2006. 

The devices may only be used as described in this manual. Any other use is not 

in accordance with the intended use. Turck accepts no liability for any resulting 

damage.

General safety instructions

 

The device may only be assembled, installed, operated, parameterized and 

maintained by professionally-trained personnel.

 

The device only meets the EMC requirements for industrial areas and is not 

suitable for use in residential areas.

 

The devices may only be used in accordance with applicable national and 

international regulations, standards and laws. 

 

Do not open the devices under voltage.

Product description

Device overview

See fig. 1

Functions and operating modes

The devices of the TX700 series combine control, operation and monitoring 

by a CODESYS V3 PLC with web visualization to a complete control unit. The 

CODESYS V3 control of the TX700 devices has the functions PROFINET controller, 

EtherNet/IP scanner and Modbus TCP as well as Modbus RTU master. Addi-

tionally the devices of the TX700 family can be used as Modbus TCP as well as 

Modbus RTU slave.

Additional functions

 

Ethernet TCP/IP or UDP/IP communication 

 

OPC-UA server and client, MQTT

 

Serial communication via RS232, RS485 and RS422

Installing

See fig. 2 and 3

A = TX7…

B = installation cut-out

 

Screw each fixing screw until the bezel corner gets in contact with the panel. 

The maximum tightening torque is 1.3 Nm.

 

Do not cover the ventilation slits in the device.

TX…

Brackets included in delivery

TX707FB

Connecting

Connectors and slots

See fig. 4

Connector/slot

Function

1

USB port , V2.0, max. 500 mA (for maintenance only)

Ethernet port 2 (10/100 Mbit) 

3

Ethernet port 1 (10/100 Mbit) 

4

Serial interface

5

Ethernet port 0 (10/100/1000 Mbit) 

6

Power supply

7

SD card slot

8

2 expansion slots for plug-in modules

NOTE

Devices of protection class III according to EN 61140 or Class 2 according to UL 

standards: All connections are SELV connections.

Power supply

 

Connect the device to the voltage supply according to fig. 5 and 6.

DANGER

Wrong selection of power supply

Danger to life due to overvoltage and electric shock!

Only operate devices at SELV power supplies.

Grounding the device

The minimum conductor cross-section for the ground connection is 1.5 mm².

 

Ground the housing via the grounding screw on the back of the housing.

 

Connect terminal 3 on the power supply terminal block to ground. 

Serial interface

See fig. 7

Pin

RS232

RS422/RS485

1

RxD

CHB-

2

TxD

CHA-

3

CTS

CHB+

4

RTS

CHA+

5

+5 VDC output

+5 VDC output

6

GND

GND

7

n.c.

n.c.

8

Shield

Shield

NOTE

When used as RS485 interface, pins 1 and 2 as well as pins 3 and 4 must be 

connected externally.

Maintenance

 

Clean the devices at regular intervals with a damp cloth.

Repair

The device must not be repaired by the user. The device must be decommis-

sioned if it is faulty. Observe our return acceptance conditions when returning 

the device to Turck.

Disposal

The device is equipped with a rechargeable lithium battery, which is not user 

replaceable.

 

For disposal, open the back of the device and remove the battery.

The device and the lithium battery must be disposed of properly in ac-

cordance with WEEE Directive 2012/19/EU and must not be included in 

general household garbage.

EN

Quick Start Guide

© Hans Turck GmbH & Co. KG | 1000015593 2020-11 DE EN FR 

Summary of Contents for TX707FB-P3CV01

Page 1: ...urable Max 3 serial ports using plug in modules SD card Yes Expansion 2 slots for max 4 plug in modules General Information Operating temperature 20 C 60 C vertical installation Plug in modules and USB devices may limit the max temperature to 50 C Storage temperature 20 C 70 C Relative humidity 5 85 RH non condensing Protection class IP69 front IP20 rear Dimenstions Housing W H 217 177 mm Installa...

Page 2: ...uausschnitt Jede der Schrauben anziehen bis die Ecken des Rahmens auf dem Panel aufliegen Das maximale Anzugsdrehmoment beträgt 1 3 Nm Lüftungsschlitze im Gerät nicht verdecken TX Halterungen im Lieferumfang TX707FB 4 Anschließen Anschlüsse und Steckplätze Siehe Abb 4 Anschluss Steckplatz Funktion 1 USB Port V2 0 max 500 mA nur für Wartung 2 Ethernet Port 2 10 100 Mbit 3 Ethernet Port 1 10 100 Mbi...

Page 3: ... out Screw each fixing screw until the bezel corner gets in contact with the panel The maximum tightening torque is 1 3 Nm Do not cover the ventilation slits in the device TX Brackets included in delivery TX707FB 4 Connecting Connectors and slots See fig 4 Connector slot Function 1 USB port V2 0 max 500 mA for maintenance only 2 Ethernet port 2 10 100 Mbit 3 Ethernet port 1 10 100 Mbit 4 Serial in...

Page 4: ...ue la tête de celle ci sera en contact avec l afficheur Le couple de serrage max est 1 3 Nm Ne pas couvrir les ouvertures de ventilation de l appareil TX Étriers de fixation fournis TX707FB 4 Raccordement Connecteurs et emplacements Voir fig 4 Connecteur emplacement Fonction 1 Port USB V2 0 max 500 mA pour la maintenance 2 Port Ethernet 2 10 100 Mbit 3 Port Ethernet 1 10 100 Mbit 4 Port série 5 Po...

Reviews: