TX707FB-P3CV01
HMI – TX707FB-P3CV01
Other documents
The following additional documents are available online at
www.turck.com
■
Data sheet
■
Instructions for use for TX series
■
EU declaration of conformity (current version)
For your safety
Intended use
The HMIs (Human Machine Interfaces) of the TX700 family are used to control,
operate and monitor machine processes.
The HMI/PLC operator panels of the F&B series are suitable for use in the F&B
industry and comply with the standards and guidelines for hygienic design
DIN EN1672-2 and EHEDG/FDA 21 CFR 177.2006.
The devices may only be used as described in this manual. Any other use is not
in accordance with the intended use. Turck accepts no liability for any resulting
damage.
General safety instructions
■
The device may only be assembled, installed, operated, parameterized and
maintained by professionally-trained personnel.
■
The device only meets the EMC requirements for industrial areas and is not
suitable for use in residential areas.
■
The devices may only be used in accordance with applicable national and
international regulations, standards and laws.
■
Do not open the devices under voltage.
Product description
Device overview
See fig. 1
Functions and operating modes
The devices of the TX700 series combine control, operation and monitoring
by a CODESYS V3 PLC with web visualization to a complete control unit. The
CODESYS V3 control of the TX700 devices has the functions PROFINET controller,
EtherNet/IP scanner and Modbus TCP as well as Modbus RTU master. Addi-
tionally the devices of the TX700 family can be used as Modbus TCP as well as
Modbus RTU slave.
Additional functions
■
Ethernet TCP/IP or UDP/IP communication
■
OPC-UA server and client, MQTT
■
Serial communication via RS232, RS485 and RS422
Installing
See fig. 2 and 3
A = TX7…
B = installation cut-out
➤
Screw each fixing screw until the bezel corner gets in contact with the panel.
The maximum tightening torque is 1.3 Nm.
➤
Do not cover the ventilation slits in the device.
TX…
Brackets included in delivery
TX707FB
4
Connecting
Connectors and slots
See fig. 4
Connector/slot
Function
1
USB port , V2.0, max. 500 mA (for maintenance only)
2
Ethernet port 2 (10/100 Mbit)
3
Ethernet port 1 (10/100 Mbit)
4
Serial interface
5
Ethernet port 0 (10/100/1000 Mbit)
6
Power supply
7
SD card slot
8
2 expansion slots for plug-in modules
NOTE
Devices of protection class III according to EN 61140 or Class 2 according to UL
standards: All connections are SELV connections.
Power supply
➤
Connect the device to the voltage supply according to fig. 5 and 6.
DANGER
Wrong selection of power supply
Danger to life due to overvoltage and electric shock!
➤
Only operate devices at SELV power supplies.
Grounding the device
The minimum conductor cross-section for the ground connection is 1.5 mm².
➤
Ground the housing via the grounding screw on the back of the housing.
➤
Connect terminal 3 on the power supply terminal block to ground.
Serial interface
See fig. 7
Pin
RS232
RS422/RS485
1
RxD
CHB-
2
TxD
CHA-
3
CTS
CHB+
4
RTS
CHA+
5
+5 VDC output
+5 VDC output
6
GND
GND
7
n.c.
n.c.
8
Shield
Shield
NOTE
When used as RS485 interface, pins 1 and 2 as well as pins 3 and 4 must be
connected externally.
Maintenance
➤
Clean the devices at regular intervals with a damp cloth.
Repair
The device must not be repaired by the user. The device must be decommis-
sioned if it is faulty. Observe our return acceptance conditions when returning
the device to Turck.
Disposal
The device is equipped with a rechargeable lithium battery, which is not user
replaceable.
➤
For disposal, open the back of the device and remove the battery.
The device and the lithium battery must be disposed of properly in ac-
cordance with WEEE Directive 2012/19/EU and must not be included in
general household garbage.
EN
Quick Start Guide
© Hans Turck GmbH & Co. KG | 1000015593 2020-11 DE EN FR