Appendix: designations and abbreviations
Abbreviation Meaning
DC
Diagnostic Coverage
HFT
Hardware failure tolerance
MTTF
D
Mean Time To Failure Dangerous
PFD
Probability of dangerous failure on demand
PFH
D
Average frequency of dangerous failure per hour
PL
Performance Level
SIL
Safety Integrity Level
11
Appendix: function tests
Ensure that the function test is only carried out by qualified personnel. A suggested function
test consists of the following steps:
Step
Action
1
Switch every safety related input at least once a year.
2
Control the switching behavior by monitoring the output circuits.
3
Observe the maximum duty cycle and the total operation time depending on
the selected PFD value.
4
If the maximum duty cycle is reached: Request the shutdown function in order
to check the function of the safety system.
Once the test has been completed, document and archive the results.