V01.10 | 2020/11
17
7.2
System commands
The device supports the following system commands (System Command).
General system commands (according to IO-Link specification)
Command
128
Device reset, the device is restarted.
130
Reset to factory settings
Manufacturer specific system commands
Command
Invert digital input
170
All inputs not inverted
171
All inputs inverted
Pulse stretching input
180
Deactivate pulse stretching for all channels
(standard pulse = 2.5 ms)
Command
Activate output
190
Configure all channels as input
191
Configure all channels as output
Manual output reset after overcurrent
200
Automatic output recovery after overcurrent for all channels
201
Manual output reset after overcurrent for all channels
Output After Error
210
All outputs set LOW after error
211
All outputs set HIGH after error
212
All outputs hold their current value after error